Presentation is loading. Please wait.

Presentation is loading. Please wait.

Announcements Please read Chapter 4 HW 1 is due now

Similar presentations


Presentation on theme: "Announcements Please read Chapter 4 HW 1 is due now"— Presentation transcript:

0 ECE 476 Power System Analysis
Lecture 4: Three-Phase, Power System Operations Prof. Tom Overbye Dept. of Electrical and Computer Engineering University of Illinois at Urbana-Champaign

1 Announcements Please read Chapter 4 HW 1 is due now
It does not need to be turned in, but will be covered by an in-class quiz on Sept 10 San Diego Gas & Electric is on campus for the ECE Career Fair on 9/9) (ARC Gym) and then for interviews on 9/10

2 Three-Phase - Wye Connection
There are two ways to connect 3 systems Wye (Y) Delta ()

3 Wye Connection Line Voltages
Van Vcn Vbn Vab Vca Vbc -Vbn (α = 0 in this case) Line-to-line voltages are also balanced

4 Wye Connection, cont’d Define voltage/current across/through device to be phase voltage/current Define voltage/current across/through lines to be line voltage/current

5 Delta Connection Ica Ic Iab Ibc Ia Ib

6 Three-Phase Example Assume a -connected load is supplied from a 3 kV (L-L) source with Z = 10020W

7 Three-Phase Example, cont’d

8 Delta-Wye Transformation

9 Delta-Wye Transformation Proof

10 Delta-Wye Transformation, cont’d

11 Three Phase Transmission Line

12 Per Phase Analysis Per phase analysis allows analysis of balanced 3 systems with the same effort as for a single phase system Balanced 3 Theorem: For a balanced 3 system with All loads and sources Y connected No mutual Inductance between phases

13 Per Phase Analysis, cont’d
Then All neutrals are at the same potential All phases are COMPLETELY decoupled All system values are the same sequence as sources. The sequence order we’ve been using (phase b lags phase a and phase c lags phase a) is known as “positive” sequence; later in the course we’ll discuss negative and zero sequence systems.

14 Per Phase Analysis Procedure
To do per phase analysis Convert all  load/sources to equivalent Y’s Solve phase “a” independent of the other phases Total system power S = 3 Va Ia* If desired, phase “b” and “c” values can be determined by inspection (i.e., ±120° degree phase shifts) If necessary, go back to original circuit to determine line-line values or internal  values.

15 Per Phase Example Assume a 3, Y-connected generator with Van = 10 volts supplies a -connected load with Z = -j through a transmission line with impedance of j0.1 per phase. The load is also connected to a -connected generator with Va”b” = 10 through a second transmission line which also has an impedance of j0.1 per phase. Find 1. The load voltage Va’b’ 2. The total power supplied by each generator, SY and S

16 Per Phase Example, cont’d

17 Per Phase Example, cont’d

18 Per Phase Example, cont’d

19 Per Phase Example, cont’d

20 Power System Operations Overview
Goal is to provide an intuitive feel for power system operation Emphasis will be on the impact of the transmission system Introduce basic power flow concepts through small system examples

21 Power System Basics All power systems have three major components: Generation, Load and Transmission/Distribution. Generation: Creates electric power. Load: Consumes electric power. Transmission/Distribution: Transmits electric power from generation to load. Lines/transformers operating at voltages above 100 kV are usually called the transmission system. The transmission system is usually networked. Lines/transformers operating at voltages below 100 kV are usually called the distribution system (radial).

22 Simulation of the Eastern Interconnect

23 Small PowerWorld Simulator Case
Load with green arrows indicating amount of MW flow Note the power balance at each bus Used to control output of generator Direction of arrow is used to indicate direction of real power (MW) flow

24 Power Balance Constraints
Power flow refers to how the power is moving through the system. At all times in the simulation the total power flowing into any bus MUST be zero! This is know as Kirchhoff’s law. And it can not be repealed or modified. Power is lost in the transmission system.

25 Basic Power Control Opening or closing a circuit breaker causes the power flow to instantaneously(nearly) change. No other way to directly control power flow in a transmission line. By changing generation or load, or by switching other lines, we can indirectly change this flow.

26 Modeling Consideration – Change is Not Really Instantaneous!
The change isn’t really instantaneous because of propagation delays, which are near the speed of light; there also wave reflection issues This will be addressed more in Chapters 5 and 13 Red is the vs end, green the v2 end

27 Transmission Line Limits
Power flow in transmission line is limited by heating considerations. Losses (I2 R) can heat up the line, causing it to sag. Each line has a limit; Simulator does not allow you to continually exceed this limit. Many utilities use winter/summer limits.

28 Overloaded Transmission Line

29 Interconnected Operation
Power systems are interconnected across large distances. For example most of North America east of the Rockies is one system, with most of Texas and Quebec being major exceptions Individual utilities only own and operate a small portion of the system, which is referred to an operating area (or an area).

30 Operating Areas Transmission lines that join two areas are known as tie-lines. The net power out of an area is the sum of the flow on its tie-lines. The flow out of an area is equal to total gen - total load - total losses = tie-flow

31 Area Control Error (ACE)
The area control error is the difference between the actual flow out of an area, and the scheduled flow. There is also a frequency dependent component that we’ll address in Chapter 12 Ideally the ACE should always be zero. Because the load is constantly changing, each utility must constantly change its generation to “chase” the ACE.

32 Automatic Generation Control
Most utilities use automatic generation control (AGC) to automatically change their generation to keep their ACE close to zero. Usually the utility control center calculates ACE based upon tie-line flows; then the AGC module sends control signals out to the generators every couple seconds.

33 Three Bus Case on AGC Generation is automatically changed to match
change in load Net tie flow is close to zero

34 MISO Real-Time ACE Previously individual utilities did their own ACE calculations; now we are part of MISO, which does one for the region

35 MISO Real-Time ACE MISO's real-time ACE is available online (along with lots of other data)


Download ppt "Announcements Please read Chapter 4 HW 1 is due now"

Similar presentations


Ads by Google