Current operation (black keys) Descriptions Parameter / protection setting (blue keys) Main points to remember A B C D ? SEPAM UMIs SEPAM UMI OPERATION.

Similar presentations


Presentation on theme: "Current operation (black keys) Descriptions Parameter / protection setting (blue keys) Main points to remember A B C D ? SEPAM UMIs SEPAM UMI OPERATION."— Presentation transcript:

1 Current operation (black keys) Descriptions Parameter / protection setting (blue keys) Main points to remember A B C D ? SEPAM UMIs SEPAM UMI OPERATION Use the different UMIs

2 Series 80 Remote advanced UMI Integrated advanced UMI Mimic-based UMI Series 20 & 40 Basic UMI Different SEPAM UMIs

3 Current operation (black keys) Descriptions Parameter / protection setting (blue keys) Main points to remember A B C D ? SEPAM UMIs DESCRIPTIONS Descriptions

4 Basic UMI Display Series 80Series 20 & 40 –none on front panel Keypad LEDs –Reset key –9 LEDs –none – 2 LEDs visible on rear panel indicate Sepam operating status

5 Remote advanced UMI, and integrated UMI Graphic LCD display, 128 x 64 pixels, with backlighting 9-key keypad –Black keys for current operation –Blue keys for parameter and protection setting LEDs –2 LEDs for Sepam operating status –9 indication LEDs Series 20, 40 & 80 The remote UMI must be connected to a base unit without UMI by a CCA77x cord.

6 Mimic-base UMI Graphic LCD display, 128 x 240 pixels, with backlighting 9-key keypad –Black keys for current operation and parameter/protection setting –Blue key to confirm selection –White and red keys to control devices LEDs –2 LEDs for Sepam operating status –9 indication LEDs Remote / Local / Test selector switch Series 80

7 Description of advanced UMI PC connection Green ON LED Red Fault LED 9 indication LEDs Metering Switchgear, network and machine diagnosis Alarms LED test Acknowledge and clear alarms Reset Sepam Entry of password Setting of protection functions activated via SFT2841 Sepam characteristics Confirm user choices Move cursor up Move cursor down Series 20, 40 & 80

8 Description of advanced UMI DoorCartridge Battery –same display as SEPAM 20 & 40 –plus: Series 80

9 Entry of password MeteringDiagnosis LED test Alarms Protection setting Sepam characteristics Acknowledge and clear alarms Reset Sepam Confirm user choices Move cursor up Move cursor down Description of mimic-based UMI Door Cartridge Battery PC connection Green ON LED Red Fault LED 9 yellow indication LEDs Close switchgear Open switchgear 3-position selector switch Confirm user choices Move cursor up Move cursor down Mimic diagram Series 80

10 3 categories of users Operator: –Access to all data in read mode only –Clear/Reset actions Personnel qualified to set protection functions –Know the «Setting» code (1 key) –Operator + access to protection settings Personnel qualified to set Sepam parameters –Know the «Parameters» code (2 keys) –Operator + access to protection settings + access to Sepam parameters

11 Working language All the texts and messages are available in 2 languages: –English, the working language by default –a second, local language –French or Spanish –customized language, created via SFT2840 software

12 Current operation (black keys) Descriptions Parameter / protection setting (blue keys) Main points to remember A B C D ? SEPAM UMIs CURRENT OPERATION (BLACK KEYS) Current operation (black keys)

13 Using the menus Chosen directly from a series of screens in a loop: Press the function key repeatedly to scroll the menus Series 20

14 Example: metering loop Using the menus 2.Then a series of screens in a loop: 1.A menu page opens for the user to choose a type of data – Press the function key repeatedly to scroll – Press or to select an item – Confirm via the key After the user presses the function key: Series 40 & 80 Vector

15 4 main functions (black keys) MeteringDiagnosisAlarms Reset Series 80 reset Series 20 & 40

16 Metering Displays the measurements provided by Sepam Series 20 "Vector" menu: on mimic-based UMI only Series 40 & 80 Vector l1 l2 l3 lo l1 l2 l3 Imoy1 2 3 Imax1 2 3 T1 to T8 V1 V2 V3 U12,32,13 Vo F RMS current measurement Residual current, digital and bargraph Phase current bargraph Average current value Peak demand current Temperature on sensor Phase-to-neutral voltage Phase-to-phase voltage Residual voltage Frequency

17 Diagnosis Information on switching device and additional measurements to facilitate fault analysis Series 40 & 80Series 20 trip l1, l2, l3, lo unbalance breaking dev. kA 2 E Istart Tstart Nb st, waitT Phase and residual trip currents Unbalance ration (negative sequence) Trip circuit supervision, nb. of operations, operating and charging time Cumulative breaking current Heat rise, Overheating, time before tripping, time before starting authorization Starting current and time Start inhibit time/nb of starts before inhibition Running hour counter Positive sequence voltage Ch Vd Diagnosis Trip -1 Trip -3 Trip -2 Trip -4 Trip 0 Diagnosis

18 "List" loop: press the button to clear the alarms displayed Used to look up the 16 most recent alarms not yet acknowledged Alarms Alarms are not saved in the event of a power failure. Series 40 & 80Series 20 Alarms ListDetails

19 «Alarms» menu (cont'd) “Alarm details” loop –The loop presents the details of alarms that have not been cleared (16 maximum). –Alarms that have not been acknowledged are differentiated from acknowledged alarms by the icon: Acknowledged alarm Unacknowledged alarm 2 cases occur when the clear key is pressed –The alarm is not acknowledged: the alarm is acknowledged but not cleared. –The alarm is acknowledged: the alarm is cleared and the user goes on to the next one or to the menu if there are no more alarms. Series 40 & 80

20 Reset Resets Sepam and / or releases protection latching reset Series 20, 40 & 80 PHASE FAULT

21 LED test Runs a sequence of LED and display tests No effect when an alarm is present Series 20, 40 & 80

22 Current operation (black keys) Descriptions Parameter / protection setting (blue keys) Main points to remember A B C D ? SEPAM UMIs PARAMETER / PROTECTION SETTING Parameter / protection setting (blue keys)

23 Wrench key For the entry of passwords to access the different modes: –protection setting –parameter setting and return to "operation" mode = no password Series 20, 40 & 80 Password

24 Status key To display and enter Sepam general settings: –protected equipment characteristics –optional modules Series 20

25 «General settings» menu Series 40Series 80Series 20 modbus MSA TC / TP O1 main LDC Sepam info MES I / O communication parameter setting analog output module option nb, type, ratio of sensors parameter setting output O1 setting mode, modif, passwords CB control, choice of use of inputs type, version input/output module option In put reading, output reading & testing General settings GeneralModules I/O test Logipam

26 Protection To display, set and activate/deactivate protection functions Series 40 & 80Series 20 Trip

27 «Protection» menu (cont'd) There is one field for each protection function (ANSI code), provided access to: Some protection settings may not be adjusted. A specific screen informs the user when this is the case. Only protection functions with at least one unit activated are displayed. Series 80 –protection threshold (if protection setting is allowed on the DSM module). –time delay setting

28 Current operation (black keys) Descriptions Parameter / protection setting (blue keys) Main points to remember A B C D ? SEPAM UMIs MAIN POINTS TO REMEMBER

29 Main points to remember 3 Different UMI available matching to the customer needs Protected by PASS WORD for 3 categories of users. Displays the Measurements provided by Sepam Diagnosis of Switching device and Network Displays the 16 most recent alarms Manages Acknowledgement of alarm and Reset Set Protection functions for Sepam 20,40 and Adjust some for Sepam 80 Remote UMI Mimic UMI Advanced UMI


Download ppt "Current operation (black keys) Descriptions Parameter / protection setting (blue keys) Main points to remember A B C D ? SEPAM UMIs SEPAM UMI OPERATION."