Detailed Program March 2011 to September 2011 goal – allow the winery to be self-sustainable in water & energy.

Similar presentations


Presentation on theme: "Detailed Program March 2011 to September 2011 goal – allow the winery to be self-sustainable in water & energy."— Presentation transcript:

1

2 Detailed Program March 2011 to September 2011 goal – allow the winery to be self-sustainable in water & energy

3 Best Value Competition June 2011 to January 2012 Advertisement & Prequalification 17 Teams submit Prequalification Packets, June 2011 Prequalification consists of required elements (pass/fail) and scoring (48 points possible) based on experience of team and individuals 5 Teams interviewed, August 2011 Design Build Competition 3 Teams selected to prepare designs and bid price Two one-on-one sessions with each team, Nov & Dec 2011 Bids Received Bid date, January 2012 Detailed evaluation with points awarded Best value price determined

4 Project Award March 2012

5

6

7

8

9 Passive Design clerestory windows and shading devices

10

11

12 Optimize Design reduce loads insulate well daylight reduce infiltration address thermal breaks passive cooling

13 WALL Exterior Wall 4 inch insulated wall panel over Snap-R 1 inch EPS spacer over 10 inch girt (11in batt insulation) = R-55.7

14 ROOF Roof 6 inch insulated roof panel over 12 inch metal girt with batt insulation = R-70

15 specified double wall insulated dampers on all envelope penetrations provided thermal and load bearing insulation pads at structural steel connections Thermal Bridging

16

17 Challenges: maintain building interior temperature between 50 and 80 degrees F WITHOUT the use of any active mechanical systems net zero site energy Software Selection: IES vs Epro Thermal / Energy Modeling

18 Where to Look? Net Zero Energy Building Tip: Understand building physics Infiltration Opaque Envelope Windows

19 Infiltration construct an airtight building followed ASTM E1827-11 single point method for air tightness looking for rate less than 0.1 cfm/sf door blower test, identify leaks with smoke guns actual leakage 0.08 cfm/sf

20 once load reduced, use night flush through one fan with thermal storage in internal concrete walls and slab Net Zero Energy Building Tip: Understand micro climate Mechanical Solution

21 Temperature Results

22

23 Energy Results

24 If 6 months results are extrapolated to one year, Total Building Energy consumption = 3,588 kWh That is 1.44 kBtu/sq.ft-year Modeled was 1.66kBtu/sq.ft-year Energy Results Net Zero Energy Building Tip: Model accurately

25


Download ppt "Detailed Program March 2011 to September 2011 goal – allow the winery to be self-sustainable in water & energy."