Download presentation
Published byEleanor King Modified over 9 years ago
1
SFT 2841 IN CONNECTED MODE Prepare setting files
2
Starting the application
Click on the icon Select the working language Choose the operating mode: connected point to point via the front panel via the network Same access for SFT disconnected
3
Connection via the network
Choice of the network If required: creation or modification of the network Connection to Sepam units via the network Starting of SFT 2841 software on the chosen station
4
SFT 2841 expert UMI The protection and parameter setting data may be saved. Reports may be edited.
5
PARAMETER SETTING Parameter setting
6
Current operation Metering and operating data Parameter setting
alarm messages tripping current number of operations logic status of inputs, outputs and LEDs Parameter setting of each protection function of control logic of general installation and Sepam data
7
Logipam Selection Choice in the list Apply Activate Delete
Download onto the PC Automatic updating
8
Logipam internal resources
internal bits counters clocks delays
9
General information on connected mode
Connection Sepam type Sepam name Code operating mode Remote control Internal clock
10
General diagnosis Series 20 General characteristics Sepam status
Software versions Sepam status Clock with time-setting Presence of modules Monitoring of communication exchanges
11
General diagnosis Series 40 General characteristics Sepam status
Software versions Sepam status Clock with time-setting Presence of modules Monitoring of communication exchanges
12
General diagnosis Series 80 General characteristics Sepam status
Software versions Sepam status Clock with time-setting Presence of modules Monitoring of communication exchanges
13
Diagnosis: LED, input and output status
Series 40 & 80 Display of LEDs Display of validated inputs Display of outputs Testing of 3s pulse outputs
14
Diagnosis: remote indication (TS) status
Series 40 & 80 Status transmitted via the communication link
15
Measurements Series 80 Network measurements: Current measurements rms
demand maximum residual additional Voltage measurements phase-to-neutral phase-to-phase positive-sequence negative-sequence Frequency measurement
16
Measurements: vector diagram
Series 80 Display voltage current Select scale référence
17
Power and energy measurements
Series 80 Power measurements active reactive apparent power factor Energy measurements
18
Temperature measurements
Series 80 MET 148 modules
19
Network diagnosis Series 80 Unbalance ratio Phase displacement
Number of trips Phase Earth Total Harmonic Distortion
20
Network diagnosis Series 80 Machine diagnosis
Differential measurements Phase angles Impedance measurements Thermal overload Running hours counter
21
Network diagnosis Series 80 Tripping contexts Selection by date
22
Switchgear diagnosis Series 80 Cumulative breaking current …
23
Alarm management Series 80 Current alarms Alarm history
Not acknowledged Clear Reset Alarm history 200 alarms
24
Disturbance recording
Series 80 Selection by date Voluntary trigger Recovery of recording
25
On-line help Series 80 On-line help
26
MAIN POINTS TO REMEMBER
27
Network diagnosis functions Tripping current
This function gives the RMS values of the phase currents and residual currents at time of the last trip. The measurement is defined as the maximum RMS value measured during a 30 ms interval after the activation of the O1 output. Acquisition of tripping current TRIPI1. RETURN
28
Machine operating assistance functions Current phase displacement
Current phase displacement between the main phase currents (I) and additional phase currents (I') (1, 2, 3) is calculated for each phase. The angle is measured in the clockwise direction. The information is used to check Sepam wiring when 87T protection functions are implemented. I I’1 RETURN
29
Metering functions Power factor (Cos)
This function gives the phase displacement between the phase currents and the phase-to-neutral voltages. The + and - signs and the IND (inductive) and CAP (capacitive) indications give the direction of power flow and the type of load. Q P +IND +CAP -CAP -IND V I RETURN
30
Network diagnosis functions Phase displacement
This function gives: phase displacement measured between the residual voltage and residual current in the trigonometric direction phase displacement between the V1, V2, V3 voltages and I1, I2, I3 currents respectively, in the trigonometric direction The measurements are used during Sepam commissioning to check that the voltage and current inputs are wired correctly. The angle is positive when the current is leading compared to the voltage (trigonometric direction). the angle is modified by 180° by the setting incomer / feeder. Io Vo 0 I V RETURN
31
Machine operating assistance Differential / through current
Differential / through current is calculated for the implementation of the differential protection functions 87T and 87M. It is calculated for each phase by: When a transformer is used (87T), the Idiff / It calculation takes into account the vector shift and transformation ratio.. The Idiff / It value is expressed with respect to In, the rated current of the main channels. It = max ( Iadjusted , I’adjusted ) Idiff = Iadjusted + I’adjusted RETURN
32
Metering functions Physical values measured
Sepam measures the following physical values: phase current (3I) residual current (Io) phase voltage (3V) residual voltage (Vo) Each measured signal is processed by Sepam to produce all the values necessary for the metering, diagnosis and protection functions. RETURN
33
Metering functions RMS measurement
RMS measurement is only used by the phase current metering function and for the thermal overload protection function (49). The RMS values take into account harmonics up the the 13th. For all other metering and diagnosis functions, the H1 fundamental 50 Hz or 60 Hz component is used. RETURN
34
Metering functions Residual current
This function gives the RMS value of the residual current obtained by: measurement: Io calculation of the sum of the phase currents: Io Accuracy at Ino: ±1%. Accuracy ± 2% from 0.3 to 1.5 Ino Accuracy ± 3% from 0.1 to 0.3 Ino The measurement range extends to 40 Ino when Io measurement is used. In the other cases, the range extends to 20 Ino. RETURN
35
Metering functions Demand phase current
5mn 55A 63A 89A 78A 59A 100A Demand current Resetting to zero: by the clear key on the display unit if one of the two screens is displayed, by the clear command in the SFT2841 software, via the communication link (remote control order TC4). RETURN
36
Metering functions Peak demand current
At the end of each integration period, i.e. once the new demand current values are available, the function determines the greatest demand current value obtained since the last reset. A t 55A 63A 89A 89A 89A 100A Peak demand current 5mn RETURN
37
Metering functions Phase-to-phase voltage
This function gives the RMS value of the 50 or 60 Hz component of the phase-to-phase voltages. U21 voltage between phases 2 and 1 (U21=V1-V2) U32 voltage between phases 3 and 2 (U32=V2-V3) U13 voltage between phases 1 and 3 (U13=V3-V1) by calculation when 3 phase-to-earth VTs are connected, by measurement (U21 and U32) and by calculation (U13) when 2 phase-to-phase VTs are connected, by measurement (U21) when only one phase-to-phase VT is connected, in which case the U32 and U13 voltages are not available. RETURN
38
Metering functions Frequency
This measurement is based on: U21 if only one phase-to-phase voltage is available, positive sequence voltage if the U21 and U32 measurements are available. The frequency is not displayed (replaced by ****) if: U21 or Vd is less than 40% of Un. frequency is out of range. Accuracy at Unp: ±0.01Hz 25 to 65 Hz range Sepam series40 and 80 45 to 55 Hz if 50Hz Sepam series 20 55 to 65 Hz if 60Hz Sepam series 20 RETURN
39
Metering functions Power factor (Cos)
Capacitive/inductive circuit: If V is leading compared to I, in the trigonometric (counter-clockwise) direction, then is positive. A capacitive (CAP) circuit is one in which the current is leading compared to the voltage ( <0). An inductive (IND) circuit is one in which the current is lagging compared to the voltage ( >0). V I CAP I IND V RETURN
40
Metering functions Active, reactive and apparent power
For an incoming circuit: Power supplied to the busbars is positive. Power supplied by the busbars is negative. For an outgoing circuit: Power supplied to the busbars is negative. Power supplied by the busbars is positive. Direction of power flow Direction of power flow P+ P+ RETURN
Similar presentations
© 2025 SlidePlayer.com. Inc.
All rights reserved.