Presentation is loading. Please wait.

Presentation is loading. Please wait.

Carbon Reduction Strategies at the University of East Anglia

Similar presentations


Presentation on theme: "Carbon Reduction Strategies at the University of East Anglia"— Presentation transcript:

1 Carbon Reduction Strategies at the University of East Anglia
NBS-M Carbon Reduction Strategies at the University of East Anglia Recipient of James Watt Gold Medal 2007 N.K. Tovey (杜伟贤) M.A, PhD, CEng, MICE, CEnv Н.К.Тови М.А., д-р технических наук School of Environmental Sciences / Norwich Business School

2 Original buildings Teaching wall Library Student residences
This is an ariel view of the University campus The University was established in 1963 The original buildings are outlined in red

3 Nelson Court Constable Terrace

4 Low Energy Educational Buildings
Thomas Paine Study Centre Nursing and Midwifery School ZICER Medical School Elizabeth Fry Building Medical School Phase 2 You can see that the University has expanded in size In recent years 4 educational building have been built on the campus to strenuous green design guidelines – all of which have the same construction type EFRY – 1995 Medical School – 2001 ZICER – 2003 Nursing and Midwifery – 2005 This talk focuses on the third building – the ZICER building 4 4

5 The Elizabeth Fry Building 1994
Cost 6% more but has heating requirement ~25% of average building at time. Building Regulations have been updated: 1994, 2002, 2006, but building outperforms all of these. Runs on a single domestic sized central heating boiler. Would have scored 13 out of 10 on the Carbon Index Scale. 8

6 Constable Terrace - 1993 Four Storey Student Residence
Divided into “houses” of 10 units each with en-suite facilities Heat Recovery of body and cooking heat ~ 50%. Insulation standards exceed 2006 standards Small 250 W panel heaters in individual rooms.

7 Educational Buildings at UEA in 1990s
Elizabeth Fry Building 1994 Queen’s Building 1993 Elizabeth Fry Building Employs Termodeck principle and uses ~ 25% of Queen’s Building

8 Conservation: management improvements –
User Satisfaction thermal comfort % air quality % lighting % noise % Careful Monitoring and Analysis can reduce energy consumption. A Low Energy Building is also a better place to work in

9 ZICER Building Low Energy Building of the Year Award 2005 awarded by the Carbon Trust. Heating Energy consumption as new in 2003 was reduced by further 50% by careful record keeping, management techniques and an adaptive approach to control. Incorporates 34 kW of Solar Panels on top floor

10 The first floor open plan office The first floor cellular offices
The ZICER Building – Main part of the building High in thermal mass Air tight High insulation standards Triple glazing with low emissivity ~ equivalent to quintuple glazing The first floor open plan office High in thermal mass – lots and lots of concrete. The external walls are built out of dense concrete blocks with a thickness of 23cm. All the ceilings are concrete blocks. Air tight – very little air leakage in and out of the building. So if you put heat into the building it actually stays within the building without escaping through gaps in the structure. High insulation standards - that exceed the current UK building regulations Triple glazing windows with low e – effectively the equivalent to quadruple glazing The main part of the building includes Basement …. The first floor cellular offices

11 Regenerative heat exchanger Incoming air into the AHU
Operation of Main Building Mechanically ventilated that utilizes hollow core ceiling slabs as supply air ducts to the space Regenerative heat exchanger Incoming air into the AHU 11 11

12 Air passes through hollow cores in the ceiling slabs
Operation of Main Building Filter 过滤器 Heater 加热器 Air passes through hollow cores in the ceiling slabs 空气通过空心的板层 Air enters the internal occupied space 空气进入内部使用空间 12 12

13 Recovers 87% of Ventilation Heat Requirement.
Operation of Main Building Recovers 87% of Ventilation Heat Requirement. Space for future chilling 将来制冷的空间 Out of the building 出建筑物 The return air passes through the heat exchanger 空气回流进入热交换器 Return stale air is extracted from each floor 从每层出来的回流空气 13 13

14 Operation of Regenerative Heat Exchangers
Stale air passes through Exchanger A and heats it up before exhausting to atmosphere Fresh Air is heated by exchanger B before going into building B Fresh Air Stale Air A 14 14

15 After ~ 90 seconds the flaps switch over
Operation of Regenerative Heat Exchangers After ~ 90 seconds the flaps switch over Stale air passes through Exchanger B and heats it up before exhausting to atmosphere Fresh Air is heated by exchanger A before going into building B Fresh Air Stale Air A 15 15

16 Fabric Cooling: Importance of Hollow Core Ceiling Slabs
Hollow core ceiling slabs store heat and cool at different times of the year providing comfortable and stable temperatures Warm air Heat is transferred to the air before entering the room Slabs store heat from appliances and body heat. 热量在进入房间之前被传递到空气中 板层储存来自于电器以及人体发出的热量 Air Temperature is same as building fabric leading to a more pleasant working environment Winter Day

17 Fabric Cooling: Importance of Hollow Core Ceiling Slabs
Hollow core ceiling slabs store heat and cool at different times of the year providing comfortable and stable temperatures Cold air In late afternoon heating is turned off. Heat is transferred to the air before entering the room Slabs also radiate heat back into room 热量在进入房间之前被传递到空气中 板层也把热散发到房间内 Winter Night

18 Fabric Cooling: Importance of Hollow Core Ceiling Slabs
Hollow core ceiling slabs store heat and cool at different times of the year providing comfortable and stable temperatures Cool air Draws out the heat accumulated during the day Cools the slabs to act as a cool store the following day 把白天聚积的热量带走。 冷却板层使其成为来日的冷 存储器 night ventilation/ free cooling Summer night

19 Fabric Cooling: Importance of Hollow Core Ceiling Slabs
Hollow core ceiling slabs store heat and cool at different times of the year providing comfortable and stable temperatures Warm air Slabs pre-cool the air before entering the occupied space concrete absorbs and stores heat less/no need for air-conditioning 空气在进入建筑使用空间前被 预先冷却 混凝土结构吸收和储存了热量 以减少/停止对空调的使用 Summer day

20 Good Management has reduced Energy Requirements
Space Heating Consumption reduced by 57% 能源消耗(kWh/天) 800 350 原始供热方法 新供热方法 20 20

21 Life Cycle Energy Requirements of ZICER compared to other buildings
建造209441GJ 自然通风221508GJ 54% 28% 51% 34% 使用空调384967GJ Materials Production 材料制造 Materials Transport 材料运输 On site construction energy 现场建造 Workforce Transport 劳动力运输 Intrinsic Heating / Cooling energy 基本功暖/供冷能耗 Functional Energy 功能能耗 Refurbishment Energy 改造能耗 Demolition Energy 拆除能耗 29% 61%

22 Life Cycle Energy Requirements of ZICER compared to other buildings
Compared to the Air-conditioned office, ZICER as built recovers extra energy required in construction in under 1 year.

23 Photo shows only part of top Floor
ZICER Building Photo shows only part of top Floor Mono-crystalline PV on roof ~ 27 kW in 10 arrays Poly- crystalline on façade ~ 6.7 kW in 3 arrays

24 Arrangement of Cells on Facade
Individual cells are connected horizontally Cells active Cells inactive even though not covered by shadow If individual cells are connected vertically, only those cells actually in shadow are affected. As shadow covers one column all cells are inactive 24 24 24

25 Performance of PV cells on ZICER
All arrays of cells on roof have similar performance respond to actual solar radiation The three arrays on the façade respond differently

26 Orientation relative to True North

27

28 Use of PV generated energy
Peak output is 34 kW 峰值34 kW Sometimes electricity is exported Inverters are only 91% efficient Most use is for computers DC power packs are inefficient typically less than 60% efficient Need an integrated approach

29 Original Way Heat was supplied to UEA campus
Three 8MW oil fired boilers – 85% efficient on full load, but only ~25% on low load. Heat distributed via ~ 4 km of pipe work which was originally poorly insulated leading to losses of 500 kW or more – now ~ 200 kW. ~ 1984 small 4 MW boiler added for use at times of low demand 1987 all boilers converted to run on either gas or oil 1998 – one boiler removed and 3 CHP units installed 2004 – absorption chiller installed to provide cooling throughout campus

30 Exhaust Heat Exchanger
Conversion efficiency improvements – Building Scale CHP 3% Radiation Losses Localised generation makes use of waste heat. Reduces conversion losses significantly 61% Flue Losses Exhaust Heat Exchanger 11% Flue Losses 36% 86% Gas 50% Heat Engine Generator Heat Exchanger 36% Electricity

31 UEA’s Combined Heat and Power
3 units each generating up to 1.0 MW electricity and 1.4 MW heat

32 Conversion efficiency improvements Before installation
1997/98 electricity gas oil Total MWh 19895 35148 33 Emission factor kg/kWh 0.46 0.186 0.277 Carbon dioxide Tonnes 9152 6538 9 15699 After installation Electricity Heat 1999/ 2000 Total site CHP generation export import boilers CHP oil total MWh 20437 15630 977 5783 14510 28263 923 Emission factor kg/kWh -0.46 0.46 0.186 0.277 CO2 Tonnes -449 2660 2699 5257 256 10422 This represents a 33% saving in carbon dioxide 32

33 Trailblazing to a Low Carbon Future
Low Energy Buildings Photo-Voltaics Low Energy Buildings Absorption Chilling Advanced CHP using Biomass Gasification World’s First MBA in Strategic Carbon Management Low Energy Buildings Effective Adaptive Energy Management Photovoltaics Combined Heat and Power Efficient CHP Absorption Chilling 33 33 33

34 Load Factor of CHP Plant at UEA
Conversion efficiency improvements Load Factor of CHP Plant at UEA Demand for Heat is low in summer: plant cannot be used effectively More electricity could be generated in summer 34 34

35 Heat extracted for cooling
冷凝器 绝热 Condenser Heat rejected 高温高压 High Temperature High Pressure 节流阀 Throttle Valve 低温低压 Low Temperature Low Pressure Compressor 压缩器 蒸发器 为冷却进行热提取 Evaporator Heat extracted for cooling A typical Air conditioning/Refrigeration Unit

36 Heat from external source Heat extracted for cooling
Absorption Heat Pump 外部热 Heat from external source 冷凝器 绝热 Condenser Heat rejected 高温高压 High Temperature High Pressure 吸收器 热交换器 Absorber Desorber Heat Exchanger 节流阀 Throttle Valve 蒸发器 为冷却进行热提取 Evaporator Heat extracted for cooling 低温低压 Low Temperature Low Pressure W ~ 0 Adsorption Heat pump reduces electricity demand and increases electricity generated

37 A 1 MW Adsorption chiller
Uses Waste Heat from CHP provides most of chilling requirements in summer Reduces electricity demand in summer Increases electricity generated locally Saves ~500 tonnes Carbon Dioxide annually

38 The Future: Biomass Advanced Gasifier/ Combined Heat and Power
Addresses increasing demand for energy as University expands Will provide an extra 1.4MW of electrical energy and 2MWth heat Will have under 7 year payback Will use sustainable local wood fuel mostly from waste from saw mills Will reduce Carbon Emissions of UEA by ~ 25% despite increasing student numbers by 250%

39 Trailblazing to a Low Carbon Future
Photo-Voltaics Efficient CHP Absorption Chilling Advanced Biomass CHP using Gasification 39

40 Trailblazing to a Low Carbon Future
Efficient CHP Absorption Chilling 1990 2006 Change since 1990 2011 Students 5570 14047 +152% 16000 +187% Floor Area (m2) 138000 207000 +50% 220000 +159% CO2 (tonnes) 19420 21652 +11% 14000 -28% CO2 kg/m2 140.7 104.6 -25.7% 63.6 -54.8% CO2 kg/student 3490 1541 -55.8% 875 -74.9% 40

41 Results of the “Big Switch-Off”
Target Day With a concerted effort savings of 25% or more are possible How can these be translated into long term savings?

42 UEA’s Pathway to a Low Carbon Future: A summary
Good Management Raising Awareness Improving Conversion Efficiency Using Renewable Energy Don’t need the English on this slide so Chinese is fine Offset Carbon Emissions 42 42

43 Conclusions UEA has achieved Carbon reductions by:
Constructing Low Energy Buildings Effective adaptive energy management which has typically reduced energy requirements in a low energy building by 50% or more. Use of Renewable Energy: Photovoltaic electric generation but opportunities were missed which would have made more optimum use of electricity generated. The existing CHP plant reduced carbon emissions by around 30% Adsorption chilling has been a win-win situation reducing summertime electricity demand and increasing electricity generated locally. Awareness raising of occupants of buildings can lead to significant savings By the end of 2013, UEA should have reduced its carbon emissions per student by 70% compared to 1990.


Download ppt "Carbon Reduction Strategies at the University of East Anglia"

Similar presentations


Ads by Google