Download presentation
Presentation is loading. Please wait.
Published byAubrey Carter Modified over 9 years ago
1
Technical Training. 1 Configuration: 2558 Analog Input Module 1. Select voltage or current input mode for each channel 3. Select digital filtering, offset scaling, and 13/16 bit compatibility for the module 4. Set DIP switches to match the hardware selections 2. Select 5V/10V range and unipolar / bipolar for each channel
2
Technical Training. 2 Configuration: 2558 Analog Input Module Select voltage or 20mA for each channel Select 10V or 5V range for each channel Select bipolar (+/-) or unipolar (+ only) for each channel
3
Technical Training. 3 Configuration: 2558 Analog Input Module Select 4-20ma offset for the module Select digital filtering for the module Select compatibility mode (13bit = Siemens 6108) Note: These settings affect all channels
4
Technical Training. 4 Configuration: 2558 Analog Input Module Configure DIP switches to match range and polarity hardware setting on each channel 00 = unipolar 5V 01 = unipolar 10V 10 = bipolar 5V 11 = bipolar 10V
Similar presentations
© 2025 SlidePlayer.com. Inc.
All rights reserved.