1
Two Minute Drill #10 Copyright 2005 Ted "Smitty" Smith
2
Left click on the presentation ICON located at the bottom of the slide directory to the left of the this slide. Each slide will transition to the correct answer automatically in 2:00 minutes. The correct answer will transition in 10 seconds. You may also left click on the slide to manually transition. Do not worry about writing down the correct answer for now. You will have the opportunity to do that at the end of the two minute drill Good luck Remember to start the slide show to activate the timer. Copyright 2005 Ted "Smitty" Smith
3
This drill is a mixture of calculations and code look up questions. You have seen many of them before. Focus on time. Try to find all the answers before the slide transitions. Remember do not worry about writing down the right answer for now. When you reach the end all of the slides will be repeated without the timer so you can take your time to find the ones you missed and write down the correct answers then. Click on the slide to proceed. Copyright 2005 Ted "Smitty" Smith
4
Where handhold enclosures without bottoms are installed, all enclosed conductors and any splices or terminations, if present, shall be listed as suitable for ____________. Corosive atmospheres Special locations Wet locations None of the above
5
Copyright 2005 Ted "Smitty" Smith wet locations 314.30(D)
6
What is the minimum headroom of working space required above a motor control center? 10 feet 3 feet 6.5 feet 5 feet Copyright 2005 Ted "Smitty" Smith
7
6.5 ft 110.26(E) Copyright 2005 Ted "Smitty" Smith
8
What is the minimum sized service required for a 1500 square foot single family dwelling equipped with a 14.7 kW range at 240 volts and a 1.2 kW dishwasher at 120 volts and a 1.1 kW garbage disposal at 120 V, and 3.9 kW of air conditioning at 240 volts and 9 kW of electric heat at 240 volts? 100 A 110 A 125 A 150 A
9
Copyright 2005 Ted "Smitty" Smith 125 A Article 220 Part III
10
How thick must sealing compound be in a ½” seal off in a class I, div. 1 area? ½” 5/8” ¾” 1” Copyright 2005 Ted "Smitty" Smith
11
5/8 “ 501.15(C)(3) Copyright 2005 Ted "Smitty" Smith
12
The non-heating leads on heating cables must be a minimum of _______________ in length. 2 feet 3 feet 6 feet 7 feet Copyright 2005 Ted "Smitty" Smith
13
7 ft 424.34 Copyright 2005 Ted "Smitty" Smith
14
Each unit length of heating cable shall have a lead wire with a color code of ______________ if it is rated to operate at 208V. Yellow Blue Orange Red Copyright 2005 Ted "Smitty" Smith
15
Blue 424.35 Copyright 2005 Ted "Smitty" Smith
16
The requirement of “shall be listed” indicates that a piece of material or equipment must ______________. be accepted by an authority having jurisdiction be tested by a qualified person be listed in a publication that is produced by an organization accepted by the authority having jurisdiction and states that the equipment of material meets appropriate designated standards or has been tested and found suitable for a specific purpose. Copyright 2005 Ted "Smitty" Smith
17
be listed in a publication that is produced by an organization accepted by the authority having jurisdiction and states that the equipment of material meets appropriate designated standards or has been tested and found suitable for a specific purpose. Article 100 Copyright 2005 Ted "Smitty" Smith
18
Where submersible pump is used in a metal well casing, the well casing shall be bonded to the pump circuit __________ conductor. Equipment grounding Bonding jumper Grounded conductor None of the above
19
Copyright 2005 Ted "Smitty" Smith Equipment grounding 250.112(M)
20
Copyright 2005 Ted "Smitty" Smith A single grounding electrode conductor can be used to connect multiple grounding electrodes. True False
21
Copyright 2005 Ted "Smitty" Smith True 250.64(F)
22
Copyright 2005 Ted "Smitty" Smith A single rod or pipe electrode shall have a resistance of _________ ohms or less to ground. 10 ohms 15 ohms 25 ohms 50 ohms
23
Copyright 2005 Ted "Smitty" Smith 25 250.56
24
Copyright 2005 Ted "Smitty" Smith A ballast in a fluorescent luminaire that is used for egress lighting and energized only during a failure of the normal supply shall not have ________________. Disconnecting means Switching means Thermal protection None of the above
25
Copyright 2005 Ted "Smitty" Smith Thermal Protection 410.73(E)(4)
26
Copyright 2005 Ted "Smitty" Smith Can the next standard sized overcurrent protective device be used to protect tap conductors for transformer secondary conductors? Yes No
27
Copyright 2005 Ted "Smitty" Smith NO 240.21(C)
28
Copyright 2005 Ted "Smitty" Smith All grounding electrodes as described in 250. 52(A)(1) through 250.52(A)(6) that are ____________ at each building or structure served shall be bonded together to form the grounding electrode system. Present Approved Required Inspected
29
Copyright 2005 Ted "Smitty" Smith Present 250.50
30
Copyright 2005 Ted "Smitty" Smith An enclosure mounted to structural or supporting elements of a suspended ceiling shall be not more than ______________________ in size and shall be securely fastened in place. 25 cubic inches 50 cubic inches 75 cubic inches 100 cubic inches
31
Copyright 2005 Ted "Smitty" Smith 100 cubic inches 314.23(D)
32
Copyright 2005 Ted "Smitty" Smith Sheet metal boxes not over 100 cubic inches in size shall be made from steel not less than ______ inches thick. 1 inches .5 inches .0814 inches .0625 inches
33
Copyright 2005 Ted "Smitty" Smith .0625 inches 314.40(B)
34
Copyright 2005 Ted "Smitty" Smith What is the minimum sized main bonding jumper, copper, required if a conductor is used and the supply conductors consist of 4 parallel runs of 500 kcmil copper conductors? 1/0 AWG 3/0 AWG 250 kcmil 500 kcmil
35
Copyright 2005 Ted "Smitty" Smith 250 kcmil 250.28(C) and Table 8 500 x 4= 2000 kcmil. 12.5% of 2000 kcmil is 250 A minimum of 250 kcmil wire is needed.
36
Copyright 2005 Ted "Smitty" Smith The service entrance of a building may be located less than three feet from a window as long as the conductors are installed so that they___________ of the window. Run parallel to the vertical edge Run above the top level Run along the bottom leve None of the above
37
Copyright 2005 Ted "Smitty" Smith Run above the top level 230.9(A)Ex
38
Copyright 2005 Ted "Smitty" Smith What is the maximum sized duel element time delay fuse that can be used to provide branch circuit short circuit protection for a 40 hp, 208V, three-phase, induction motor, that has a nameplate full load current of 96.5 amperes? The motor is a design B motor with a marked service factor of 1.15. 100 A 150 A 200 A 225 A
39
Copyright 2005 Ted "Smitty" Smith 200A 430.52 Table and Exception
40
Copyright 2005 Ted "Smitty" Smith Sheet metals screws shall not be used to connect grounding conductors or _______________ to enclosures as applied to grounding requirements. Connection devices Neutral bus bars Mounting hardware None of the above
41
Copyright 2005 Ted "Smitty" Smith connection devices 250.8
42
Which of the following best describes the definition of accessible as applied to wiring methods: Easy Do not have to leave ground to access Can be rendered accessible without damaging the structure or finish No sweat Copyright 2005 Ted "Smitty" Smith
43
Can be rendered accessible without damaging the structure or finish Article 100 Copyright 2005 Ted "Smitty" Smith
44
What is the minimum sized grounding electrode conductor required for a service that is supplied by (4) parallel runs of 500 kCMIL service entrance conductors? The conductors are copper and the grounding electrode conductor will also be copper. 3/0 AWG 300 kcmil 500 kcmil 1/0 AWG
45
Copyright 2005 Ted "Smitty" Smith 3/0 Table 250.66
46
Copyright 2005 Ted "Smitty" Smith What is the minimum sized main bonding jumper that can be used for a service that is supplied by (3) parallel runs of 750 kcmil service entrance conductors? The service entrance conductors are copper. 1/0 AWG 2/0 AWG 300 kcmil 500 kcmil
47
Copyright 2005 Ted "Smitty" Smith 300 kcmil 250.28(D) and Table 8 for circular mills
48
Copyright 2005 Ted "Smitty" Smith What is the minimum sized equipment grounding conductor that is required for a circuit that is protected by a 50 ampere overcurrent protective device if the ungrounded conductors are increased in size from a number 6 AWG, THHN to a number 2 AWG, THHN? All conductors are copper. 10 AWG 8 AWG 6 AWG 4 AWG
49
Copyright 2005 Ted "Smitty" Smith 4 AWG 250.22(B) and Table 8 for circular mills
50
Copyright 2005 Ted "Smitty" Smith A junction box that is 18" x 18" x 6" that has two 1 1/2" EMT conduits entering and exiting through concentric knockouts and the conduits contain conductor that are number 4 AWG, THHN must be equipped with grounding bushings, threaded bosses or bonding lock nuts to accommodate the bonding and continuity requirements of article 250 of the NEC. The circuits in the junction box are operating at 208 volts, three-phase. True False
51
Copyright 2005 Ted "Smitty" Smith False 250.96 and 250.97 would only be required if circuits were operating at more than 250 volts to ground.
52
Copyright 2005 Ted "Smitty" Smith The earth shall not be considered as an effective ground fault current path. True False
53
Copyright 2005 Ted "Smitty" Smith True 250.4(A)(5)
54
Copyright 2005 Ted "Smitty" Smith Only those conduit bodies that are durably and visibly marked by the manufacturer with __________ shall be permitted to contain splices, taps, or devices. Their size Their volume allowance Their dimensions Their manufacturer
55
Copyright 2005 Ted "Smitty" Smith their volume allowance 314.16(C)(2)
56
Copyright 2005 Ted "Smitty" Smith An emergency system shall be suitable for the ___________________ available fault current at its terminals. Minimum Maximum Listed rated
57
Copyright 2005 Ted "Smitty" Smith Maximum 700.5
58
Copyright 2005 Ted "Smitty" Smith When grounding the outer conductive shield of a coaxial cable the maximum sized ground required shall be ______________ AWG copper 2 AWG 4 AWG 6 AWG 8 AWG
59
Copyright 2005 Ted "Smitty" Smith 6 820.100(A)(3)
60
Copyright 2005 Ted "Smitty" Smith If a system is a three phase, three wire Delta configured system, operating at 230 Volts, is it required to be a grounded system? Yes No
61
Copyright 2005 Ted "Smitty" Smith No 250.20(B)
62
Copyright 2005 Ted "Smitty" Smith What is the demand on the main service entrance of a single family dwelling of a range with a nameplate rating of 13.9 kVA at 240 volts? 8000 VA 8800 VA 9600 VA 10000 VA
63
Copyright 2005 Ted "Smitty" Smith 8800 VA Table 220.55 Note 1
64
Copyright 2005 Ted "Smitty" Smith What is the minimum number of 15 ampere lighting circuits required for a 1500 square foot single family dwelling equipped with a 14.7 kW range at 240 volts and a 1.2 kW dishwasher at 120 volts and a 1.1 kW garbage disposal at 120 V, and 3.9 kW of air conditioning at 240 volts and 9 kW of electric heat at 240 volts? 1 2 3 5
65
Copyright 2005 Ted "Smitty" Smith 3 4500 VA of lighting load/120= 37.5A
66
Copyright 2005 Ted "Smitty" Smith Raceways that carry service-conductors that are embedded in masonry shall be __________. Sealed Arranged to drain Weatherproof None of the above
67
Copyright 2005 Ted "Smitty" Smith Arranged to drain 230.53
68
Copyright 2005 Ted "Smitty" Smith What is the minimum sized grounding electrode conductor that can be used if the service entrance conductors are 250 kCMIL copper? 1 AWG 2 AWG 3 AWG 3/0 AWG
69
Copyright 2005 Ted "Smitty" Smith 2 AWG T250.66
70
Copyright 2005 Ted "Smitty" Smith A cable tray may serve to carry service-entrance conductors along with other conductors as long as there is a ________. Constraint Listed device Approved means None of the above
71
Copyright 2005 Ted "Smitty" Smith None of the above. The actual answer is: Barrier 230.44Ex
72
Copyright 2005 Ted "Smitty" Smith True of False, the disconnect for a TVSS is not counted as one of the six disconnects allowed for a service. True False
73
Copyright 2005 Ted "Smitty" Smith True 230.71(A)
74
Copyright 2005 Ted "Smitty" Smith The service head for entrance-conductors should be located above the point of attachment but may be located elsewhere as long as the attachment is within __________ feet. 1 feet 2 feet 3 feet 8 feet
75
Copyright 2005 Ted "Smitty" Smith 2 feet 230.54(C) Ex
76
Copyright 2005 Ted "Smitty" Smith The size of a feeder, grounded conductor shall not be smaller than required by_________, except that _________ shall not apply where grounded conductors are run in parallel. 250.122, 250.122(F) 110.14(C), 130.4 220.55, 310.16 None of the above
77
Copyright 2005 Ted "Smitty" Smith 250.122, 250.122(F) 215.2(A)
78
Copyright 2005 Ted "Smitty" Smith Where the premises wiring system has branch circuits supplied from more than one nominal voltage system, each ungrounded conductor of a branch circuit, where accessible, shall be identified by __________. Phase Color code System supply
79
Copyright 2005 Ted "Smitty" Smith System 210.5(C)
80
Each of the slides will now be repeated. They are not timed in this segment. To change a slide, click on the side with your left mouse button. Be sure to physically look up the answers in your code book to improve your look up speed and skill. Copyright 2005 Ted "Smitty" Smith
81
Where handhold enclosures without bottoms are installed, all enclosed conductors and any splices or terminations, if present, shall be listed as suitable for ____________. Corosive atmospheres Special locations Wet locations None of the above
82
Copyright 2005 Ted "Smitty" Smith wet locations 314.30(D)
83
What is the minimum headroom of working space required above a motor control center? 10 feet 3 feet 6.5 feet 5 feet Copyright 2005 Ted "Smitty" Smith
84
6.5 ft 110.26(E) Copyright 2005 Ted "Smitty" Smith
85
What is the minimum sized service required for a 1500 square foot single family dwelling equipped with a 14.7 kW range at 240 volts and a 1.2 kW dishwasher at 120 volts and a 1.1 kW garbage disposal at 120 V, and 3.9 kW of air conditioning at 240 volts and 9 kW of electric heat at 240 volts? 100 A 110 A 125 A 150 A
86
Copyright 2005 Ted "Smitty" Smith 125 A Article 220 Part III
87
How thick must sealing compound be in a ½” seal off in a class I, div. 1 area? ½” 5/8” ¾” 1” Copyright 2005 Ted "Smitty" Smith
88
5/8 “ 501.15(C)(3) Copyright 2005 Ted "Smitty" Smith
89
The non-heating leads on heating cables must be a minimum of _______________ in length. 2 feet 3 feet 6 feet 7 feet Copyright 2005 Ted "Smitty" Smith
90
7 ft 424.34 Copyright 2005 Ted "Smitty" Smith
91
Each unit length of heating cable shall have a lead wire with a color code of ______________ if it is rated to operate at 208V. Yellow Blue Orange Red Copyright 2005 Ted "Smitty" Smith
92
Blue 424.35 Copyright 2005 Ted "Smitty" Smith
93
The requirement of “shall be listed” indicates that a piece of material or equipment must ______________. be accepted by an authority having jurisdiction be tested by a qualified person be listed in a publication that is produced by an organization accepted by the authority having jurisdiction and states that the equipment of material meets appropriate designated standards or has been tested and found suitable for a specific purpose. Copyright 2005 Ted "Smitty" Smith
94
be listed in a publication that is produced by an organization accepted by the authority having jurisdiction and states that the equipment of material meets appropriate designated standards or has been tested and found suitable for a specific purpose. Article 100 Copyright 2005 Ted "Smitty" Smith
95
Where submersible pump is used in a metal well casing, the well casing shall be bonded to the pump circuit __________ conductor. Equipment grounding Bonding jumper Grounded conductor None of the above
96
Copyright 2005 Ted "Smitty" Smith Equipment grounding 250.112(M)
97
Copyright 2005 Ted "Smitty" Smith A single grounding electrode conductor can be used to connect multiple grounding electrodes. True False
98
Copyright 2005 Ted "Smitty" Smith True 250.64(F)
99
Copyright 2005 Ted "Smitty" Smith A single rod or pipe electrode shall have a resistance of _________ ohms or less to ground. 10 ohms 15 ohms 25 ohms 50 ohms
100
Copyright 2005 Ted "Smitty" Smith 25 250.56
101
Copyright 2005 Ted "Smitty" Smith A ballast in a fluorescent luminaire that is used for egress lighting and energized only during a failure of the normal supply shall not have ________________. Disconnecting means Switching means Thermal protection None of the above
102
Copyright 2005 Ted "Smitty" Smith Thermal Protection 410.73(E)(4)
103
Copyright 2005 Ted "Smitty" Smith Can the next standard sized overcurrent protective device be used to protect tap conductors for transformer secondary conductors? Yes No
104
Copyright 2005 Ted "Smitty" Smith NO 240.21(C)
105
Copyright 2005 Ted "Smitty" Smith All grounding electrodes as described in 250. 52(A)(1) through 250.52(A)(6) that are ____________ at each building or structure served shall be bonded together to form the grounding electrode system. Present Approved Required Inspected
106
Copyright 2005 Ted "Smitty" Smith Present 250.50
107
Copyright 2005 Ted "Smitty" Smith An enclosure mounted to structural or supporting elements of a suspended ceiling shall be not more than ______________________ in size and shall be securely fastened in place. 25 cubic inches 50 cubic inches 75 cubic inches 100 cubic inches
108
Copyright 2005 Ted "Smitty" Smith 100 cubic inches 314.23(D)
109
Copyright 2005 Ted "Smitty" Smith Sheet metal boxes not over 100 cubic inches in size shall be made from steel not less than ______ inches thick. 1 inches .5 inches .0814 inches .0625 inches
110
Copyright 2005 Ted "Smitty" Smith .0625 inches 314.40(B)
111
Copyright 2005 Ted "Smitty" Smith What is the minimum sized main bonding jumper, copper, required if a conductor is used and the supply conductors consist of 4 parallel runs of 500 kcmil copper conductors? 1/0 AWG 3/0 AWG 250 kcmil 500 kcmil
112
Copyright 2005 Ted "Smitty" Smith 250 kcmil 250.28(C) and Table 8 500 x 4= 2000 kcmil. 12.5% of 2000 kcmil is 250 A minimum of 250 kcmil wire is needed.
113
Copyright 2005 Ted "Smitty" Smith The service entrance of a building may be located less than three feet from a window as long as the conductors are installed so that they___________ of the window. Run parallel to the vertical edge Run above the top level Run along the bottom leve None of the above
114
Copyright 2005 Ted "Smitty" Smith Run above the top level 230.9(A)Ex
115
Copyright 2005 Ted "Smitty" Smith What is the maximum sized duel element time delay fuse that can be used to provide branch circuit short circuit protection for a 40 hp, 208V, three-phase, induction motor, that has a nameplate full load current of 96.5 amperes? The motor is a design B motor with a marked service factor of 1.15. 100 A 150 A 200 A 225 A
116
Copyright 2005 Ted "Smitty" Smith 200A 430.52 Table and Exception
117
Copyright 2005 Ted "Smitty" Smith Sheet metals screws shall not be used to connect grounding conductors or _______________ to enclosures as applied to grounding requirements. Connection devices Neutral bus bars Mounting hardware None of the above
118
Copyright 2005 Ted "Smitty" Smith connection devices 250.8
119
Which of the following best describes the definition of accessible as applied to wiring methods: Easy Do not have to leave ground to access Can be rendered accessible without damaging the structure or finish No sweat Copyright 2005 Ted "Smitty" Smith
120
Can be rendered accessible without damaging the structure or finish Article 100 Copyright 2005 Ted "Smitty" Smith
121
What is the minimum sized grounding electrode conductor required for a service that is supplied by (4) parallel runs of 500 kCMIL service entrance conductors? The conductors are copper and the grounding electrode conductor will also be copper. 3/0 AWG 300 kcmil 500 kcmil 1/0 AWG
122
Copyright 2005 Ted "Smitty" Smith 3/0 Table 250.66
123
Copyright 2005 Ted "Smitty" Smith What is the minimum sized main bonding jumper that can be used for a service that is supplied by (3) parallel runs of 750 kcmil service entrance conductors? The service entrance conductors are copper. 1/0 AWG 2/0 AWG 300 kcmil 500 kcmil
124
Copyright 2005 Ted "Smitty" Smith 300 kcmil 250.28(D) and Table 8 for circular mills
125
Copyright 2005 Ted "Smitty" Smith What is the minimum sized equipment grounding conductor that is required for a circuit that is protected by a 50 ampere overcurrent protective device if the ungrounded conductors are increased in size from a number 6 AWG, THHN to a number 2 AWG, THHN? All conductors are copper. 10 AWG 8 AWG 6 AWG 4 AWG
126
Copyright 2005 Ted "Smitty" Smith 4 AWG 250.22(B) and Table 8 for circular mills
127
Copyright 2005 Ted "Smitty" Smith A junction box that is 18" x 18" x 6" that has two 1 1/2" EMT conduits entering and exiting through concentric knockouts and the conduits contain conductor that are number 4 AWG, THHN must be equipped with grounding bushings, threaded bosses or bonding lock nuts to accommodate the bonding and continuity requirements of article 250 of the NEC. The circuits in the junction box are operating at 208 volts, three-phase. True False
128
Copyright 2005 Ted "Smitty" Smith False 250.96 and 250.97 would only be required if circuits were operating at more than 250 volts to ground.
129
Copyright 2005 Ted "Smitty" Smith The earth shall not be considered as an effective ground fault current path. True False
130
Copyright 2005 Ted "Smitty" Smith True 250.4(A)(5)
131
Copyright 2005 Ted "Smitty" Smith Only those conduit bodies that are durably and visibly marked by the manufacturer with __________ shall be permitted to contain splices, taps, or devices. Their size Their volume allowance Their dimensions Their manufacturer
132
Copyright 2005 Ted "Smitty" Smith their volume allowance 314.16(C)(2)
133
Copyright 2005 Ted "Smitty" Smith An emergency system shall be suitable for the ___________________ available fault current at its terminals. Minimum Maximum Listed rated
134
Copyright 2005 Ted "Smitty" Smith Maximum 700.5
135
Copyright 2005 Ted "Smitty" Smith When grounding the outer conductive shield of a coaxial cable the maximum sized ground required shall be ______________ AWG copper 2 AWG 4 AWG 6 AWG 8 AWG
136
Copyright 2005 Ted "Smitty" Smith 6 820.100(A)(3)
137
Copyright 2005 Ted "Smitty" Smith If a system is a three phase, three wire Delta configured system, operating at 230 Volts, is it required to be a grounded system? Yes No
138
Copyright 2005 Ted "Smitty" Smith No 250.20(B)
139
Copyright 2005 Ted "Smitty" Smith What is the demand on the main service entrance of a single family dwelling of a range with a nameplate rating of 13.9 kVA at 240 volts? 8000 VA 8800 VA 9600 VA 10000 VA
140
Copyright 2005 Ted "Smitty" Smith 8800 VA Table 220.55 Note 1
141
Copyright 2005 Ted "Smitty" Smith What is the minimum number of 15 ampere lighting circuits required for a 1500 square foot single family dwelling equipped with a 14.7 kW range at 240 volts and a 1.2 kW dishwasher at 120 volts and a 1.1 kW garbage disposal at 120 V, and 3.9 kW of air conditioning at 240 volts and 9 kW of electric heat at 240 volts? 1 2 3 5
142
Copyright 2005 Ted "Smitty" Smith 3 4500 VA of lighting load/120= 37.5A
143
Copyright 2005 Ted "Smitty" Smith Raceways that carry service-conductors that are embedded in masonry shall be __________. Sealed Arranged to drain Weatherproof None of the above
144
Copyright 2005 Ted "Smitty" Smith Arranged to drain 230.53
145
Copyright 2005 Ted "Smitty" Smith What is the minimum sized grounding electrode conductor that can be used if the service entrance conductors are 250 kCMIL copper? 1 AWG 2 AWG 3 AWG 3/0 AWG
146
Copyright 2005 Ted "Smitty" Smith 2 AWG T250.66
147
Copyright 2005 Ted "Smitty" Smith A cable tray may serve to carry service-entrance conductors along with other conductors as long as there is a ________. Constraint Listed device Approved means None of the above
148
Copyright 2005 Ted "Smitty" Smith None of the above. The actual answer is: Barrier 230.44Ex
149
Copyright 2005 Ted "Smitty" Smith True of False, the disconnect for a TVSS is not counted as one of the six disconnects allowed for a service. True False
150
Copyright 2005 Ted "Smitty" Smith True 230.71(A)
151
Copyright 2005 Ted "Smitty" Smith The service head for entrance-conductors should be located above the point of attachment but may be located elsewhere as long as the attachment is within __________ feet. 1 feet 2 feet 3 feet 8 feet
152
Copyright 2005 Ted "Smitty" Smith 2 feet 230.54(C) Ex
153
Copyright 2005 Ted "Smitty" Smith The size of a feeder, grounded conductor shall not be smaller than required by_________, except that _________ shall not apply where grounded conductors are run in parallel. 250.122, 250.122(F) 110.14(C), 130.4 220.55, 310.16 None of the above
154
Copyright 2005 Ted "Smitty" Smith 250.122, 250.122(F) 215.2(A)
155
Copyright 2005 Ted "Smitty" Smith Where the premises wiring system has branch circuits supplied from more than one nominal voltage system, each ungrounded conductor of a branch circuit, where accessible, shall be identified by __________. Phase Color code System supply
156
Copyright 2005 Ted "Smitty" Smith System 210.5(C)