Frankfurt (Germany), 6-9 June 2011 Achim Hobl – Germany – RIF Session 1 – 0352 – p 1 Nexans' Superconducting Fault Current Limiters for medium voltage applications - status and prospects - Achim Hobl, Joachim Bock, Simon Krämer, Markus Bludau, Judith Schramm, Christian Jänke, Steffen Elschner Nexans SuperConductors
2
Frankfurt (Germany), 6-9 June 2011 Achim Hobl – Germany – RIF Session 1 – 0352 – p 2 Contents Function of SFCL´s Possible installation sites SFCL Systems Perspectives for future grids
3
Frankfurt (Germany), 6-9 June 2011 Achim Hobl – Germany – RIF Session 1 – 0352 – p 3 Operating area of HTS devices operating area HTS FCL normal operationlimitation Transition faster due to temperature rise
4
Frankfurt (Germany), 6-9 June 2011 Achim Hobl – Germany – RIF Session 1 – 0352 – p 4 Resistive Limitation FCL Breaker Load + compact + intrinsically safe + strong limitation + independent of short circuit level – current leads to low temperature
5
Frankfurt (Germany), 6-9 June 2011 Achim Hobl – Germany – RIF Session 1 – 0352 – p 5 Inductive Limitation + no quench of the superconductor + can be without interruption – large volume and weight – low level of limitation – relatively high impedance FCL Load
6
Frankfurt (Germany), 6-9 June 2011 Achim Hobl – Germany – RIF Session 1 – 0352 – p 6 Function normal operationlimiting operation ultrafast reacts in 1-2 ms automatic no external trigger, self-recovering wear-free service only for cooling
7
Frankfurt (Germany), 6-9 June 2011 Achim Hobl – Germany – RIF Session 1 – 0352 – p 7 Installation sites Bus bar coupling In line (secondary side of transformer) House load protection in power plants (auxiliary power) FCL Transformerfeeder Busbarcoupler Highvoltage Medium voltage
8
Frankfurt (Germany), 6-9 June 2011 Achim Hobl – Germany – RIF Session 1 – 0352 – p 8 Advantages of the FCL system Passive limiting characteristics of the superconductor Inherently safe and free from wear and maintenance The power flow is not interrupted completely Less mechanical and thermal stress Higher network reliability Considerable cost savings Low impedance networks Voltage stability and reduction of harmonics Load levelling of busbars / transformers Customer benefits
9
Frankfurt (Germany), 6-9 June 2011 Achim Hobl – Germany – RIF Session 1 – 0352 – p 9 FCL Systems 12-100 (ASL 1) first commercial system Field tested for ~8 months 12-800 (Vattenfall) first system in a power station Field tested Nov. 2009 - Dec. 2010 XX-YYY XX: Voltage [kV] YYY: Current [A] 12-400 (ASL 2) second system for UK (bifilar) Delivered to UK April 2011
10
Frankfurt (Germany), 6-9 June 2011 Achim Hobl – Germany – RIF Session 1 – 0352 – p 10 12-100 ASL, Newcastle ENW, Bamber Bridge Live on grid 10-2009 to 06-2010
11
Frankfurt (Germany), 6-9 June 2011 Achim Hobl – Germany – RIF Session 1 – 0352 – p 11 12-400 Test at IPH Customer has ordered second system!
12
Frankfurt (Germany), 6-9 June 2011 Achim Hobl – Germany – RIF Session 1 – 0352 – p 12 12-800
13
Frankfurt (Germany), 6-9 June 2011 Achim Hobl – Germany – RIF Session 1 – 0352 – p 13 12-800 Power Plant Boxberg, Germany Supply for crushers and conveyor belts Nominal voltageU r = 12 kV Nominal currentI r = 800 A Inrush current, peaki max = 4100 A (50 ms) Inrush current, rmsI max = 1800 A (15 s) Prospective short currenti p = 63 kA (R/X=0.08) limited 1 st Peaki lim < 30 kA Limiting timet = 120 ms Operating temperatureT = 65 K
14
Frankfurt (Germany), 6-9 June 2011 Achim Hobl – Germany – RIF Session 1 – 0352 – p 14 Perspectives for future grids Low impedance networks WITH low short circuit power Supports integration of distributed generation Load / generation growth without substation upgrading Improvements in availability and stability
15
Frankfurt (Germany), 6-9 June 2011 Achim Hobl – Germany – RIF Session 1 – 0352 – p 15 Integration of distributed generation 110 kV 10 kV grid generator transformer G 5...50 MVA 10 kV FCL
16
Frankfurt (Germany), 6-9 June 2011 Achim Hobl – Germany – RIF Session 1 – 0352 – p 16 thank you for your attention power safety at its best