Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith1
3
Instructions Click on the slide show ICON in the lower left hand corner of this screen to start the slide show. A question will appear and stay on the screen for 2 minutes. The question will then be replaced with the correct answer and code reference. This process will repeat until you reach a slide with a stop sign. You can then click on the slides and the questions and answers will be repeated without the timer so you can look up the answers or take notes. Do not worry about writing down the answers until after the timed portion of the program. Concentrate on finding the answer and improving your speed using the NEC. This drill is focused on changes to the 2008 NEC. (C) Copyright 2008 Ted "Smitty" Smith2
4
The life safety branch and critical branch of the emergency system shall be kept __________________ of all other wiring systems and equipment. (C) Copyright 2008 Ted "Smitty" Smith3
5
Entirely independent 517.30(C)(1) (C) Copyright 2008 Ted "Smitty" Smith4
6
All branch circuits serving patient care areas shall be provided with an _________________ by installation in a metal raceway system, or a cable having a metallic armor or sheath assembly. (C) Copyright 2008 Ted "Smitty" Smith 5
7
An effective ground-fault current path 517.13(A) (C) Copyright 2008 Ted "Smitty" Smith6
8
The essential electrical system for these facilities shall comprise a system capable of supplying a ______________ of lighting and power service which is considered essential for life safety and orderly cessation of procedures during the time normal electrical service is interrupted for any reason. (C) Copyright 2008 Ted "Smitty" Smith7
9
Limited amount 517.25 (C) Copyright 2008 Ted "Smitty" Smith8
10
Which of the following is not allowed as an alternate source of power for the essential electrical systems in a health care facility? Generator located on the premises Battery system A second external utility service, separate from the main external utility provided service An external utility service when the normal source of power consists of a generating unit located on premises. (C) Copyright 2008 Ted "Smitty" Smith9
11
A second external utility service 517.35(A) An external utility service can only be used as an alternate source of power if the hospital is normally fed by a generating source on the premises. (C) Copyright 2008 Ted "Smitty" Smith10
12
The disconnecting means for x-ray equipment shall be operable from a location readily accessible from the ______________. (C) Copyright 2008 Ted "Smitty" Smith11
13
X-ray control 517.72(B) (C) Copyright 2008 Ted "Smitty" Smith12
14
The task illumination for the medication preparation area of a patient care area shall be permitted to be connected the critical branch and shall be arranged for _______________ connection to the alternate power source. (C) Copyright 2008 Ted "Smitty" Smith13
15
Delayed automatic 517.43(A) (C) Copyright 2008 Ted "Smitty" Smith14
16
The ___________ system shall supply major electrical equipment necessary for patient care and basic hospital operation. (C) Copyright 2008 Ted "Smitty" Smith15
17
Equipment 517.30(B)(3) (C) Copyright 2008 Ted "Smitty" Smith16
18
Isolated power systems shall be permitted to be used for __________________ areas and if used the isolated power system equipment shall be listed as isolated power equipment. (C) Copyright 2008 Ted "Smitty" Smith17
19
Critical care 517.19(F) (C) Copyright 2008 Ted "Smitty" Smith18
20
The grounding terminals of all receptacles and all non-current carrying conductive surfaces of fixed electrical equipment likely to become energized that are subject to personal contact, operating at over ________ volts, shall be connected to an insulated copper grounding conductor. (C) Copyright 2008 Ted "Smitty" Smith19
21
100 517.13(B) (C) Copyright 2008 Ted "Smitty" Smith20
22
In addition to the usual control and overcurrent protective devices, each isolated power system shall be provided with a continually operating _________________ that indicates total hazard current. (C) Copyright 2008 Ted "Smitty" Smith21
23
Line isolation monitor 517.160(B) (C) Copyright 2008 Ted "Smitty" Smith22
24
The disconnecting means for x-ray equipment shall be of adequate capacity for at least _______ percent of the input required for momentary rating or 100 percent of the input required for the long-time rating of the x-ray equipment, whichever is greater. (C) Copyright 2008 Ted "Smitty" Smith23
25
50 percent 517.72(A) (C) Copyright 2008 Ted "Smitty" Smith24
26
Illumination of means of egress, such as lighting required for corridors shall be supplied from the ____________ branch of the emergency system. (C) Copyright 2008 Ted "Smitty" Smith25
27
Life safety 517.32(A) (C) Copyright 2008 Ted "Smitty" Smith26
28
Nurse call systems shall be provided power from the __________ branch of the emergency system. (C) Copyright 2008 Ted "Smitty" Smith27
29
Critical branch 517.33(A)(5) (C) Copyright 2008 Ted "Smitty" Smith28
30
Each patient bed location shall be provided with a minimum of __________ receptacles. (C) Copyright 2008 Ted "Smitty" Smith29
31
Four 517.18(B) (C) Copyright 2008 Ted "Smitty" Smith30
32
The equipment grounding terminal buses of the normal and essential branch circuit panelboards serving the same individual patient care vicinity shall be connected together with an insulated continuous copper conductor not smaller than _________ AWG. (C) Copyright 2008 Ted "Smitty" Smith31
33
10 517.14 (C) Copyright 2008 Ted "Smitty" Smith32
34
End of Drill This is the end of the timed portion of the drill. You can now click on each slide and take your time reviewing the questions and answers. (C) Copyright 2008 Ted "Smitty" Smith33
35
The life safety branch and critical branch of the emergency system shall be kept __________________ of all other wiring systems and equipment. (C) Copyright 2008 Ted "Smitty" Smith34
36
Entirely independent 517.30(C)(1) (C) Copyright 2008 Ted "Smitty" Smith35
37
All branch circuits serving patient care areas shall be provided with an _________________ by installation in a metal raceway system, or a cable having a metallic armor or sheath assembly. (C) Copyright 2008 Ted "Smitty" Smith 36
38
An effective ground-fault current path 517.13(A) (C) Copyright 2008 Ted "Smitty" Smith37
39
The essential electrical system for these facilities shall comprise a system capable of supplying a ______________ of lighting and power service which is considered essential for life safety and orderly cessation of procedures during the time normal electrical service is interrupted for any reason. (C) Copyright 2008 Ted "Smitty" Smith38
40
Limited amount 517.25 (C) Copyright 2008 Ted "Smitty" Smith39
41
Which of the following is not allowed as an alternate source of power for the essential electrical systems in a health care facility? Generator located on the premises Battery system A second external utility service, separate from the main external utility provided service An external utility service when the normal source of power consists of a generating unit located on premises. (C) Copyright 2008 Ted "Smitty" Smith40
42
A second external utility service 517.35(A) An external utility service can only be used as an alternate source of power if the hospital is normally fed by a generating source on the premises. (C) Copyright 2008 Ted "Smitty" Smith41
43
The disconnecting means for x-ray equipment shall be operable from a location readily accessible from the ______________. (C) Copyright 2008 Ted "Smitty" Smith42
44
X-ray control 517.72(B) (C) Copyright 2008 Ted "Smitty" Smith43
45
The task illumination for the medication preparation area of a patient care area shall be permitted to be connected the critical branch and shall be arranged for _______________ connection to the alternate power source. (C) Copyright 2008 Ted "Smitty" Smith44
46
Delayed automatic 517.43(A) (C) Copyright 2008 Ted "Smitty" Smith45
47
The ___________ system shall supply major electrical equipment necessary for patient care and basic hospital operation. (C) Copyright 2008 Ted "Smitty" Smith46
48
Equipment 517.30(B)(3) (C) Copyright 2008 Ted "Smitty" Smith47
49
Isolated power systems shall be permitted to be used for __________________ areas and if used the isolated power system equipment shall be listed as isolated power equipment. (C) Copyright 2008 Ted "Smitty" Smith48
50
Critical care 517.19(F) (C) Copyright 2008 Ted "Smitty" Smith49
51
The grounding terminals of all receptacles and all non-current carrying conductive surfaces of fixed electrical equipment likely to become energized that are subject to personal contact, operating at over ________ volts, shall be connected to an insulated copper grounding conductor. (C) Copyright 2008 Ted "Smitty" Smith50
52
100 517.13(B) (C) Copyright 2008 Ted "Smitty" Smith51
53
In addition to the usual control and overcurrent protective devices, each isolated power system shall be provided with a continually operating _________________ that indicates total hazard current. (C) Copyright 2008 Ted "Smitty" Smith52
54
Line isolation monitor 517.160(B) (C) Copyright 2008 Ted "Smitty" Smith53
55
The disconnecting means for x-ray equipment shall be of adequate capacity for at least _______ percent of the input required for momentary rating or 100 percent of the input required for the long-time rating of the x-ray equipment, whichever is greater. (C) Copyright 2008 Ted "Smitty" Smith54
56
50 percent 517.72(A) (C) Copyright 2008 Ted "Smitty" Smith55
57
Illumination of means of egress, such as lighting required for corridors shall be supplied from the ____________ branch of the emergency system. (C) Copyright 2008 Ted "Smitty" Smith56
58
Life safety 517.32(A) (C) Copyright 2008 Ted "Smitty" Smith57
59
Nurse call systems shall be provided power from the __________ branch of the emergency system. (C) Copyright 2008 Ted "Smitty" Smith58
60
Critical branch 517.33(A)(5) (C) Copyright 2008 Ted "Smitty" Smith59
61
Each patient bed location shall be provided with a minimum of __________ receptacles. (C) Copyright 2008 Ted "Smitty" Smith60
62
Four 517.18(B) (C) Copyright 2008 Ted "Smitty" Smith61
63
The equipment grounding terminal buses of the normal and essential branch circuit panelboards serving the same individual patient care vicinity shall be connected together with an insulated continuous copper conductor not smaller than _________ AWG. (C) Copyright 2008 Ted "Smitty" Smith62
64
10 517.14 (C) Copyright 2008 Ted "Smitty" Smith63