OIIL BURNERS R D B series Riello Burners - TRAining CEntre
2
REG burners control box 535 SE Riello Burners - TRAining CEntre
3
CONTROL BOX 535 SE TR ST PH N + M - Riello Burners - TRAining CEntre
4
CONTROL BOX 535 SE PH N Electrical supply: 230 V±10% fuse 6A 250V
9 ST L1 Valve coil starting:30V; 280mA running:3V; 30mA PH Valve coil: 100 Photoresistence sensibility: 2 lux (starting) 3 lux (running) Ignition transformer 20 kHz 8 kV 10 mA W N 1 A 800 VL input: 48 AC output: 72 DC Pre-purge timer: 12’’ by a capacitor 22µF and a resistence 1M Motor pack 35 90W Safety relais (bimetallic) Amplifier 11 8 6 + M Remote lock-out signal 230 V; max 0.1A - Safety relais (bimetallic) 10 Internal relais 12V N Riello Burners - TRAining CEntre
5
CONTROL BOX 535 SE start up procedure: pre-purge
PH N + M - Riello Burners - TRAining CEntre
6
CONTROL BOX 535 SE start up procedure: pre-purge
PH N + M - Riello Burners - TRAining CEntre
7
CONTROL BOX 535 SE start up procedure: pre-purge
PH N + M - Riello Burners - TRAining CEntre
8
CONTROL BOX 535 SE start up procedure: pre-purge
PH N + M - Riello Burners - TRAining CEntre
9
CONTROL BOX 535 SE start up procedure: pre-purge
PH N 52 V AC 72V DC + M - Timer is supplied (12”) Riello Burners - TRAining CEntre
10
CONTROL BOX 535 SE start up procedure: ignition
PH N + M - Riello Burners - TRAining CEntre
11
CONTROL BOX 535 SE start up procedure: ignition
PH N + M - Riello Burners - TRAining CEntre
12
CONTROL BOX 535 SE start up procedure: ignition
PH N + M - Riello Burners - TRAining CEntre
13
CONTROL BOX 535 SE start up procedure: ignition
PH N + M - Riello Burners - TRAining CEntre
14
CONTROL BOX 535 SE start up procedure: ignition
PH N + M - Riello Burners - TRAining CEntre
15
CONTROL BOX 535 SE start up procedure: ignition
PH N + M - Riello Burners - TRAining CEntre
16
CONTROL BOX 535 SE start up procedure: ignition
PH N + M - Riello Burners - TRAining CEntre
17
CONTROL BOX 535 SE start up procedure: ignition
PH N + M - Riello Burners - TRAining CEntre
18
CONTROL BOX 535 SE start up procedure: running
PH N + M - Riello Burners - TRAining CEntre
19
CONTROL BOX 535 SE faults: no flame at ignition PH N 280 mA
ST PH 280 mA N + 280 mA at bimetallic relais M - Riello Burners - TRAining CEntre
20
CONTROL BOX 535 SE faults: no flame at ignition PH N + M - TR ST
Riello Burners - TRAining CEntre
21
no flame at ignition => lock-out
CONTROL BOX 535 SE faults: no flame at ignition => lock-out TR ST PH N + M - Riello Burners - TRAining CEntre
22
light into the chambre (or short at photoresistence)
CONTROL BOX 535 SE faults: light into the chambre (or short at photoresistence) TR ST PH N + M - Riello Burners - TRAining CEntre
23
light into the chambre (or short at photoresistence)
CONTROL BOX 535 SE faults: light into the chambre (or short at photoresistence) TR ST PH N + M - Riello Burners - TRAining CEntre
24
light into the chambre (or short at photoresistence)
CONTROL BOX 535 SE faults: light into the chambre (or short at photoresistence) continous pre-purge TR ST PH N + M - Riello Burners - TRAining CEntre
25
valve coil interrupted : continous pre-purge
CONTROL BOX 535 SE faults: valve coil interrupted : continous pre-purge TR ST PH N Timer is not supplied + M - Riello Burners - TRAining CEntre
26
Short at Darlington R3381 by Texas
CONTROL BOX 535 SE faults: Short at Darlington R3381 by Texas TR ST PH N + M - Riello Burners - TRAining CEntre
27
Short at Darlington R3381 by Texas
CONTROL BOX 535 SE faults: Short at Darlington R3381 by Texas TR ST PH N + M - Riello Burners - TRAining CEntre
28
Immediate change of position
CONTROL BOX 535 SE faults: Short at Darlington R3381 by Texas TR ST Immediate change of position PH N + M - 2A at bimetallic relais Riello Burners - TRAining CEntre
29
Short at Darlington R3381 by Texas
CONTROL BOX 535 SE faults: Short at Darlington R3381 by Texas TR ST PH N + M - Riello Burners - TRAining CEntre
30
Short at Darlington R3381 by Texas Immediate lock-out
CONTROL BOX 535 SE faults: Short at Darlington R3381 by Texas Immediate lock-out TR ST PH N + M - Riello Burners - TRAining CEntre
31
OIL BURNERS R E G series Riello Burners - TRAining CEntre
32
OIL BURNERS CONTROL BOX 535R SE Riello Burners - TRAining CEntre
33
CONTROL BOX 535R SE TR ST PH N + M - Riello Burners - TRAining CEntre
34
CONTROL BOX 535R SE PH N Electrical supply: 230 V±10% fuse 6A 250V
9 ST L1 Valve coil starting:30V; 280mA running:3V; 30mA PH Valve coil: 100 Photoresistence sensibility: 2 lux (starting) 3 lux (running) Ignition transformer 20 kHz 8 kV 10 mA W 1 A 800 VL input: 48 AC output: 72 DC Pre-purge timer: 12’’ by a capacitor 22µF and a resistence 1M N Motor pack 35 90W 12 Amplifier Pre-heater 55W Safety relais (bimetallic) 11 8 13 6 + M Remote lock-out signal 230 V; max 0.1A - Safety relais (bimetallic) 10 Internal relais 12V N Riello Burners - TRAining CEntre
35
CONTROL BOX 535R SE start up procedure: pre-heating
PH N + M - Riello Burners - TRAining CEntre
36
CONTROL BOX 535R SE start up procedure: pre-heating
PH N + M - Riello Burners - TRAining CEntre
37
CONTROL BOX 535R SE start up procedure: pre-heating
PH N + M - Riello Burners - TRAining CEntre
38
CONTROL BOX 535R SEstart up procedure: pre-heating
PH N + M - Riello Burners - TRAining CEntre
39
CONTROL BOX 535R SE start up procedure: pre-purge
PH N 70° C + M - Riello Burners - TRAining CEntre
40
CONTROL BOX 535R SE start up procedure: pre-purge
PH N + M - Riello Burners - TRAining CEntre
41
CONTROL BOX 535R SE start up procedure: pre-purge
PH N + M - Riello Burners - TRAining CEntre
42
CONTROL BOX 535R SE start up procedure: pre-purge
PH N + M - Riello Burners - TRAining CEntre
43
CONTROL BOX 535R SE start up procedure: pre-purge
PH N 52 V AC 72V DC + M - Timer is supplied (12”) Riello Burners - TRAining CEntre
44
CONTROL BOX 535R SE start up procedure: ignition
PH N + M - Riello Burners - TRAining CEntre
45
CONTROL BOX 535R SE start up procedure: ignition
PH N + M - Riello Burners - TRAining CEntre
46
CONTROL BOX 535R SE start up procedure: ignition
PH N + M - Riello Burners - TRAining CEntre
47
CONTROL BOX 535R SE start up procedure: ignition
PH N + M - Riello Burners - TRAining CEntre
48
CONTROL BOX 535R SE start up procedure: ignition
PH N + M - Riello Burners - TRAining CEntre
49
CONTROL BOX 535R SE start up procedure: ignition
PH N + M - Riello Burners - TRAining CEntre
50
CONTROL BOX 535R SE start up procedure: ignition
PH N + M M - Riello Burners - TRAining CEntre
51
CONTROL BOX 535R SE start up procedure: ignition
PH N + M - Riello Burners - TRAining CEntre
52
CONTROL BOX 535R SE start up procedure: running
PH N + M - Riello Burners - TRAining CEntre
53
CONTROL BOX 535R SE faults: no flame at ignition
ST PH 280 mA N + 280 mA at bimetallic relais M - Riello Burners - TRAining CEntre
54
CONTROL BOX 535R SE faults: no flame at ignition
ST PH N + M - Riello Burners - TRAining CEntre
55
CONTROL BOX 535R SE faults: no flame at ignition => lock-out
ST PH N + M - Riello Burners - TRAining CEntre
56
CONTROL BOX 535R SE faults:
light into the chambre (or short at photoresistence) TR ST PH N + M - Riello Burners - TRAining CEntre
57
CONTROL BOX 535R SE faults:
light into the chambre (or short at photoresistence) TR ST PH N + M - Riello Burners - TRAining CEntre
58
CONTROL BOX 535R SE faults:
light into the chambre (or short at photoresistence) continous pre-purge TR ST PH N + M - Riello Burners - TRAining CEntre
59
CONTROL BOX 535R SE faults: valve coil interrupted
: continous pre-purge TR ST PH N Timer is not supplied + M - Riello Burners - TRAining CEntre
60
CONTROL BOX 535R SE faults: Short at Darlington R3381 by Texas
ST PH N + M - Riello Burners - TRAining CEntre
61
CONTROL BOX 535R SE faults: Short at Darlington R3381 by Texas
ST PH N + M - Riello Burners - TRAining CEntre
62
Immediate change of position
CONTROL BOX 535R SE faults: Short at Darlington R3381 by Texas TR ST Immediate change of position PH N + M - 2A at bimetallic relais Riello Burners - TRAining CEntre
63
CONTROL BOX 535R SE faults: Short at Darlington R3381 by Texas
ST PH N + M - Riello Burners - TRAining CEntre
64
CONTROL BOX 535R SE faults: Short at Darlington R3381 by Texas
Immediate lock-out TR ST PH N + M - Riello Burners - TRAining CEntre