UPS Topologies and Multi-Module Configurations
IEEE IAS Section Atlanta GA November 17, 2008
2
Agenda Line Interactive UPS UPS Topologies UPS Design Market Drivers
Delta Conversion UPS Double Conversion UPS Rotary UPS UPS Design Market Drivers UPS Components Multi-Module UPS Configurations
3
Critical Power System Critical Load Generation Power Quality
Distribution TVSS UPS PDU Servers Static Switch ATS Paralleling Switchgear
4
Line Interactive UPS
5
UPS Topologies – Line Interactive
Runs on AC power from Utility and switches to Inverter if Utility source power quality is not within predetermined tolerance. Provides some surge protection. Benefits – very efficient due to minimizing inverter run time Disadvantages – limited surge protection Application – Single computer or single rack
6
Delta Conversion
7
Delta Conversion This Line Interactive system carries the load by using both the utility line by means of a Line Conditioner (Course Regulation) and two converters (Actually two inverters for Fine Regulation & Battery Charger). This topology can regulate the load voltage by manipulating the secondary winding of the series t-former using the Series Converter. Advantages System does not go on battery for voltage fluctuations. System efficiency is higher in normal mode. Disadvantages The unit needs two inverters, less reliability. It circulates more ripple current to the batteries. If the utility frequency goes out of tolerance, the unit must go on batteries.
8
Double Conversion UPS
9
UPS Topologies – Double Conversion
Rectifies AC power into DC and then converts the DC back to AC. Provides clean power, completely isolated from the Utility during normal operation. Benefits – No interruption of Power; Protects load from Utility spikes and Surges Disadvantages – Greater losses than Line Interactive design
10
Rotary UPS
11
UPS Design Key Market Drivers
Reliability – The 5 “9’s” % up time Efficiency EPA Influence Green Grid Server Technology Voltage Outage Ride Through
12
Efficiency Line Interactive UPS ~98% efficient
Double Conversion ~ 92% to 94% efficient Methods to improve UPS efficiency Eliminate Input and Output Transformers “ECO” mode -Line interactive mode of operation Data Center Efficiency Trends Eliminate PDU transformers Electrical Distribution Voltages
13
ECO Mode Overview
14
Server Technology Server Voltages Today –120VAC - 240VAC
600V or 480V distribution with PDU transformers 400V distribution without PDU transformers Future – 277 VAC? ; 480VAC? Server Power Outage Ride Through CEMBA Curve – Now the “ITIC” Curve Key Factor for “ECO” mode.
15
CBEMA-ITIC Curve for Double Conversion UPS
16
UPS Components Rectifiers SCR or IGBT Inverters IGBT with PWM
SCR – 6 Pulse and 12 Pulse Inverters IGBT with PWM Static Switch Module Transformers Input Transformer Output Transformer Filters Input Harmonic Filters
17
Rectifiers IGBT Rectifier – Clean Input SCR Rectifiers
High power sinusoidal rectification – low harmonics, limited need for filters SCR Rectifiers 6 Pulse – ~30% THD without filters – 7% with 5th Harmonic Filter <5% with 5th and 11th filter 12 Pulse – reduces harmonics by using parallel rectifiers with a phase shift ahead of one rectifier – requires input transformer Lower efficiency than 6 Pulse Rectifiers can be programmed to sequentially ramp up
18
6 Pulse Current Input THD without filter THD with filter
19
12 Pulse Rectifiers
20
750 kVA - 6P vs 12P Rectifier – Energy Efficiency
Percentage load 6-Pulse - no Xfrmr 12-Pulse w/xfrmr 25% 92.8 % 91.8 % 50% 94.2 % 93.3 % 75% 93.2 % 100% 93.6 % 92.4 % Efficiency Difference 1.0 % 0.9 % 1.2 %
21
Inverters Converts DC power into AC using IGBTs and PWM
Several different methods to implement PWM
22
Static Switch Modules Static Switch Module consists of breaker or contactor in series with back to back SCRs. Static Switch modules can be continuous duty or momentary rated. Momentary rated Modules have a breaker or contactor in parallel. Continuous duty is required for ECO mode operation.
23
Input Isolation Transformer
Input Isolation Transformer – required for 12 Pulse Rectifier
24
UPS Output Transformer
Isolates load from inverter Provides greater protection to load during inverter failure Transformer MTBF > IGBT MTBF
25
Input Filters 5th Harmonic Cancellation Power Factor Correction
The filter is designed to cancel the current distortion that is most present on the 5th harmonic. Power Factor Correction The input filter also raises the input pf to approximately 0.93 with addition of capacitors. This will allow the generator to operate more efficiently delivering more real power
26
Multi-Module UPS Configurations
Paralleling UPS Modules Capacity or Redundancy Centralized Bypass Distributed Bypass Typical Parallel UPS Configurations Isolated Redundant Parallel Redundant Distributed Redundant System plus System
27
Parallel for Capacity Parallel for capacity reduces MTBF value
Multiple units = N Not recommended for a N System (single system) Frequently used for System + System (N+N) MTBF impact Parallel for capacity reduces MTBF value Approximately half the MTBF of a single unit
28
Centralized Bypass
29
Distributed Bypass 29
30
Centralized Bypass Cabinet
Distributed Bypass Configuration does not need this gear lineup
31
Parallel UPS Configurations
Isolated Redundant Parallel Redundant Distributed Redundant System plus System
32
Isolated Redundant
33
Parallel Redundant
34
Distributed Redundant
35
System + System