Interactive Intelligence Putting you in Control…
Controls V 1.08 Sebastien Desmottes - Controls Development Engineer @ Plymouth (UK)
2
Controls Product Contents
RBC-RDx-PE: Refrigerant Detection RBC-FDP1-PE: Fault Display Panel RBC-CRx-PE: Central Remote Controller RBC-WG1-PE: Windows Gateway RBC-WP1-PE: Windows Software RBC-EM1-PE: Energy Monitoring RBC-IK1-PE: Internet Kit
3
Refrigerant Detection
Indoor / Outdoor RBC-RD1-PE / RBC-RD2-PE
4
Refrigerant Detection Contents
Why Refrigerant Detection Options available Indoor Unit: RBC-RD1-PE Outdoor Unit: RBC-RD2-PE System Layout Electrical Installation System Operation Installation Indoor / Outdoor Note: RBC-RD1-PE, RBC-RD2-PE
5
Refrigerant Detection Why Refrigerant Detection?
To protect personnel (EN 378) To prevent environmental damage To maintain system efficiency Government Tax Incentives Note: RBC-RD1-PE, RBC-RD2-PE
6
Refrigerant Detection Options Available
Indoor Unit: RBC-RD1-PE Interface box with remote refrigerant sensor & audible alarm Outdoor Unit: RBC-RD2-PE Interface box with internal sensor RBC-RDx-PE Note: RBC-RD1-PE, RBC-RD2-PE
7
Refrigerant Detection Indoor Unit: RBC-RD1-PE
Control box and screw caps Remote sensor/audible alarm assembly Front plate FCU interface cable Installation instructions Owners manual RBC-RD1-PE
8
Refrigerant Detection Outdoor Unit: RBC-RD2-PE
Control box with integral sensor and screw caps CDU interface cable Mounting bracket and screw Installation Instructions Owners Manual RBC-RD2-PE
9
Refrigerant Detection RBC-RD1-PE System Layout
FCU Electrical Box Hotel Room Metal oxide refrigerant detector. Low level position with audible alarm and 3 alarm set-points Standard XY communication protocol Front end PC running Windows control package (RBC-WP1-PE). Displays alarm message and unit location. Isolating solenoid valves positioned in the gas and liquid lines (supplied by installer). Interconnecting cable: control and Sensor. Gateway: RBC-WG1-PE XY PQ RBC-RD1-PE
10
Refrigerant Detection RBC-RD1-PE System Layout
Liquid Line Suction Line To Indoor Network Communication cable Sensor located close to the floor monitors room air.Emits audible alarm when 1000ppm refrigerant (R407C) detected. RD1 box near unit sends signal to solenoid valves and indoor unit.
11
Refrigerant Detection Electrical Installation RBC-RD1-PE
Mount the control box near to the indoor unit in a visible location Mount the remote sensor assembly low down in the room. Maximum height from the floor surface should be 300mm. Ensure 500mm clearance around the sensor Connect the remote sensor assembly to the control box using a 6 core cable Connect the control box to a fused 240V AC 1amp supply For RAV units connect the FCU interface cable to CN17 on the indoor PCB For MM units connect the FCU interface cable to CN21 on the indoor PCB RBC-RD1-PE
12
Refrigerant Detection Electrical Installation RBC-RD2-PE
Mount the control box inside the compressor housing of the outdoor unit Connect a 3-core supply cable from the control unit to the electrical box on the outdoor unit. Ensure a 1A fuse is fitted If one outdoor unit is used connect the CDU interface cable from the control unit to the electrical box on the outdoor unit. Locate the 3 ceramic fuses at the top of the electrical box From the top fuse remove the small red cable from the right side of the fuse. In its place fit the CDU interface cable From the small red cable removed from the ceramic fuse place into the crimp butt joint and crimp firmly
13
Refrigerant Detection Electrical Installation RBC-RD2-PE
For multiple outdoor units, each refrigerant detector must be connected in series to the unit in the inverter outdoor unit. The CDU interface cable is only used in the inverter unit Connect each refrigerant detector using 3-core cable to the L1, N and earth terminals in each CDU. Each detector must be protected by a 1amp 240VAC fuse Connect the AI terminals in the control units as shown in the diagram To complete the series circuit connect the CDU interface cable to the inverter electrical box as described in the previous slide RBC-RD1-PE
14
Refrigerant Detection System Operation
Low Level Alarm – 250ppm (RBC-RD1-PE Only): When the low level alarm limit is reached: The Detector Active LED will be “ON” The amber Low Level Alarm LED will start flashing After 10 minutes, the Low Level Alarm LED will stop flashing and remain “ON” B5 fault code will be generated by the indoor unit The indoor unit will not shut down RBC-RD1-PE Note: If the refrigerant concentration drops below 250ppm the control box will self reset
15
Refrigerant Detection System Operation
High Level Alarm – 1000ppm (RBC-RD1/RD2-PE): When the high level alarm limit is reached: The Detector Active and the Low Level Alarm LED’s will be “ON” The red High Level Alarm LED will start flashing After 10 minutes, the High Level Alarm LED will stop flashing and remain “ON”. The red Shutdown LED will also come “ON” B5 & B6 fault codes will be generated by the indoor unit, 04 fault code will be generated by the outdoor unit The indoor unit will shut down and the audible alarm will sound if an RD1 was activated The outdoor unit will shut down if an RD2 was activated The alarm volt free contacts will operate to control any suitable external device RBC-RDx-PE Note: The system must be manually reset using the reset buttons on the control box
16
Refrigerant Detection System Operation
Spill Alarm – 2200ppm (RBC-RD1/RD2-PE) When the spill alarm limit is reached: The Detector Active LED will be “ON” After 10 seconds at the Spill Alarm limit, the Shutdown LED will come “ON” The Low Level Alarm & the High Level Alarm LED’s will start flashing B6 fault code will be generated by the indoor unit if the refrigerant is detected in the room by RBC-RD1-PE 04 fault code will be generated by the outdoor unit if the refrigerant is detected in the compressor housing by RBC-RD2-PE The indoor unit will shut down and the audible alarm will sound if an RD1 was activated The outdoor unit will shut down if an RD2 was activated The “alarm” volt free contacts will operate to control any suitable external device connected to the control box RBC-RDx-PE Note: The system must be manually reset using the reset buttons on the control box
17
Refrigerant Detection System Operation
Sensor Failure (RBC-RD1/RD2-PE) When the refrigerant sensor fails: After 1 minute the Detector Active LED will go “OFF”, and the Low Level Alarm LED will come “ON” B5 fault code will be generated by the indoor unit. No fault code will be generated by the outdoor unit. The indoor or outdoor unit will not shut down After 4 hours the Low Level Alarm LED will go “OFF” and the Shutdown LED will come “ON” B6 fault code will be generated by the indoor unit if the refrigerant leak is detected in the room by RBC-RD1-PE A 04 fault code will be generated by the outdoor unit if the refrigerant is detected in the compressor housing by RBC-RD2-PE The indoor or outdoor unit will shutdown The “alarm” volt free contacts will operate to control any suitable external device connected to the control box RBC-RDx-PE Note: The system must be manually reset using the reset buttons on the control box after replacing the sensor
18
Refrigerant Detection Refrigerant Mass Required
RBC-RD1-PE : High Level Alarm Calculation based on a hotel room 5m x 8m x 2.5m. Density of R407C vapour at ambient pressure = 3.518kg/m3. For high level alarm (unit shutdown) at 1000ppm: Ppm concentration = 1000/ = 0.001 Grams of R407C = 5m x 8m x 2.5m x 3.518kg/m3 x ppm/conc = kg = 352 g RBC-RD1-PE : Low Level Alarm Grams of R407C = 5m x 8m x 2.5m x 3.518kg/m3 x ppm/conc = kg = 88 g RBC-RD1-PE
19
Refrigerant Detection Refrigerant Mass Required
RBC-RD2-PE : High Level Alarm Calculation based on the volume of the compressor housing = 0.8m3 Density of R407C vapour at ambient pressure = 3.518kg/m3. For high level alarm (unit shutdown) at 1000ppm: Ppm concentration = 1000/ = 0.001 Grams of R407C = 0.8m3 x 3.518kg/m3 x ppm/conc = kg = 2.8 g RBC-RD2-PE
20
Refrigerant Detection Installation Indoor / Outdoor
Indoor Installation Standard Grid Plate (BS 57533:1995) Standard Front Plate Integral audible alarm mute button and refrigerant sensor RBC-RD1-PE
21
Refrigerant Detection Installation Indoor / Outdoor
Outdoor Installation RBC-RD2-PE only available with MMS RBC-RD2-PE
22
Fault Display Panel Fault Display Panel RBC-FDP1-PE
23
Fault Display Panel Contents
Features Installation
24
Fault Display Panel Features
Detect all Indoor Units faults Attached in parallel with the Remote Controller (ABC) LED to indicate activity (flashing at 1s rate) LED to indicate fault / no fault Volt-free contact allows external signalling of the fault Relay closed under fault free conditions 09 Fault can be optionally filtered RBC-FDP1-PE
25
Fault Display Panel Installation
No external power supply needed as it is attached in parallel with the Remote Controller (ABC). Fault filter OFF: 09 faults are treated like any other fault code ON: 09 faults are only reported after 3 hours RBC-FDP1-PE
26
Central Remote Controller
RBC-CR1-PE, RBC-CR64-PE
27
Central Remote Controller Contents
Models Features / Options Installation
28
Central Remote Controller Models Available
RBC-CR1-PE Control up to 16 Indoor Units RBC-CR64-PE Control up to 64 Indoor Units RBC-CRx-PE Note: RBC-CRx-PE cannot be used in conjunction with the Windows Gateway (WG1)
29
Central Remote Controller Options Available
RBC-CR1-PE / RBC-CR64-PE Compatible with Toshiba MMS and 4 Series Heat Pump Compatible with 7 Day Timer (RBC-WT1-PE) RBC-CR64-PE External switch (Input Shutdown) External timer Units can be grouped in Zones Two central Controllers can be used on the same XY Network RBC-CRx-PE Note: RBC-CRx-PE cannot be used in conjunction with the Windows Gateway (WG1)
30
Central Remote Controller Installation (RBC-CR64-PE)
All types of systems (MMS, SMi, Single split) can be connected to the same Central Remote Controller RBC-CR64-PE Note: RBC-CR64-PE cannot be used in conjunction with the Windows Gateway (WG1)
31
Interactive Intelligence
Building Management System RBC-WG1-PE, RBC-WP1-PE, RBC-EM1-PE, RBC-IK1-PE
32
Interactive Intelligence BMS - Contents
Link Between Products Windows Gateway Windows Software Energy Monitoring Internet Kit Note: RBC-WG1-PE, RBC-WP1-PE, RBC-EM1-PE, RBC-IK1-PE
33
Interactive Intelligence Link Between Product ?
Internet / Intranet
34
Link Between Controls Product Windows Gateway 1:64
To control up to 64 Toshiba I./D (MMS or RAV AI) units Consists of: One Gateway One IEC Plug Installation Instruction with functional profile RBC-WG1-PE Note: RBC-WG1-PE cannot be used in conjunction with any other Central Controller
35
Link Between Controls Product Windows Software 1:1024
To manage on one PC up to 1024 I/D i.e. 16 Gateways Consists of: One CD “Interactive Intelligence” One hardware key One owner's manual PCI Card (Extension) RBC-WG1-PE Note: RBC-WG1-PE cannot be used in conjunction with any other Central Controller
36
Link Between Controls Product Energy Monitoring
RBC-EM1-PE is an add-on to RBC-WP1-PE Consists of: One power meter Current Transformers x3 Installation Instructions RBC-EM1-PE Note: RBC-EM1-PE must be used in conjunction with RBC-WG1-PE, RBC-WP1-PE
37
Link Between Controls Product Internet Kit 1:5
RBC-IK1-PE is an add-on to RBC-WP1-PE Consists of: One key file CD “Interactive Intelligence” License for 5 concurrent users RBC-WP1-PE Note: RBC-IK1-PE must be used in conjunction with RBC-WG1-PE, RBC-WP1-PE
38
Interactive Intelligence
Windows Gateway RBC-WG1-PE
39
Interactive Intelligence Windows Gateway 1:64
Gateway using LonWorks Technology Control up to to 64 I/D Auto Detect number of I/D automatically Functions of Central Remote Controller Ambient & Coil Temperatures available RBC-WG1-PE Note: RBC-WG1-PE is not compliant with Echelon.
40
Interactive Intelligence
Windows Software Interactive Intelligence RBC-WP1-PE
41
Interactive Intelligence Windows Software 1:1024 Contents
Features Installation Navigation (Schematics) Alarms Remote Connection Timed Operation and Optimised Start Frost Protection Module Data Logging Graphical view Backup / Restore of the complete System Customisation of Schematics Website
42
Interactive Intelligence Features
Automated Configuration Display and retransmission of Intelligent fault code Unit location can be displayed on PC Data and alarms logging Timed operation under several schedule Navigator (schematics) fully customisable Hardware key protection and 100 access level configurable RBC-WP1-PE Note: Compatible with Win 98 SE, Win NT 4.0, Win 2000 and Win XP.
43
Interactive Intelligence Automatic Installation
BEFORE: LonMaker / Front End Software PC & PCLTA20 Systems Integrator AFTER: Interactive Intelligence PC RBC-WP1-PE
44
Interactive Intelligence Automatic Installation
Auto-detect of the number of units on each Windows Gateway Auto-detect how many Gateways on the network Auto-detect how many Power Meters if any are present Generates a Network database Generates standard schematics for each units RBC-WP1-PE Note: The XY network connection must be checked.
45
Interactive Intelligence Automatic Installation
Opening system Create schematics ? RBC-WP1-PE
46
Interactive Intelligence Automatic Installation
Commissioned Devices ? (Windows Gateway / Power Meter) Software looking for devices (Commissioned / Decommissioned) RBC-WP1-PE
47
Interactive Intelligence Automatic Installation
Database generated Able to rename Gateways Able to rename Indoor Units Able to decommission Gateways (right click on the Gateway) RBC-WP1-PE
48
Interactive Intelligence Navigation / Schematics
Level 1 Schematic Number of Gateways Click here to go to Level 2 (I/D attached to this Gateway) RBC-WP1-PE Note: LEVEL 1 Schematic
49
Interactive Intelligence Navigation / Schematics
Level 2 Schematic Number of Indoor Units Click here to go to Level 3 (details of the settings) RBC-WP1-PE Note: LEVEL 2 Schematic
50
Interactive Intelligence Navigation / Schematics
Level 3 Schematic Settings of the Indoor Unit Able to change the picture of the Indoor Unit RBC-WP1-PE Note: LEVEL 3 Schematic
51
Interactive Intelligence Navigation / Schematics
All models RBC-WP1-PE Note: LEVEL 3 Schematic
52
Interactive Intelligence Alarms
Indication: Intelligent FaultCode Gateway/Indoor Unit RBC-WP1-PE
53
Interactive Intelligence Alarms
Transmission Print Audio Popup Window Retransmission: Fax Remote Site GSM / Pager RBC-WP1-PE Note: Modem Internal / External Required on Supervisor.
54
Interactive Intelligence Remote Connection
Internet Kit Site: RBC-WP1-PE + RBC-IK1-PE Office: Internet Explorer Remote Connection: Site: RBC-WP1-PE Office: RBC-WP1-PE Site Office WP1 / IK1 IE RBC-WP1-PE RBC-WP1-PE RBC-WP1-PE Note: Modem Internal / External Required on Supervisor.
55
Interactive Intelligence Remote Connection
Able to: Access system set-up Edit / Modify schematics Not able to access: Driver set-up Any plug-in (Optimised Start, Frost Protection Module, Energy Monitoring) RBC-WP1-PE Note: Modem Internal / External Required on Supervisor.
56
Interactive Intelligence Timer – Option 1: Local Calendar
Weekly Schedule 300 Items 24 Events in a day Special Day RBC-WP1-PE Note: Local Calendar Option.
57
Interactive Intelligence Timer – Option 2: Optimised Start
Weekly Schedule RBC-WP1-PE Note: Optimised Start Option.
58
Interactive Intelligence Timer – Option 2: Optimised Start
Weekly Schedule Optimised Start Option User Friendly set-up RBC-WP1-PE Note: Optimised Start Option.
59
Interactive Intelligence Timer – Option 2: Optimised Start
Enable a specific Temperature to be achieved at a specific time Learning the room inertia to determine when to start the Air Conditioning system 23 °C 20 °C Setpoint 08: : : time DAY 1 DAY 2 DAY 3 RBC-WP1-PE Note: Optimised Start Option.
60
Interactive Intelligence Frost Protection Module
Can enable the A/C and maintain in constant temperature in the event of low temperature being detected Can stop the A/C when a temperature is achieved Able to: Turn On / Off Change the Set Point Change the Mode Conditions can be entered which includes samples times, the trigger and reset points. RBC-WP1-PE
61
Interactive Intelligence Data Logging
Record any data SetPoint Mode Fan Speed On / Off Fault Codes Demand Data TA, TC RBC-WP1-PE Note: Max Log Time Base = 1 Day.
62
Interactive Intelligence Graphical View
Graphics from Data logging Colours and type of Graphic customisable Zoom In / Out Print RBC-WP1-PE
63
Interactive Intelligence Backup the complete system
Backup system Notes Basic Configuration Schematics Data logging Local Calendars Script RBC-WP1-PE
64
Interactive Intelligence Restore the complete system
Restore system Notes Basic Configuration Schematics Data logging Local Calendars Script RBC-WP1-PE
65
Interactive Intelligence Customisation
Site fully customisable Examples: United Kingdom Plymouth - Life Test United Kingdom Leatherhead – UTC House Life Test United Kingdom Glasgow – Airbels Road France Nantes - System U Austria – Office Diagnostics (16 I/D and 32 I/D) RBC-WP1-PE
66
Interactive Intelligence Customisation – UK - Plymouth
Level 1 Schematic 4 Gateways 8 Different Systems RBC-WP1-PE
67
Interactive Intelligence Customisation – UK - Plymouth
Level 2 Schematic MMS14HP Energy Consumption available RBC-WP1-PE
68
Interactive Intelligence Customisation – UK - Plymouth
Level 2 Schematic SMI10HP Top view imported from AutoCAD RBC-WP1-PE
69
Interactive Intelligence Customisation – UK - Leatherhead
Level 1 Schematic UTC House RBC-WP1-PE
70
Interactive Intelligence Customisation – UK - Leatherhead
Level 2 Schematic Top view imported from AutoCAD Blue and Red button to specify if the I./D is cooling or heating RBC-WP1-PE
71
Interactive Intelligence Customisation – UK - Leatherhead
Level 2 Schematic Only available for Service Engineers RBC-WP1-PE
72
Interactive Intelligence Customisation – UK - Leatherhead
Level 2 Schematic Outdoor view imported from AutoCAD RBC-WP1-PE
73
Interactive Intelligence Customisation – UK – AirbelsRoad
Level 1 Schematic 2 Gateways Trend System (Ventilation, hot water air handling plant, water levels, metering) RBC-WP1-PE
74
Interactive Intelligence Customisation – UK – AirbelsRoad
Level 2 Schematic Gateway Ground & First floor I/D Fault Codes RBC-WP1-PE
75
Interactive Intelligence Customisation – UK – AirbelsRoad
Level 2 Schematic Gateway First & Second floor I/D Fault Codes RBC-WP1-PE
76
Interactive Intelligence Customisation – UK – AirbelsRoad
Trend Control Fan Heaters Water Tank Metering RBC-WP1-PE
77
Interactive Intelligence Customisation – UK – AirbelsRoad
Air Handling Unit Global view RBC-WP1-PE
78
Interactive Intelligence Customisation – UK – AirbelsRoad
Extract Fan Global view RBC-WP1-PE
79
Interactive Intelligence Customisation – UK – AirbelsRoad
Heaters Global view RBC-WP1-PE
80
Interactive Intelligence Customisation – UK – AirbelsRoad
Metering RBC-WP1-PE
81
Interactive Intelligence Customisation – FR - Nantes
Level 1 Schematic Building view 3 Gateways 150 I/D RBC-WP1-PE
82
Interactive Intelligence Customisation – FR - Nantes
Level 2 Schematic Top view imported from AutoCAD TS, TA reading Heat / Cool reading RBC-WP1-PE
83
Interactive Intelligence Customisation – FR - Nantes
Special Schematic Top view imported from AutoCAD Outdoor view Display outdoor faults RBC-WP1-PE
84
Interactive Intelligence Customisation – AT - Adelsberger
Level 2 Schematic Complete view of the system Temperatures reading from LonWorks sensors Ventilation controlled with Interactive Intelligence I/D will stop if ventilation off RBC-WP1-PE
85
Interactive Intelligence Customisation – Diagnostics 16
Special Schematic Able to see I/D data: 01 to 16 17 to 38 39 to 48 49 to 64 RBC-WP1-PE
86
Interactive Intelligence Customisation – Diagnostics 32
Special Schematic Able to see all the data from the Gateway RBC-WP1-PE
87
Interactive Intelligence Website - Home
Home (basic feature of Interactive Intelligence) RBC-WP1-PE
88
Interactive Intelligence Website -Updates
LNS Driver RGM NDS OZM FPM Node Utility Checklist RBC-WP1-PE
89
Interactive Intelligence Website - FAQ
Commissioning… RBC-WP1-PE
90
Interactive Intelligence
Energy Monitoring RBC-EM1-PE
91
Energy Monitoring Contents
Features Installation of Power Meter Set-up the system View data Set-up the report RBC-EM1-PE
92
Energy Monitoring Features
Automatic Power Meter configuration Calculation of Unit Running costs per indoor unit and system Running costs based on a multiple tariffs Running report based with different clients Option for data export to CSV file (Compatible with Excel) One Power Meter for one Outdoor Unit RBC-EM1-PE Note: Possibility to connect one Power Meter to 2 MMS Outdoor Units.
93
Energy Monitoring Installation of Power Meter
Installation 1: MMS14HP Inverter Power Meter Fix Power Meter Current Transformer x 3 RBC-EM1-PE
94
Energy Monitoring Installation of Power Meter
Installation 2: MMS26HP Inverter Power Meter Fix Power Meter (1 Power Meter for 2 Fix Speed) Current Transformer x 3 RBC-EM1-PE
95
Energy Monitoring Installation of Power Meter
Installation 3: SMI10HP Inverter Power Meter Current Transformer x 3 RBC-EM1-PE
96
Energy Monitoring Set-up the system
Set-up the database Data Tree System Power Meter Indoor Units RBC-EM1-PE
97
Energy Monitoring Set-up the system
Set-up Power Meters and Indoor Units Link with LonWorks database Model names RBC-EM1-PE
98
Energy Monitoring View Data
System data: Indoor Unit 1 Indoor Unit 2 Indoor Unit 3 Indoor Unit 4 … RBC-EM1-PE
99
Energy Monitoring Set-up the report
Select: Client Tariff Layout Destination ( or Printer) Link (System) Select Indoor Unit RBC-EM1-PE
100
Energy Monitoring Set-up the report
View the report: Toshiba Standard Report with: Client Date System reference RBC-EM1-PE
101
Energy Monitoring Set-up the report
Modify the report: Able to change the complete layout Able to import pictures RBC-EM1-PE
102
Interactive Intelligence
Internet Kit RBC-IK1-PE
103
Internet Kit Internet Kit is a license which enables a plug-in
Get connected to server using Internet Explorer No software need to be installed on the client PC Click HERE RBC-IK1-PE Note: The license is for 5 concurrent users.
104
Internet Kit 2 Levels of Access: Remote A/C system monitoring
Full remote A/C system control and RBC-IK1-PE Note: The license is for 5 concurrent users.
105
Internet Kit Internet Kit does not allow to modify the system set-up of Interactive Intelligence 5 concurrent users can be connected in the same time Each user can be allocated their own unique schematic Alarms can be viewed remotely RBC-IK1-PE Note: The license is for 5 concurrent users.
106
Interactive Intelligence
Any questions ? Internet / Intranet
107
Interactive Intelligence Putting you in Control…
Thanks for your time… Controls Sebastien Desmottes - Controls Development Engineer @ Plymouth (UK)
108
Interactive Intelligence Putting you in Control…
In Touch with Tomorrow TOSHIBA Controls Sebastien Desmottes - Controls Development Engineer @ Plymouth (UK)