Equipment Use In Occupancies  A receptacle shall not be grouped or ganged in enclosures with other receptacles unless they are so arranged so that voltage.

Similar presentations


Presentation on theme: "Equipment Use In Occupancies  A receptacle shall not be grouped or ganged in enclosures with other receptacles unless they are so arranged so that voltage."— Presentation transcript:

1

2 Equipment Use In Occupancies

3  A receptacle shall not be grouped or ganged in enclosures with other receptacles unless they are so arranged so that voltage between adjacent devices does not exceed __________________ volts unless they are installed in enclosures equipped with identified, securely installed barriers between adjacent devices.

4  300 Volts  406.4 (G)

5  Flexible, fine-stranded cables used in PV systems shall be terminated only with terminals, lugs, devices or connectors that are ____________________________.

6  Identified and listed for such use  690.31 (F)

7  A disconnecting means shall be provided for all ungrounded conductors derived from a stationary battery system over __________ volts.

8  30 volts  480.5

9  A clearly labeled emergency shutoff or control switch for the purpose of stopping the motors that provide power to the recirculation system and jet system shall be installed at a point readily accessible to the users and not less than _________ feet away if a spa is installed in other than a single family dwelling.

10  5 feet  680.41

11  A 125V, 20 ampere rated receptacle installed in an agricultural livestock holding area which has an equipotential plane installed shall not require GFCI protection.  True  False

12  547.5 (G)(1)

13  A transformer insulated with a dielectric fluid indentified as nonflammable shall be permitted to be installed indoors or outdoors. Such transformers shall be installed in a vault if installed indoors and rated over ____________________ volts.

14  35000 volts  450.24

15  An electric radiant heating panel installed in poured concrete shall not exceed a rating of ___________ watts per square foot.

16  33 watts per square foot  424.98 (A)

17  The attachment plug cap for the power supply to a mobile home shall be a 3-pole, 4- wire, grounding type, rated _________ amperes if the mobile home is supplied with a power supply cord.

18  50 amperes  550.10 (A)

19  In one and two family dwellings, PV source circuits and PV output circuits that do not include lampholders, fixtures, or receptacles shall be permitted to have a maximum PV system voltage of ______________ volts.

20  600 Volts  690.7 (C)

21  In a Class I, Zone 0 hazardous location threaded entries into explosion proof or flame proof equipment by rigid metallic conduit shall be made up with at least ____________ threads fully engaged.

22  Five threads  505.9 (E)

23  When flexible cords are installed in an ambient temperature in excess of ________ degrees Fahrenheit, the ampacity of the conductors of the cord shall be derated.

24  86 degree F  400.5(A)

25  Panelboards equipped with snap switches rated at 30 amperes or less shall have a maximum overcurrent protection of _____________ amperes.

26  200 amperes  408.36 (A)

27  Fixed outdoor electric deicing and snow- melting equipment shall be considered as a ____________________ load.

28  Continuous  426.4

29  The maximum length of an extra hard usage type, 12 AWG flexible cord that will provide interconnection of partitions for office furniture shall be __________ feet.

30  2 feet  605.4 (3)

31  The minimum length of flexible cord used to provide power to a cord and plug connected, permanently installed trash compactor in a single family dwelling is ______________.

32  3 feet  422.16 (B)(2)(2)

33 STOP End of Timed Drill The drill slides will now be repeated without the timer. Left click on the presentation to advance to the next slide.

34  A receptacle shall not be grouped or ganged in enclosures with other receptacles unless they are so arranged so that voltage between adjacent devices does not exceed __________________ volts unless they are installed in enclosures equipped with identified, securely installed barriers between adjacent devices.

35  300 Volts  406.4 (G)

36  Flexible, fine-stranded cables used in PV systems shall be terminated only with terminals, lugs, devices or connectors that are ____________________________.

37  Identified and listed for such use  690.31 (F)

38  A disconnecting means shall be provided for all ungrounded conductors derived from a stationary battery system over __________ volts.

39  30 volts  480.5

40  A clearly labeled emergency shutoff or control switch for the purpose of stopping the motors that provide power to the recirculation system and jet system shall be installed at a point readily accessible to the users and not less than _________ feet away if a spa is installed in other than a single family dwelling.

41  5 feet  680.41

42  A 125V, 20 ampere rated receptacle installed in an agricultural livestock holding area which has an equipotential plane installed shall not require GFCI protection.  True  False

43  547.5 (G)(1)

44  A transformer insulated with a dielectric fluid indentified as nonflammable shall be permitted to be installed indoors or outdoors. Such transformers shall be installed in a vault if installed indoors and rated over ____________________ volts.

45  35000 volts  450.24

46  An electric radiant heating panel installed in poured concrete shall not exceed a rating of ___________ watts per square foot.

47  33 watts per square foot  424.98 (A)

48  The attachment plug cap for the power supply to a mobile home shall be a 3-pole, 4- wire, grounding type, rated _________ amperes if the mobile home is supplied with a power supply cord.

49  50 amperes  550.10 (A)

50  In one and two family dwellings, PV source circuits and PV output circuits that do not include lampholders, fixtures, or receptacles shall be permitted to have a maximum PV system voltage of ______________ volts.

51  600 Volts  690.7 (C)

52  In a Class I, Zone 0 hazardous location threaded entries into explosion proof or flame proof equipment by rigid metallic conduit shall be made up with at least ____________ threads fully engaged.

53  Five threads  505.9 (E)

54  When flexible cords are installed in an ambient temperature in excess of ________ degrees Fahrenheit, the ampacity of the conductors of the cord shall be derated.

55  86 degree F  400.5(A)

56  Panelboards equipped with snap switches rated at 30 amperes or less shall have a maximum overcurrent protection of _____________ amperes.

57  200 amperes  408.36 (A)

58  Fixed outdoor electric deicing and snow- melting equipment shall be considered as a ____________________ load.

59  Continuous  426.4

60  The maximum length of an extra hard usage type, 12 AWG flexible cord that will provide interconnection of partitions for office furniture shall be __________ feet.

61  2 feet  605.4 (3)

62  The minimum length of flexible cord used to provide power to a cord and plug connected, permanently installed trash compactor in a single family dwelling is ______________.

63  3 feet  422.16 (B)(2)(2)