Frankfurt (Germany), 6-9 June 2011 Luciano Martini – IT – RIF S1 – Paper 1162 The ECCOFLOW EU FP7 Project: Design and Simulations Results of a Superconducting Fault Current Limiter for Operation in Electricity Networks Luciano MARTINI*, Mathias NOE #, Pascal TIXADOR°, Achim HOBL §, Marco BOCCHI* * RSE – Italy # KIT – Germany ° Grenoble INP – France § Nexans SuperConductors – Germany
2
Frankfurt (Germany), 6-9 June 2011 The Superconducting Fault Current Limiter The FP7 EU Project ECCOFLOW Participants and objectives Site installations SFCL Specifications SFCL Device Conceptual Design Short-circuit Simulation Results OUTLINE Luciano Martini – IT – RIF S1 – Paper 1162
3
Frankfurt (Germany), 6-9 June 2011 Luciano Martini – IT – RIF S1 – Paper 1162 Major Benefits from SFCL Applications
4
Frankfurt (Germany), 6-9 June 2011 Luciano Martini – IT – RIF S1 – Paper 1162 FP7 EU Project ECCOFLOW
5
Frankfurt (Germany), 6-9 June 2011 Luciano Martini – IT – RIF S1 – Paper 1162 FP7 EU Project ECCOFLOW www.eccoflow.org
6
Frankfurt (Germany), 6-9 June 2011 Luciano Martini – IT – RIF S1 – Paper 1162 FP7 EU Project ECCOFLOW
7
Frankfurt (Germany), 6-9 June 2011 Luciano Martini – IT – RIF S1 – Paper 1162 FP7 EU Project ECCOFLOW
8
Frankfurt (Germany), 6-9 June 2011 Luciano Martini – IT – RIF S1 – Paper 1162 Site 1Site 2ECCOFLOW Nominal Voltage (kV)16.5242400 Nominal Current (A)10001005100500 Short Circuit Current (kA)21.725.625.600 Max. Limited first peak (kA)10.81710.800 Recovery Time (s)< 30 < 3000 AC withstand Voltage (kV)50 5000 Lightning Impulse (kV)125 12500 Main specifications for both SFCL locations SFCL Specifications
9
Frankfurt (Germany), 6-9 June 2011 Luciano Martini – IT – RIF S1 – Paper 1162 Conceptual sketch of the SFCL system including all major parts in a single-phase line diagram SFCL Device Conceptual Design
10
Frankfurt (Germany), 6-9 June 2011 Luciano Martini – IT – RIF S1 – Paper 1162 Limited current and SFCL temperature after a 120 ms fault transient, as function of shunt impedance Simulation Results
11
Frankfurt (Germany), 6-9 June 2011 Luciano Martini – IT – RIF S1 – Paper 1162 3-phase fault (V=24 kV, Inom=1 kA, ISC=12 kA rms ): Evolution of ILim, ISC and THTS Short-circuit Simulation Results
12
Frankfurt (Germany), 6-9 June 2011 This work is funded by the European Union Seventh Framework Program (FP7/2007-2013) under the grant agreement No. 241285. The authors would like to thank: K. de Tessieres and J. Bock (Nexans) J. Frau Valenti (ENDESA) and M. Fedorko (VSE) for providing the network installation information Acknowledgments Luciano Martini – IT – RIF S1 – Paper 1162
13
Frankfurt (Germany), 6-9 June 2011 Luciano Martini – IT – RIF S1 – Paper 1162