1
Service Section Technical Training
2
Good Air Conditioning Installation Practices
3
Contents Location of installationLocation of installation PipingPiping CleanlinessCleanliness ElectricalElectrical Refrigerant CircuitRefrigerant Circuit
4
Storage and Transportation
5
Condensing units must be stored and transport in an upright positionCondensing units must be stored and transport in an upright position
6
Storage and Transportation The air conditioner should not be over-stackThe air conditioner should not be over-stack Prevent drop of unitPrevent drop of unit
7
Location of Installation
8
Indoor unit Ceiling too highCeiling too high
9
Location of Installation Indoor unit Unit installed in an enclosed areaUnit installed in an enclosed area
10
Location of Installation Indoor unit Dirty or chemically hazardous environmentDirty or chemically hazardous environment
11
Location of Installation Indoor unit Avoid high electrical interference environment ( infra red bar code scanning machine, lighting with electronic ballast)Avoid high electrical interference environment ( infra red bar code scanning machine, lighting with electronic ballast)
12
Location of Installation Indoor unit No service openingNo service opening
13
Location of Installation Indoor unit Duct work too shortDuct work too short
14
Location of Installation Outdoor unit Select a suitable installation siteSelect a suitable installation site A place where …... …… Easy for service
15
Location of Installation Outdoor unit Select a suitable installation siteSelect a suitable installation site A place where …... …… Comply to installation clearance
16
Location of Installation Outdoor unit Select a suitable installation siteSelect a suitable installation site A place where …... …… Do not block the air discharge
17
Location of Installation Outdoor unit Select a suitable installation siteSelect a suitable installation site A place where …... …… The return air is not short cycle
18
Location of Installation Outdoor unit Select a suitable installation siteSelect a suitable installation site A place where …... …… To avoid strong wind
19
Location of InstallationDrainage A proper drainage system is crucialA proper drainage system is crucial
20
Location of InstallationDrainage A proper drainage system must be slopedA proper drainage system must be sloped
21
Location of InstallationDrainage Beware of where it endsBeware of where it ends
22
Location of InstallationDrainage Proper length is crucialProper length is crucial
23
Piping
24
Piping Keep the piping as short as possibleKeep the piping as short as possible
25
Piping Provide oil traps if height of installation exceed 10mProvide oil traps if height of installation exceed 10m 10m 5m Condenser Evaporator Condenser Evaporator
26
Piping Insulate the pipe and insulate it separatelyInsulate the pipe and insulate it separately
27
Piping Bend the pipe using pipe bender instead of hands.Bend the pipe using pipe bender instead of hands.
28
Piping Do not size up or size down the pipe (especially for heatpump model)Do not size up or size down the pipe (especially for heatpump model) >Pipe size up - refrigerant velocity down >Pipe size up - more refrigerant needed - refrigerant floodback >Pipe size up - dilution of oil
29
Cleanliness
30
Cleanliness Do not expose pipes or components to environment over an prolong period.Do not expose pipes or components to environment over an prolong period.
31
Cleanliness Keep moisture out of pipes or componentsKeep moisture out of pipes or components
32
Cleanliness When laying pipes through walls, end of pipes must be properly sealedWhen laying pipes through walls, end of pipes must be properly sealed
33
Cleanliness When cutting a copper pipe, use copper cutter instead of saw.When cutting a copper pipe, use copper cutter instead of saw.
34
Cleanliness Always vacuum before charge in refrigerantAlways vacuum before charge in refrigerant
35
Cleanliness Always braze with present of nitrogenAlways braze with present of nitrogen
36
Electrical
37
Electrical Remote control wiring should be separated from power cableRemote control wiring should be separated from power cable
38
Electrical Screw must be tight at terminalsScrew must be tight at terminals
39
Electrical Examine the power sourceExamine the power source Determine the maximum load the power source can handleDetermine the maximum load the power source can handle
40
Refrigerant Circuit
41
Proper leak checkProper leak check Properly charge the systemProperly charge the system For no pre-charge system which is using scroll compressor, must contain 80% charge before startFor no pre-charge system which is using scroll compressor, must contain 80% charge before start For system that using TXV, make sure the TXV is properly installedFor system that using TXV, make sure the TXV is properly installed
42