KIDDE FIRE PROTECTION Vega Peer to Peer Networking
2
Applications High rise buildings Multi-building complex Multi-loop applications Conventional system upgrade to analogue addressable Vega - Peer to Peer Networking
3
Benefits Reduced installation costs Distributed intelligence Remote indication & control Distributed risk complete with autonomous operation Vega - Peer to Peer Networking
4
48
5
Vega - Peer to Peer Networking Shared zone/plant principle - Zone/plant to group programming across network System configuration from 2 to 48 panels Support for Vega options: repeaters & motherboards Up to 2km between nodes
6
Vega - Peer to Peer Networking Zone to group programming across the network Latching & non-latching alarms 512 event log entries local & network Zone isolations across network
7
Vega - Peer to Peer Networking Network information: RS 422 communications Twin twisted pair cable Up to 2km between nodes Reliable & proven communications
8
Vega - Peer to Peer Networking System configuration via Viper or via the Membrane Selectable options for unique configurations per system Selectable options for priority level transmit & receive
9
Vega - Peer to Peer Networking Configuration options: Number Attached Panels Selectable in Viper, each panel must be programmed with the correct number of network panels
10
Vega - Peer to Peer Networking Configuration options: Display & Broadcast Alarms If set to No, the panel will inhibit the transmission & receipt of all network alarms
11
Vega - Peer to Peer Networking Configuration options: Global Evacuate If set to Yes, the panel will transmit locally generated evacuate signals & receive evacuate signals from the network
12
Vega - Peer to Peer Networking Configuration options: Act on T1 / T2 If set to Yes, the panel will shall respond to any network timer acknowledge signals
13
Vega - Peer to Peer Networking Configuration options: Global Silence / Reset If set to Yes, the panel will transmit & receive all silence & reset commands
14
Vega - Peer to Peer Networking Configuration options: Global Output Control If set to Yes, the panel will respond to & transmit all network commands relating to output control
15
Configuration Options: Panel of origin S/R override Selection of this option allows a network panel to silence and reset the panel of origin Vega - Peer to Peer Networking
16
Transmit / Receive Options
17
Vega - Peer to Peer Networking Transmit / Receive Options
18
Vega - Peer to Peer Networking Connection Details
19
Vega Peer to Peer Panel of Origin FIRE Total 01 Access Level 1 1st Z001 Ground Floor East Wing Operate to list devices
20
Vega Peer to Peer Network Panel FIRE Total 01 Access Level 1 1st Z001 Ground Floor East Wing Operate to list devices Network Event
21
Vega Peer to Peer Panel of Origin FIRE Total 01 1st Z001 Ground Floor East Wing Dev 01:001.1 Outside room 101 Panel 01 Accommodation on block #1
22
Vega Peer to Peer Network Panel FIRE Total 01 1st Z001 Ground Floor East Wing Break glass outside room 101 Loop 01 Dev 001.1 Zone 001 tot 001/001
23
Vega Peer to Peer Panel of Origin EVACUATE Access level 3
24
Vega Peer to Peer Network Panel REMOTE EVACUATE Access level 1
25
Vega Peer to Peer Panel of Origin FAULT Total 01 Zone Z001 Ground Floor East Wing Optical Room G121 Switch room 02 Loop 01 Dev 008.1 Zone 001 tot 001/001 Access level 1
26
Vega Peer to Peer Network Panel FAULT Total 01 Zone Z001 Ground Floor East Wing Device 01:998.1 Room G121 Switch room 02 Panel 01 Accommodation block #1 Access level 1
27
Vega Peer to Peer Event Log - Network Event Access level 3List event log Event 007Network event FirePriority 1 Panel 01 Accommodation block #1 Zone 001Ground floor east wing Device 01:001.1 Room G121 Switch room 11:38am Monday 14 Aug 2000 to scroll, + to quit
28
Vega Peer to Peer Event Log - Local Event Access level 3List event log Event 003Network event FirePriority 1 Zone 003Second floor east wing D001.1Loop 01 Break glassCentral staircase 11:39am Monday 14 Aug 2000 to scroll, + to quit
29
Vega Peer to Peer - Example #1 SPECIFICATION 1. Panel 3 manual evacuate sounders constant, panels 2 & 4 sounders pulsed panels 1 & 5 silent. 2. Silence alarms & reset from panel 4. 3. Fault on panel 5 signalled locally & to panel 1 only. 4. Pre-alarm on panel 4 signalled locally & to panel 1 only. 5. Pre-alarm on panel 3 signalled locally & to panel 1 only. 1 2 345
30
Vega Peer to Peer - Example #2 SPECIFICATION 1. Panel of origin sounders constant network panels pulsed with 2 min timer to evacuate. 2. Output to operate in each panel to shutdown the air conditioning. 3. Network panels to have ability to silence own sounders only. 1 23