BPA RTU Winter Operation Presented to: RTUG August 2010 Presented by: Kathryn Hile, The Cadmus Group Howard Reichmuth, New Buildings Institute
2
B O N N E V I L L E P O W E R A D M I N I S T R A T I O N Winter Analysis Overview Improvements to analysis template Downloading and organizing data Fan operation – schedules Gas pack operation Heat pump operation Winter economizing (or cooling) Additional opportunities Lessons learned 2
3
B O N N E V I L L E P O W E R A D M I N I S T R A T I O N Winter Sample 45 serviced RTUs –32 at 3 sites in Puget Sound area –13 at 3 sites in Tri-Cities area 4 baseline RTUs in Tri-Cities: serviced spring 2010 3 RTU TypeNumber of Units SubtractionsUnits Analyzed All Electric1 1 Gas Pack34 529 Heat Pump10 0
4
B O N N E V I L L E P O W E R A D M I N I S T R A T I O N Analysis Template Improvements All winter data in one spreadsheet (at hour level) Much smaller analysis files Automation with SAS and VBA Time series dynamic graph Both SA min and SA max plotted in time series 4
5
B O N N E V I L L E P O W E R A D M I N I S T R A T I O N 5 Downloading and Cleaning Data HOBOlink Excel Visual Basic SAS
6
B O N N E V I L L E P O W E R A D M I N I S T R A T I O N Data Preparation Process Download zip file from HOBOlink with data from all HOBOs Organize by HOBO Create one file for each HOBO, based on power, one sheet for each two-week period Import to SAS with keys for CT size, WattNode scale factor, fan low and fan high 6
7
B O N N E V I L L E P O W E R A D M I N I S T R A T I O N Data Preparation Calculate hourly and daily minimums, maximums, totals and averages Export to Excel Only full 24 hour days used to create energy signature View data in hourly compressor map, dynamic time series and energy signature 7
8
B O N N E V I L L E P O W E R A D M I N I S T R A T I O N Data Collection Issues Some (not many) sensors failed last winter, and four sites required troubleshooting to fix –Splitters –AC adapter – battery failure Downloaded data –One site: two units had nonsensical data –One site: three sensors just disappeared from HOBOlink – result of the AT&T upgrades last fall? 8
9
B O N N E V I L L E P O W E R A D M I N I S T R A T I O N Calculating Percent Outside Air 9
10
B O N N E V I L L E P O W E R A D M I N I S T R A T I O N Winter Operation Schedules – fan ON or AUTO Fan kW, duty, base load Typical signatures 10
11
B O N N E V I L L E P O W E R A D M I N I S T R A T I O N Fan Mode = ON Winter numbers similar to pilot data 11 Winter DataSummer Pilot Post-Servicing Data RTU Fan kWFan DutyBase LoadFan kWFan DutyBase Load RTU6 0.6991% 15.11 0.6588% 13.68 HP15 0.65100% 15.66 0.63100% 15.06 HP17 1.40100% 33.51 1.4887% 30.96 GP5 0.9699% 22.90 0.8796% 20.13 GP6 2.6999% 63.73 2.6399% 62.53 AC10 0.89100% 21.38 0.92100% 22.19 AC6 2.6638% 24.13 2.9425% 17.42 RTU1 1.4999% 35.28 1.4693% 32.82 RTU3 0.93100% 22.35 0.9194% 20.35 RTU6 1.7340% 16.43 1.7335% 14.43
12
B O N N E V I L L E P O W E R A D M I N I S T R A T I O N Fan Mode = AUTO Small sample Fan kW very close; fan duty and base load differed 12 Winter DataSummer Pilot Post-Servicing Data RTU Fan kWFan DutyBase LoadFan kWFan DutyBase Load RTU5 1.8476% 33.48 2.1285% 43.40 RTU3 2.065% 2.68 2.0128% 13.50 HP2 0.608% 1.20 0.69100% 16.45 GP7 1.2826% 7.86 1.2961% 18.71 GP8 1.352% 0.76 1.2314% 4.07 AC9 1.225% 1.46 1.22100% 29.31
13
B O N N E V I L L E P O W E R A D M I N I S T R A T I O N Gas Pack Signatures 24 of 32 energy signatures were as expected 8 needed more investigation to understand performance 13
14
B O N N E V I L L E P O W E R A D M I N I S T R A T I O N Gas Pack Typical Signature 1 14 Operates same set schedule each day
15
B O N N E V I L L E P O W E R A D M I N I S T R A T I O N Gas Pack Compressor Map Same RTU as previous slide 15
16
B O N N E V I L L E P O W E R A D M I N I S T R A T I O N Gas Pack Time Series 16
17
B O N N E V I L L E P O W E R A D M I N I S T R A T I O N Gas Pack Typical Signature 2 17 Operates slightly longer at lower temperatures
18
B O N N E V I L L E P O W E R A D M I N I S T R A T I O N Compressor Map Same RTU, compressor map 18
19
B O N N E V I L L E P O W E R A D M I N I S T R A T I O N Gas Pack Typical Signature 3 19 Two signatures – Monday – Saturday, and Sunday Unit may have reached setback temperatures when average daily temperatures below 40
20
B O N N E V I L L E P O W E R A D M I N I S T R A T I O N Gas Pack Findings Fan power calculated this winter was close to metered pilot data in almost all cases Fan duty was close to metered pilot data in units with fan scheduled ON Fan duty and base load were difficult to predict from summer metered data when fan ran in AUTO mode 20
21
B O N N E V I L L E P O W E R A D M I N I S T R A T I O N Winter Heat Pump Operation Heat pumps were trickier Smaller sample, all at a notorious site Units served either offices or fabrication (manufacturing) spaces Four units did not have economizers 21
22
B O N N E V I L L E P O W E R A D M I N I S T R A T I O N Heat Pump Typical Operation Energy increases as temperatures decrease Steeper slope than for cooling 22
23
B O N N E V I L L E P O W E R A D M I N I S T R A T I O N Heat Pump Compressor Map Same unit as previous slide 23
24
B O N N E V I L L E P O W E R A D M I N I S T R A T I O N Heat Pump Time Series 24
25
B O N N E V I L L E P O W E R A D M I N I S T R A T I O N Heat Pump Findings Typical heat pumps will have a second sloped line Need summer data (spring was not warm enough) to connect winter and summer usage Will use that to calculate and predict total annual energy use, not just cooling and fan 25
26
B O N N E V I L L E P O W E R A D M I N I S T R A T I O N Winter Economizing Some units modulate dampers to take advantage of free cooling. SA min and SA max track OAT Three speed fan? 26
27
B O N N E V I L L E P O W E R A D M I N I S T R A T I O N Heating to Economizing Fan operates at different power when heating or economizing 27
28
B O N N E V I L L E P O W E R A D M I N I S T R A T I O N Atypical Performance Balance point below the range of monitored temperatures Cooling at low temperatures Units serving the same space Two units with bad data 28
29
B O N N E V I L L E P O W E R A D M I N I S T R A T I O N Low Balance Point 29
30
B O N N E V I L L E P O W E R A D M I N I S T R A T I O N Cooling at Low Temperatures Mechanical cooling at 25 degrees 30
31
B O N N E V I L L E P O W E R A D M I N I S T R A T I O N Cooling at Low Temperatures 31
32
B O N N E V I L L E P O W E R A D M I N I S T R A T I O N Heating a.m., Cooling p.m. Two different max kW, at 3.5 kW, cooling (SA min at 55) and heating 4.5 kW (SA max at 90) 32
33
B O N N E V I L L E P O W E R A D M I N I S T R A T I O N Someone’s Been in my RTU… 33
34
B O N N E V I L L E P O W E R A D M I N I S T R A T I O N …Twice! 34
35
B O N N E V I L L E P O W E R A D M I N I S T R A T I O N Economizer Findings Cooling at temperatures below 40 degrees. Why? Controls? Or dampers didn’t modulate because broken? Bad sensor? Comments? Significant savings opportunity? Cooling in the 50-60 degree F. Could economizer changeover temperature be increased for additional savings? Winter is a good (better than summer?) candidate for economizer savings 35
36
B O N N E V I L L E P O W E R A D M I N I S T R A T I O N Preliminary Annual Signature Winter: –Standard, flat gas pack –Standard, sloped – but could we just take an average and keep slope at 0? –Gas pack with two occupancy schedules –Heat pump – is this signature messier than it would be during summer cooling? TBD. Atypical. 36
37
B O N N E V I L L E P O W E R A D M I N I S T R A T I O N Ex: AC w/Elect Resistance Heating 37
38
B O N N E V I L L E P O W E R A D M I N I S T R A T I O N AC Compressor Map 38
39
B O N N E V I L L E P O W E R A D M I N I S T R A T I O N AC Time Series 39
40
B O N N E V I L L E P O W E R A D M I N I S T R A T I O N Next Steps in Research Draft annualized savings methodology with separate characterizations of annual operation for summer and winter Data block interval analysis Recommendations regarding fan schedule persistence Additional persistence analysis Measure life implications from the data Updated M&V protocol recommendations 40
41
B O N N E V I L L E P O W E R A D M I N I S T R A T I O N Web-Enabled Thermostats Test the web-enabled thermostat as an M&V tool as a substitute for data-loggers –Data-friendliness? –How complete is it? –What does it look like? Use the current analysis protocol and modify it for these data 41