1 LP Series U Uninterruptible Power Supply Technical Specification & Features

2 LP Series U Technical presentation ISO 9001 UL CUL FCC Class A CE

3 Key Features & Benefits
True On-Line Double Conversion … provides highest level of power reliability Fully isolated output … additional power fault protection Power factor corrected input (>0.99) … clean input Scalable Using GEDE’s Unique “Redundant Parallel Architecture (RPA) … maximum reliability Superior battery management … enhanced battery life time ECO-mode … energy savings for less critical loads e.g., during off hours, emergency lights etc Small Footprint … easy to place Fully isolated output – Additional power fault protection Power factor corrected input – Reduces need for oversizing; cost effective for input wiring because of output power factor of 0.8 ECO – Mode tranfer time 10 ms

4 Key Features & Benefits (continued)
Excellent inrush current handling… prevents tripping protection devices Superior overload handling … protection against unplanned overloads Minimal Output Voltage Distortion of <3% … stable power for the load Multi-functional LCD screen … easy to operate Multi language display … Spanish etc Automatic battery testing – every 500 hrs. … no “surprises” Cold start … unit can be started with no AC present No load shutdown … prevents unnecessary discharging of batteries OC – Open collector

5 Key Features & Benefits (continued)
Backfeed relay … maximum safety EPO- Emergency Power Off… maximum safety Multiple I/O voltages … 120,240, 208 VAC Alarm interface : RS 232 and OC contacts … easy to integrate with existing systems Redundant power supply for critical functions (LCD, Bypass) … increased reliability UL, C-UL and CE markings for world-wide applications ...fits to many different mains voltages OC – Open collector

6 Product Specifications
LP Series 8-11U 8 kVA kW LP Series 10-11U 10 kVA - 8 kW LP Series 5-11U 5 kVA- 4 kW LP Series 6-11U 6 kVA kW Voltages and Frequencies Output Voltage /240 Fully isolated, even in bypass mode Output Frequency 50 or 60 Hz (Front Panel Selectable) Input Voltage 208 – 230/240 120 V option (for 5/6 kVA only in additional transformer cabinet; Input Frequency 45-65 Hz Flexible input and output voltages and frequency

7 Output Completely Independent of Input Voltage and Frequency
Operating Mode True On-Line - double conversion Bypass enable / disable … in frequency conversion mode no alarms … in case of weak mains protects the equipment against operations on mains Programmable frequency tracking range (2%, 4%, 6%) … compatible with gen-sets with wider frequency range HF PWM technique … compact design , low-losses, excellent characteristics HF PWM – High Frequency Pulse Width Modulation If bypass is disabled, it would never go to by pass. E.g., in frequency conversion mode Output Completely Independent of Input Voltage and Frequency 1

8 LP Series U Front Panel LCD screen 2 lines with 16 characters
- Information Screen status and alarm messages - Service screen internal settings test screens Set Up Screen setting of parameters Push buttons (keypads to scroll up, down, reset and enter) LED operation / alarm status On/Off switch turns unit on/off completely, including bypass on back of unit 13

9 Rear Panel On/Off switch turns unit on/off completely, including bypass Manual Bypass Battery fuses Utility & Bypass Protection Magnetic Circuit breakers for overload or short circuit in the UPS load I/O terminals RS232/contact interface/EPO Conduit box Optional: SNMP or relay card EMI Optional: RPA card Cable entry DC Connector for external batteries

10 Technology without compromise
Isolation on bypass EMI protection on bypass No inrush current during start up MANUAL BYPASS Bypass MCB Elektronic Bypass Backfeed protection I/O terminals Surge protection RFI Filter Mains MCB 120/240 HF input H bridge 208 Output converter Converter RFI GND Isolation transformer always active Filter 208 120/240 External Battery Battery charging capacity up to 60 minutes run time without additional charger LCD Stepdown Internal Converter Batteries Supply up enter down operation alarm optional 120 Volt auto-input xfrmr 4X General alarm, Utility failure Bypass active, Batterey low L N L MICRO- processor CONTROL UPS Shutdown L RS232 Emergency External shutdown battery INTERFACE disconnected Option: SNMP card

11 Technology with Premium Performance
Input voltage: V at 100% load Bypass MCB RFI Input voltage: V at 50 % load internal supply F3 P Line MCB THD-I < 10% PF 1 input converter N

12 Technology : Output Converter
Inverter DC Isolation on bypass +380V voltage Bypass 240 V 208V Output HS EMI H-BRIDGE F3 C2 Output C1 converter current Output 2x 120 V 1x 120 V 208 V 240 V transformer temp.sensor Heatsink 4X temp.sensor IGBT Fan speed controlled by load & heat sink temperature

13 Battery Specifications
Standard 20 X batteries 12V/7Ah (5/6kVA) or 12V/12Ah (8/10kVA) Charge voltage = 271V, 13.55V/battery Constant current/constant voltage characteristic + boost charge current is ± 0.3 C Temperature protected till 45ºC Battery extension up to 500 Ah Battery capacity programmable over LCD/serial port

14 Superior Battery Management
Ripple-free Boost Charging Temperature Compensated Charging Load dependent end of discharge voltage No-load Shutdown Automatic Battery Test /every 500 hours Deep Calibration Test Load dependent runtime prediction Load dependent battery low signal Maximum Up-time Prevents Damage Prolonged Battery Lifetime No Surprises

15 No Compromise on Output Performance
Output THD < 3% for linear loads Output Power Factor = 0.8 Output filter performance control enabling robust operation Fully isolated output Protected against: Low/high DC voltage Over-temperature Overload AC on Output Short circuit CM – Common Mode DM – Difference Mode No Compromise on Output Performance

16 Bypass Specifications
L2 L1 to output-transformer Manual Bypass Switch UPS MCB Bypass current Hall Sensor Output Line thyristors Bypass input voltage -10 to +10% Bypass frequency window selectable 2%, 4%, 6% Tracking rate 1 Hz/sec “low”, 5 Hz/sec “high” Protected against overload Short circuit protection Galvanic isolation State-of-the-art Bypass

17 Easy to integrate into computer network
Communication Standard: RS 232 dialogue UPS shutdown Emergency Power off ( EPO ) External DC - fuse alarm Optional: SNMP - card RS 232 is not available if SNMP is installed Dry contacts Easy to integrate into computer network

18 Available Options Power Distribution unit (PDU)
External battery cabinets External battery cable Seismic anchor SNMP interface card Relay interface card RPA kit (Redundant Parallel Architecture) Alarm boxes Connectivity products, like Splitter box; interface kits; interface software for all common OS, incl Java 120 Volt input voltage transformer/cabinet