Download presentation
1
Laser- based smoke detectors
Lzr-1 7251
2
LZR-1 Detector Chamber Laser Diode
Laser produces a brighter, more concentrated beam of light More signal is achieved due to the more concentrated light Smaller particles can be detected due to the brighter light Laser Diode
3
Laser Detector Benefits
Standard optical smoke detector princible Smoke Sensor (Photodiode) Focussed beam improves settled dust performance improves airborne dust performance Light Source (LED)
4
Applications suitable for LZR-1
High value property, clean environments Telecommunications switching rooms Computer Rooms Electrical equipment rooms Museums, galleries etc.. Avoid cigarette smoke, dust, steam, exhaust fumes, textile fibres
5
Detector spacing / coverage
Low Airflow ( < 10 air changes per hour) 40m2 per detector (3.5m radius) High Airflow ( > 10 air changes per hour) 25m2 per detector (2.8m radius) Extra detectors may be placed at inlets to air conditioning systems areas of high air movement inside cabinets floor and ceiling voids
6
Function of LZR-1 laser detector and a laser group in Esa1 system
PW4 analogue value of the new detector is between 100 … 500s. The Basic Environment Level (B.E.L) in panel memory is updated every 5th minute. Time constant is 21h when the value is rising (up to 65% of the new value) and 25min when it’s decreasing (65% of new value). Fire- and pre-alarm levels can be set between B.E.L + 60 … 2000s. Saturation value of panel’s memory is updated once during daytime between 10.00 … 16.00, and it can be between 2600 … 4000s. Time constant for saturation is 16 days (65% of new value). Fire level or pre-alarm level are in any case 100s under the saturation value, no matter what the configured value is. Maintenance warning level is fixed to 1200s.
7
Configuration levels vs. analogue values
Level 1 = 60s over B.E.L Level 2 = 280s “ Level 3 = 490s “ Level 4 = 710s “ Level 5 = 920s “ Level 6 = 1140s “ (default value for pre alarm) Level 7 = 1350s “ (default value for fire alarm) Level 8 = 1570s “ Level 9 = 1780s “ Level 10 = 2000s “
8
Signal processing Example 1 Fire alarm set to level L1
-Panel is filtering interferences from the signal of detectors, and will proportionate the signal between 0 and 1, so that B.E.L is 0 and alarm value is 1. Example 1 Fire alarm set to level L1 360s Fire alarm level = B.E.L + 60s (level 1) 330s Measuring value 330s proportion value is 0.5 300s B.E.L 300s
9
Signal processing Example 2 Fire alarm set to level L7
1350s Fire alarm level = B.E.L s (level 7) 330s Measuring value 330s Proportion value is 0.022 300s B.E.L 300s
10
Function of a laser group
Laser detectors in the same fire zone will automatically form a laser group There is no need for configuration. Proportion values of all detectors in same laser group are squared and added together. If the sum value is 1 or more, it will activate the alarm, which is shown from the address where the proportion value is highest. If the value of a single detector is 1 or more, it will activate the alarm. The function is the same with Fire-alarm and Pre-alarm
11
Grouping Algorithm Signal from detectors in close proximity is summed using a ‘mean square’ algorithm - 2= A 2 + B 2 + C 2 Grouping of detectors gives a higher effective sensitivity with less risk of false alarms For best performance always use more than one detector in any area
12
Function of a laser group
Example 1: Three laser detectors in the same fire zone Fire zone X Laser group Proportion value Square rooting ² ² ² = <1 No Alarm
13
Function of a laser group
Example 2: Four laser detectors in the same fire zone Fire zone X Laser group Proportion value Square rooting ² ² ² ² = >1 ALARM -- Fire alarm is shown from this address.
14
Selection of Sensitivity
High Sensitivity Pre-Alarm Alarm sensitivity from 0.01% / ft to 1.0%/ft Set Pre-alarm sensitivity just high enough to meet ‘hot-wire’ test Monitor system for three months Use lower sensitivity alarm (> 1.63%/m)
15
Analyzing of LZR-1 signals
Analogue values of LZR-1 detector can be seen on access level three There are six PW4 values at one window for one detector ZONE 0001 ADDR ENABLED LASER SENSOR A2 S28 C204 M186 P 0 F 0 A = Basic Enviroment Level (BEL), from which two least significant digits are removed. In this case A2 can be between 200s … 299s. S = Saturation value, from which the two least significant digits are removed. In this case S28 can be between 2800s … 2899s. C = Last value from detector without filtering. M = Value after filtering (lowest of the last tree readings). P = % of Pre alarm level. F = % of Fire alarm level.
16
Test: Aspirating system vs. ESA1+LZR-1
ASPIRATING TUBE AND DETECTORS VESDA / AIR-SENSE CENTRAL UNIT DETAILS POWER ELECTRONIC CABINETS
17
Smoke test 1 Fire Zone 1 00:00 START 00:55 ESA FIRE 01:20 ESA1 2nd FIRE 01:25 ESA1 3rd FIRE 01:40 VESDA FIRE 01:45 ESA1 4th FIRE Smoke test 2 Fire Zone 1 00:00 START 00:45 VESDA WARNING 00:55 ESA FIRE 01:10 VESDA FIRE 01:15 ESA1 2nd FIRE 01:20 ESA 3rd FIRE 01:25 ESA 4th FIRE Smoke test 1 Fire Zone 2 00:00 START 00:50 VESDA WARNING 01:05 ESA FIRE 01:15 VESDA FIRE 01:15 ESA1 2nd FIRE 01:20 ESA1 3rd FIRE 01:25 ESA1 4th FIRE
Similar presentations
© 2025 SlidePlayer.com. Inc.
All rights reserved.