Intelligent Control Panel SLC
SLC Manual
2
Quick-Reference Chart
Style IDC / In NAC / Out SLC / NFN Class B B D Y Z 4 6, 7 Class A SLC Manual
3
NFPA Style 4 SLC FACP Note Branch Taps Note Maximum Distance
Branch Line Resistor from End of Line to FACP Shall Not Over 50 ohms per Branch 5000 ft ( 1500 M) for Shield Twisted Pair Cable (12 to 18 AWG) Note Branch Taps Note Maximum Distance 12, Ohms Twisted Pair only Twisted Unshielded Pair 12 to 18 AWG SLC Distance 12 AWG 3810 M AWG M 14 AWG M AWG M SLC Manual
4
Isolator Application - Style 4 Riser
Max 25 standard devices between Isolators SLC Manual
5
NFPA Style 6 SLC Loop Resistor from End of Line to FACP
Shall Not Over 50 ohms M M 5000 ft ( 1500 M) for Shield Twisted Pair Cable (12 to 18 AWG) M M Note Maximum Distance 12, ohms Twisted Pair M M Twisted Unshielded Pair 12 to 18 AWG SLC Distance 12 AWG 3810 M AWG M 14 AWG M AWG M SLC Manual
6
Isolator Application - Style 6
Max 25 standard devices between Isolators SLC Manual
7
Style 6 with Isolators M M M M M M M Note Isolators provide survivability in event of short on segment Ensure proper Isolator loading M M SLC Manual
8
Isolator Application - Style 7
SLC Manual
9
Style 7 ISO M C SLC address capacity of loop is reduced by 2 addresses for every isolator device in excess of 200. Each device must be individually isolated for this mode Ensure proper Loop Loading SLC Manual
10
Floating Shield (+) SLC Channel A no connection (-) SLC Channel A NFS-320 / 640 / 3030 / NFS2-640 / NFS2-3030 In retrofit, disconnect shield drain wires at devices and junction boxes Shield increases wiring capacitance, reducing overall distance SLC Manual
11
SLC Data Formats CLIP Flash
Each device individually polled and responds with measured pulse width Default setting in Auto Programming Flash Devices polled in blocks of 10 Each device responds with true digital signal. CLIP only devices will give invalid reply in Flash Mode FlashScan is an algorithm that greatly enhances the speed of communication between the Analog intelligent devices. If one of the devices within a single group has new information, The panel CPU stops the group poll and concentrates on single points. The net effect is a response speed greater than five times that of earlier designs. SLC Manual
12
LED Operation SLC Manual
13
SLC Loop Devices Detectors, Modules and Pull Stations – Oh MY!
A Signaling Line Circuit can contain a variety of devices, each with a specific function to perform. Intelligent Detectors to identify a variety of threat conditions – various smoke levels, heat, etc. Addressable Modules to interface the system to conventional input/output circuits and devices – notification appliances, smoke detectors, waterflow and supervisory devices, etc. Addressable Pull Stations for manual alarm activation. These devices actually contain an Addressable Module inside. Loop Isolators to prevent total loop failure from a SLC short. Detectors, Modules and Pull Stations – Oh MY! SLC Manual
14
FlashScan Intelligent Detectors
FSP-851 Intelligent Photoelectric Detector. FSP-851T Intelligent Photo/Thermal Detector. FAPT-851 Acclimate™ Intelligent Photoelectric/Thermal Detector. FSI-851 Intelligent Ionization Detector. FST-851 Intelligent Thermal Detector. FST-851R Intelligent Rate-of-Rise Thermal Detector. FST-851H Intelligent High-Temperature Thermal Detector. FSD-751PL Intelligent Duct Photo Detector - Low-Flow FSD-751RPL Intelligent Duct Photo Detector with Relay - Low-Flow FSH-751 Intelligent HARSH (Hostile Area Smoke Head) Detector. FSL-751 Intelligent Laser Detector, low profile. Base Options: B501 Intelligent Detector Base without flange. B501BP Intelligent Detector Bases, without flange – 10 pack. B710LP Intelligent Detector Base with flange. B710LPBP Intelligent Detector bases with flange – 10 pack. B501BH Intelligent Sounder Base/Assembly. B501BHT Intelligent Temporal Sounder/Base Assembly. B224BI Intelligent Isolator base. B224RB Intelligent Relay base. B710HD Intelligent Base for the HARSH Detector. Low Flow = Air Velocity 100 to 4,000 FPM. SLC Manual
15
FlashScan Monitor Modules
FMM-1 Addressable Monitor Module. Monitors normally-open contact type devices on either a Class A or Class B circuit. FDM-1 Addressable Dual Monitor Module, 2 Class B circuits for normally-open contact type devices. FZM-1 Addressable Monitor Module for compatible two-wire conventional smoke detectors. FMM-101 Addressable Mini Module. Monitors a single normally-open contact type device on a Class B connection. FMM-1 The FMM-101 can be mounted inside the enclosure of a single monitored device. SLC Manual
16
FlashScan Control Modules
FCM-1 Addressable Control Module. Configured for one NFPA Style Y (Class B) or Style Z (Class A) circuit. 24 VDC power must be supplied. 3-amps max. FRM-1 Addressable Relay Module. Provides two Form-C dry contacts that switch together (DPDT). Use for elevator recall, damper control, door holding, auxiliary control functions, etc. FTM-1 Addressable Firephone Control Module.**Compatible with NFS-3030 and NFS-640 with FlashScan Software Ver. 2.0, Ver. 3.0 respectively. FCM-1 SLC Manual
17
Addressable Multiple Input Modules
XP10-M - 10 Class B or Five Class-A Initiating Device Circuits for normally open alarm contact devices. XP6-MA - Six Class B or Three Class A Initiating Device Circuit Module for Monitoring UL Listed two-wire smoke detectors (requires filtered, resettable 24 volts.) Mounts in BB-XP backboxes – two modules, surface mount. Mount up to six modules on a CHS-6 chassis. XP6-MA XP6-MA Six addressable Class B or three addressable Class A initiating device circuits. Removable 12 AWG (3.1 mm²) to 18 AWG (0.78 mm²) plugin terminal blocks. Status indicators for each point. Unused addresses may be disabled. Rotary address switches. Class A or Class B operation. FlashScan® or CLIP operation. Mount up to six modules on a CHS-6 chassis SLC Manual
18
Addressable Multiple Output Modules
XP6-C Transponder Control Module. six Notification Appliance Circuits, Class A or B. SYNC-1 Synchronization daughter module for XP6-C using System Sensor appliances. XP6-R Transponder Relay Module. Six Form-C Dry Contact Relays. Mounts in BB-XP backboxes – two modules, surface mount. XP6-C SLC Manual
19
NBG-12LX Addressable Pull Station
Key Resettable Dual Action. Can be opened without initiating an alarm condition! Addressable Mini-Module mounted inside station. Polling LED viewable through front handle. Addressable FlashScan Module SLC Manual
20
Isolator Modules ISO-X SLC Loop Isolator Module. Isolates against short circuits on the SLC. SLC Manual
21
FlashScan Modules 9 8 1 7 2 6 3 5 4 Break-off address stop
1 2 3 4 7 6 5 ADDRESS LOOP ONES 10 11 12 13 14 15 TENS Break-off address stop for panels with FlashScan Mode. SLC Manual
29
Inductive 30VDC @ 1A AC Power 125VAC @ 0.5A
Contact Ration Resistance 2A Inductive 1A AC Power 0.5A
31
Devices - Modules Isolator Module (ISO-X)
Supervises loop wiring for short circuit conditions Allows critical component functions Required for Style 7 operation Supported by FlashScan and CLIP systems 1 2 3 4 Loading 25 Units per Isolator All detectors except for Multi/Acclimate 1 Unit Multi/Acclimate detectors 12 Units Standard Bases 0 Units Sounder/Relay Bases 2.5 Units FMM, FZM, FCM, FRM Modules 1 Unit FDM 2 Units XP5 Modules 5 Units XPP, XPIQ 1 Unit Up to 100 Isolators per Loop without loss of devices Each Isolator over 100 reduces loop capacity by 2 devices. SLC Manual
32
FDM-1 Wiring Class B Style B
8 9 1 2 3 4 7 6 5 ADDRESS LOOP ONES 10 11 12 13 14 15 TENS The circuit connected to terminals 6 & 7 are assigned the base address. The circuit connected to terminals 8 & 9 are assigned the base address plus 1. RED LED lights for either circuit 1 or circuit 2 alarm. SLC Manual
33
Wiring the B224BI Isolator Base
Twisted Pair Recommended Listed FACP Isolator bases prevent an entire communication loop from being disabled when a short circuit occurs, by isolating that part from the remainder of the circuits. OTHER INTELLIGENT DEVICES SLC Manual
34
Wiring the B710HD Base AUX POWER SUPPLY SLC SLC Manual
35
Wiring an NBG-12LX Pull Station
+ SLC - + SLC - SLC Manual
36
Wiring Surge Suppressor
Building 2 Building 1 P = Primary S= Secondary UL requirement for a PRIMARY surge suppressor at the exit & entrance points. Recommend SECONDARY at FACP SLC Manual
37
Any Questions? SLC Manual