Download presentation
Presentation is loading. Please wait.
Published byAlannah Jacobs Modified over 9 years ago
1
Copyright 2008 Ted "Smitty" Smith
2
Left click on the presentation ICON located at the bottom of the slide directory to the left of the this slide. Each slide will transition to the correct answer automatically in 2:00 minutes. The correct answer will transition in 10 seconds. You may also left click on the slide to manually transition. Do not worry about writing down the correct answer for now. You will have the opportunity to do that at the end of the two minute drill Good luck Remember to start the slide show to activate the timer. Copyright 2005 Ted "Smitty" Smith
3
This drill is a mixture of calculations and code look up questions. You have seen many of them before. Focus on time. Try to find all the answers before the slide transitions. Remember do not worry about writing down the right answer for now. When you reach the end all of the slides will be repeated without the timer so you can take your time to find the ones you missed and write down the correct answers then. Click on the slide to proceed. Copyright 2005 Ted "Smitty" Smith
4
1. Equipment grounding conductors shall be permitted to be sectioned within a listed multiconductor cable, provided the combined _______________ complies with 250.122. A. Current and load B. Voltages of all applied loads C. Circular mill area D. None of the above Copyright 2008 Ted "Smitty" Smith
5
Circular mill area 310.13 Copyright 2005 Ted "Smitty" Smith
6
A conductor with insulation marked ZW will be suitable for use in all: Wet locations Hospital operating rooms House boats None of the above Copyright 2005 Ted "Smitty" Smith
7
Wet locations Table 310.13(A) Copyright 2005 Ted "Smitty" Smith
8
Where more than one calculated or ____________ ampacity could apply for a given circuit, the lowest value shall be used. Determined Tabulated Corrected Derated Copyright 2005 Ted "Smitty" Smith
9
Tabulated 310.15(A)(2) Copyright 2005 Ted "Smitty" Smith
10
Where bare or covered conductors are installed with insulated conductors, the temperature rating of the bare or covered conductor shall be _____________ for the purpose of determining ampacity Equal to the lowest temperature rating of the insulated conductors Equal to the highest temperature rating of the insulated conductors Equal to the average temperature ratings of the insulated conductors. None of the above Copyright 2005 Ted "Smitty" Smith
11
Equal to the lowest temperature rating of the insulated conductors 310.15(B)(3) Copyright 2005 Ted "Smitty" Smith
12
A 2 AWG TW conductor is installed in a location where the ambient temperature is expected to be 108 degrees F. The temperature correction factor for conductor ampacity in this location is _________. .96 .88 .82 .71 Copyright 2005 Ted "Smitty" Smith
13
.71 Table 310.16 Bottom, 60c wire at 102 degrees F. I recommend using a straight edge when using NEC tables. A clear plastic 6 inch ruler is best. Copyright 2005 Ted "Smitty" Smith
14
If the ambient temperature is 30 degrees C, the minimum insulation that a conductor must have and still have the capacity to carry current is __________ 60 C 105 C 90 C Any of these Copyright 2008 Ted "Smitty" Smith
15
Any of these All of these conductors are rated for 30 degrees C Copyright 2005 Ted "Smitty" Smith
16
Determine the minimum sized THHN aluminum conductor that can be installed to feed a load of 104 amperes that is located in a freezer that has an ambient temperature of 22 degrees Celsius. 1 AWG 2 AWG 3 AWG 1/0 AWG Copyright 2008 Ted "Smitty" Smith
17
100 A 1/0 AWG 110.14(c) will require you handle 104 amperes in the 75 C column, so another two wire sizes will be required, therefore 1/0. Copyright 2005 Ted "Smitty" Smith
18
The ampacity of six-current carrying 10 AWG RHW aluminum conductors in a raceway in an ambient temperature of 75 degrees F is ___________ › 30A › 22A › 16A › 12A Copyright 2005 Ted "Smitty" Smith
19
15.75A Table 310.16 and 310.15(B)(2)(a) Copyright 2005 Ted "Smitty" Smith
20
The ampacity of nine current carrying 10 AWG THW conductors installed in a 20 inch long raceway is _________. › 25A › 30A › 35A › None of these Copyright 2005 Ted "Smitty" Smith
21
35A Bundle factors do not apply to raceways that are 24 inches in length or less. Copyright 2005 Ted "Smitty" Smith
22
Enclosures for switches or over current devices shall not be used as junction boxes, auxiliary gutters, or raceways for conductors feeding through or tapping off to other switches or over current devices, unless adequate space for this purpose is provided. The conductors shall not fill the wiring space at any cross section to more than _______ percent of the cross-sectional area of the space. › 20 › 25 › 35 › 40 Copyright 2005 Ted "Smitty" Smith
23
40 312.8 Copyright 2005 Ted "Smitty" Smith
24
What is the area in square inches for a 14 AWG RHW without outer covering conductor? › 0.0209 › 0.0172 › 0.0252 › 0.0278 Copyright 2005 Ted "Smitty" Smith
25
0.0209 Table 5, Chapter 9 Copyright 2005 Ted "Smitty" Smith
26
What is the cross sectional area in square inches for 12 AWG RHH with outer covering conductors? › 0.0117 › 0.0353 › 0.0252 › 0.0327 Copyright 2005 Ted "Smitty" Smith
27
0.0353 Table 5, Chapter 9 Copyright 2005 Ted "Smitty" Smith
28
A 200A feeder installed in Schedule 80 rigid non-metallic conduit has three 3/0 AWG THHN, one 2 AWG THHN and one 6 AWG THHN conductors. What is the minimum sized raceway required? 2 inch 2.5 inch 3 inch 3.5 inch Copyright 2005 Ted "Smitty" Smith
29
2 inch Copyright 2005 Ted "Smitty" Smith
30
What size rigid metal nipple is required for three 4/0 AWG THHN, one 1/0 AWG THHN and one 4 AWG THHN conductors? 1.5 inch 2 inch 2.5 inch None of these Copyright 2005 Ted "Smitty" Smith
31
1.5 inch 1.239 60% fill based on note 4 to Table 1 Copyright 2005 Ted "Smitty" Smith
32
What size outlet box is required for one 12/2 NM cable that terminates on a switch, on 12/3 NM cable that terminates on a receptacle, and the box has manufactured internal cable clamps. › 4 x 1 1/4 square › 4 x 1 1/2 square › 4 x 2 1/8 square › None of these Copyright 2005 Ted "Smitty" Smith
33
4 x 2 1/8 Square Copyright 2005 Ted "Smitty" Smith
34
Machine screw type fasteners that engage not less than two and thread forming machine screws that engage not less than two threads in the enclosure may be used to mount equipment grounding bars, buses and lugs to enclosures. › True › False Copyright 2005 Ted "Smitty" Smith
35
True 250.8 Copyright 2005 Ted "Smitty" Smith
36
What is the net computed demand load for the air conditioning and heat for a 40 unit multifamily building that has an air conditioner ( 3hp, 3.91 kW 230V) and two baseboard heaters (3 kW) in each unit. › 160 kW › 240 kW › 6 kW › 5 kW Copyright 2005 Ted "Smitty" Smith
37
240 kW Heat is larger load than A/C Copyright 2005 Ted "Smitty" Smith
38
What is the demand load on the main service entrance of an apartment complex that is supplied with a 120/208V single phase service for twelve 3.25 kW ovens? 10 kW 18 kW 15 kW 20 kW Copyright 2005 Ted "Smitty" Smith
39
18 kW Copyright 2005 Ted "Smitty" Smith
40
What is the general lighting load for a dwelling unit with 2,700 square feet of living space not including open porches, garages, or unused or unfinished spaces not adaptable for future use? › 8100 VA › 12600 VA › 2700 VA › 6480 VA Copyright 2005 Ted "Smitty" Smith
41
8100 VA Copyright 2005 Ted "Smitty" Smith
42
What is the feeder or service demand for two 3 kW ranges? › 3 kW › 4.8 kW › 4.5 kW › 3.9 kW Copyright 2005 Ted "Smitty" Smith
43
4.5 kW Copyright 2005 Ted "Smitty" Smith
44
If the total demand is 30 kW for a 120/240V dwelling unit, what is the minimum sized service and feeder copper conductor size allowed? 4 AWG 3/0 AWG 2 AWG 1/0 AWG Copyright 2005 Ted "Smitty" Smith
45
2 AWG 30,000/240= 125A Table 310.15(B)(6) shows 2 AWG copper for 125A services Copyright 2005 Ted "Smitty" Smith
46
What is the demand on the main service entrance of a single family dwelling of a range with a nameplate rating of 13.9 kVA at 240 volts? › 8000 VA › 8800 VA › 9600 VA › 10000 VA Copyright 2005 Ted "Smitty" Smith
47
8800 VA Table 220.55 Note 1 Copyright 2005 Ted "Smitty" Smith
48
The disconnecting means for surge protective devices shall not be considered a disconnecting means when determining the maximum number of handles for the service disconnecting means. True False Copyright 2005 Ted "Smitty" Smith
49
True 230.71(A)(2) Copyright 2005 Ted "Smitty" Smith
50
Metal enclosures and raceways for service conductors and equipment shall be connected to the _______________ system conductor if the electrical system is grounded or to the ________________ conductor for electrical systems that are not grounded. Grounded/ ungrounded Grounded/ grounding electrode Grounding/ grounded None of the above Copyright 2005 Ted "Smitty" Smith
51
Grounded/ Grounding electrode 250.80 Copyright 2005 Ted "Smitty" Smith
52
Each of the slides will now be repeated. They are not timed in this segment. To change a slide, click on the side with your left mouse button. Be sure to physically look up the answers in your code book to improve your look up speed and skill. Copyright 2005 Ted "Smitty" Smith
53
1. Equipment grounding conductors shall be permitted to be sectioned within a listed multiconductor cable, provided the combined _______________ complies with 250.122. A. Current and load B. Voltages of all applied loads C. Circular mill area D. None of the above Copyright 2008 Ted "Smitty" Smith
54
Circular mill area 310.13 Copyright 2005 Ted "Smitty" Smith
55
A conductor with insulation marked ZW will be suitable for use in all: Wet locations Hospital operating rooms House boats None of the above Copyright 2005 Ted "Smitty" Smith
56
Wet locations Table 310.13(A) Copyright 2005 Ted "Smitty" Smith
57
Where more than one calculated or ____________ ampacity could apply for a given circuit, the lowest value shall be used. Determined Tabulated Corrected Derated Copyright 2005 Ted "Smitty" Smith
58
Tabulated 310.15(A)(2) Copyright 2005 Ted "Smitty" Smith
59
Where bare or covered conductors are installed with insulated conductors, the temperature rating of the bare or covered conductor shall be _____________ for the purpose of determining ampacity Equal to the lowest temperature rating of the insulated conductors Equal to the highest temperature rating of the insulated conductors Equal to the average temperature ratings of the insulated conductors. None of the above Copyright 2005 Ted "Smitty" Smith
60
Equal to the lowest temperature rating of the insulated conductors 310.15(B)(3) Copyright 2005 Ted "Smitty" Smith
61
A 2 AWG TW conductor is installed in a location where the ambient temperature is expected to be 108 degrees F. The temperature correction factor for conductor ampacity in this location is _________. .96 .88 .82 .71 Copyright 2005 Ted "Smitty" Smith
62
.71 Table 310.16 Bottom, 60c wire at 102 degrees F. I recommend using a straight edge when using NEC tables. A clear plastic 6 inch ruler is best. Copyright 2005 Ted "Smitty" Smith
63
If the ambient temperature is 30 degrees C, the minimum insulation that a conductor must have and still have the capacity to carry current is __________ 60 C 105 C 90 C Any of these Copyright 2008 Ted "Smitty" Smith
64
Any of these All of these conductors are rated for 30 degrees C Copyright 2005 Ted "Smitty" Smith
65
Determine the minimum sized THHN aluminum conductor that can be installed to feed a load of 104 amperes that is located in a freezer that has an ambient temperature of 22 degrees Celsius. 1 AWG 2 AWG 3 AWG 1/0 AWG Copyright 2008 Ted "Smitty" Smith
66
100 A 1/0 AWG 110.14(c) will require you handle 104 amperes in the 75 C column, so another two wire sizes will be required, therefore 1/0. Copyright 2005 Ted "Smitty" Smith
67
The ampacity of six-current carrying 10 AWG RHW aluminum conductors in a raceway in an ambient temperature of 75 degrees F is ___________ › 30A › 22A › 16A › 12A Copyright 2005 Ted "Smitty" Smith
68
15.75A Table 310.16 and 310.15(B)(2)(a) Copyright 2005 Ted "Smitty" Smith
69
The ampacity of nine current carrying 10 AWG THW conductors installed in a 20 inch long raceway is _________. › 25A › 30A › 35A › None of these Copyright 2005 Ted "Smitty" Smith
70
35A Bundle factors do not apply to raceways that are 24 inches in length or less. Copyright 2005 Ted "Smitty" Smith
71
Enclosures for switches or over current devices shall not be used as junction boxes, auxiliary gutters, or raceways for conductors feeding through or tapping off to other switches or over current devices, unless adequate space for this purpose is provided. The conductors shall not fill the wiring space at any cross section to more than _______ percent of the cross-sectional area of the space. › 20 › 25 › 35 › 40 Copyright 2005 Ted "Smitty" Smith
72
40 312.8 Copyright 2005 Ted "Smitty" Smith
73
What is the area in square inches for a 14 AWG RHW without outer covering conductor? › 0.0209 › 0.0172 › 0.0252 › 0.0278 Copyright 2005 Ted "Smitty" Smith
74
0.0209 Table 5, Chapter 9 Copyright 2005 Ted "Smitty" Smith
75
What is the cross sectional area in square inches for 12 AWG RHH with outer covering conductors? › 0.0117 › 0.0353 › 0.0252 › 0.0327 Copyright 2005 Ted "Smitty" Smith
76
0.0353 Table 5, Chapter 9 Copyright 2005 Ted "Smitty" Smith
77
A 200A feeder installed in Schedule 80 rigid non-metallic conduit has three 3/0 AWG THHN, one 2 AWG THHN and one 6 AWG THHN conductors. What is the minimum sized raceway required? 2 inch 2.5 inch 3 inch 3.5 inch Copyright 2005 Ted "Smitty" Smith
78
2 inch Copyright 2005 Ted "Smitty" Smith
79
What size rigid metal nipple is required for three 4/0 AWG THHN, one 1/0 AWG THHN and one 4 AWG THHN conductors? 1.5 inch 2 inch 2.5 inch None of these Copyright 2005 Ted "Smitty" Smith
80
1.5 inch 1.239 60% fill based on note 4 to Table 1 Copyright 2005 Ted "Smitty" Smith
81
What size outlet box is required for one 12/2 NM cable that terminates on a switch, on 12/3 NM cable that terminates on a receptacle, and the box has manufactured internal cable clamps. › 4 x 1 1/4 square › 4 x 1 1/2 square › 4 x 2 1/8 square › None of these Copyright 2005 Ted "Smitty" Smith
82
4 x 2 1/8 Square Copyright 2005 Ted "Smitty" Smith
83
Machine screw type fasteners that engage not less than two and thread forming machine screws that engage not less than two threads in the enclosure may be used to mount equipment grounding bars, buses and lugs to enclosures. › True › False Copyright 2005 Ted "Smitty" Smith
84
True 250.8 Copyright 2005 Ted "Smitty" Smith
85
What is the net computed demand load for the air conditioning and heat for a 40 unit multifamily building that has an air conditioner ( 3hp, 3.91 kW 230V) and two baseboard heaters (3 kW) in each unit. › 160 kW › 240 kW › 6 kW › 5 kW Copyright 2005 Ted "Smitty" Smith
86
240 kW Heat is larger load than A/C Copyright 2005 Ted "Smitty" Smith
87
What is the demand load on the main service entrance of an apartment complex that is supplied with a 120/208V single phase service for twelve 3.25 kW ovens? 10 kW 18 kW 15 kW 20 kW Copyright 2005 Ted "Smitty" Smith
88
18 kW Copyright 2005 Ted "Smitty" Smith
89
What is the general lighting load for a dwelling unit with 2,700 square feet of living space not including open porches, garages, or unused or unfinished spaces not adaptable for future use? › 8100 VA › 12600 VA › 2700 VA › 6480 VA Copyright 2005 Ted "Smitty" Smith
90
8100 VA Copyright 2005 Ted "Smitty" Smith
91
What is the feeder or service demand for two 3 kW ranges? › 3 kW › 4.8 kW › 4.5 kW › 3.9 kW Copyright 2005 Ted "Smitty" Smith
92
4.5 kW Copyright 2005 Ted "Smitty" Smith
93
If the total demand is 30 kW for a 120/240V dwelling unit, what is the minimum sized service and feeder copper conductor size allowed? 4 AWG 3/0 AWG 2 AWG 1/0 AWG Copyright 2005 Ted "Smitty" Smith
94
2 AWG 30,000/240= 125A Table 310.15(B)(6) shows 2 AWG copper for 125A services Copyright 2005 Ted "Smitty" Smith
95
What is the demand on the main service entrance of a single family dwelling of a range with a nameplate rating of 13.9 kVA at 240 volts? › 8000 VA › 8800 VA › 9600 VA › 10000 VA Copyright 2005 Ted "Smitty" Smith
96
8800 VA Table 220.55 Note 1 Copyright 2005 Ted "Smitty" Smith
97
The disconnecting means for surge protective devices shall not be considered a disconnecting means when determining the maximum number of handles for the service disconnecting means. True False Copyright 2005 Ted "Smitty" Smith
98
True 230.71(A)(2) Copyright 2005 Ted "Smitty" Smith
99
Metal enclosures and raceways for service conductors and equipment shall be connected to the _______________ system conductor if the electrical system is grounded or to the ________________ conductor for electrical systems that are not grounded. Grounded/ ungrounded Grounded/ grounding electrode Grounding/ grounded None of the above Copyright 2005 Ted "Smitty" Smith
100
Grounded/ Grounding electrode 250.80 Copyright 2005 Ted "Smitty" Smith
Similar presentations
© 2024 SlidePlayer.com. Inc.
All rights reserved.