2
Fuses in ABB - General Presentation
3
Fuses in ABB - General Presentation
4
Fuses in ABB - General Presentation
MV fuses portfolio MV DIN HRC fuses Back-up fuses Competitors offer ABB offer 3,6 - 7,2 kV (6, A), 192, 292, 442 mm ( A) 192 mm, ( A) 292 mm kV (6, A), 192, 292, 442, 537 mm ( A) 292 mm, ( A) 442 mm ,5 kV (6, A), 292, 367, 442 mm (6 - 63A) 292, 367, 442 mm, ( A) 442 mm kV (6, A), 292, 442, 537 mm ( A) 442 mm, ( A) 537 mm kV (6,3 - 63A), 537 mm (6,3 - 40A), 537 mm
5
High Rupturing Capacity Fuses
Product Overview Fuses type CEF High Rupturing Capacity Fuses Features: High rupturing capacity Indoor/Outdoor Low minimum breaking current Low power losses /suitable in compact switchgear Low arc-voltage High breaking capacity High current limitation Dimensions acc.to DIN/IEC & BS Standards rated voltage 3, kV rated current 6, A
6
Fuses for Voltage Transformers
Product Overview Fuses type WBP / BRT Fuses for Voltage Transformers Features: Unlimited breaking capacity Short-circuit current limiting Small dimensions Intended for protection of circuits powered by voltage transformer Intended for ABB voltage transformers Type WBP - Indoor design. Rated voltages 7.2, 12, 24, 36 kV. Rated current 0,4 - 0,8 A. Type BRT - Outdoor design. Rated voltages 7.2; 12; 17.5; 24; 36 kV. Rated current 0,8 A.
7
Fuses for MOTOR circuit applications
Product Overview Fuses type CMF Fuses for MOTOR circuit applications Features: High voltage current limiting Low power losses Low minimum breaking current High breaking capacity Short circuit current limitation Dimensions acc.to DIN/IEC & BS Standards rated voltage 3, kV rated current A
8
Fuses for RAILWAY TRACTION
Product Overview Fuses type WBT / BWT Fuses for RAILWAY TRACTION Features: High rupturing capacity Short circuit current limiting Low switching voltages Type: WBT..., Nominal voltage kV DC. Nominal current In 0, A Breaking current up to 50kA Type: BWT Rated voltage Un 3 kV DC Rated current In A Minimum breaking current Imin 4 x In ‘Specifica Generale per la Fornitura di Valvole Fusibili A.T. per Circuiti C.C’. Trenitalia (Italian Railways)
9
Automated Production Line of ABB fuse link
Product Overview Fuses type CEF/CMF Automated Production Line of ABB fuse link
10
HV Fuses AUSTRALIA CHINA HONG KONG INDIA INDONESIA JAPAN KOREA
ASIA: AUSTRALIA CHINA HONG KONG INDIA INDONESIA JAPAN KOREA NEW ZEALAND MALAYSIA PHILIPPINES SINGAPORE TAIWAN THAILAND VIETNAM EUROPE: WE+CEE AUSTRIA BELGIUM BELARUS BULGARIA CROATIA CZECH REP. DENMARK ESTONIA FINLAND FRANCE GERMANY GREAT BRITAIN GREECE HUNGARY ICELAND IRELAND ITALY LATVIA LITHUANIA LUXEMBOURG NORWAY NETHERLANDS POLAND PORTUGAL ROMANIA SLOVAKIA SPAIN SWEDEN SWITZERLAND MIDDLE EAST: EGYPT ISRAEL JORDAN KUWAIT LEBANON SAUDI ARABIA SYRIA TUNISIA TURKEY UNITED ARAB EMIRATES SOUTH&NORTH AMERICA: ARGENTINA BRAZIL CANADA CHILE COLOMBIA ECUADOR MEXICO PANAMA PERU USA VENEZUELA AFRICA: SOUTH AFRICA TANZANIA
11
HV fuses – normal operating conditions
Maximum ambient temperature +400C Minimum ambient temperature is -250C The altitude does not exceed 1000m (3300ft) The ambient air is not excessively polluted by dust, smoke, corrosive or flammable gases, vapour or salt Vibrations due to causes external to fuses or earth tremors are negligible Typical condition of humidity for indoor installations are fulfilled
12
HV fuses – Standards IEC 60282-1 High Voltage Fuses
IEC High Voltage Fuses for external protection of shunt Power capacitor IEC Specification for high voltage fuse links for motor circuit applications IEC Application guide for selection of fuse links of high voltage fuses for transformers circuit applications
13
HV fuses – design
14
HV fuses – general rules
15
HV fuses – Fuse parameters
Dimensions
16
HV fuses – Fuse parameters
Nameplate Fuse types: CEF: indoor CEF-BS: with tags CEF-U: outdoor CMF: motor CMF-BS: with tags
17
HV fuses – Graphic definition of currents
18
HV fuses – Fuse operation
19
HV fuses – general rules
20
HV fuses – Graphic definition of currents
21
HV fuses – general rules
Minimum breaking current
22
HV fuses – general rules
Minimum breaking current
23
HV fuses – general rules
Minimum Melting Time Total Clearing Time
24
HV fuses – Cut off current
25
HV fuses – Cut off current - ANSI
26
HV fuses – Transformer protection
27
HV fuses – Transformer protection
28
HV fuses – general rules
29
HV fuses – Transformer protection
30
HV fuses – Coordination current limiting fuses/cut-outs
31
HV fuses – Coordination current limiting fuses/cut-outs
32
HV fuses – Your questions