Presentation is loading. Please wait.

Presentation is loading. Please wait.

©Ted “Smitty” Smith 2008. This speed drill focuses on subjects that will be required for the journeyman and masters examination arranged by chapter of.

Similar presentations


Presentation on theme: "©Ted “Smitty” Smith 2008. This speed drill focuses on subjects that will be required for the journeyman and masters examination arranged by chapter of."— Presentation transcript:

1 ©Ted “Smitty” Smith 2008

2 This speed drill focuses on subjects that will be required for the journeyman and masters examination arranged by chapter of the NEC. The question slide will still transition in 1.5 minutes and will be followed by the correct answer which will stay on the screen for only 10 seconds. You will have to click on the heading slide of each article section to proceed with the timer. Do not worry about writing down the correct answer during the transition. At the end of the questions, a stop slide will appear and then that will be followed by the questions and answers without the timer so you can review them. You must click on the screen icon in the lower right hand or left corner of the tool bar to start the slide show in order for the timer to operate. You will have a little less time on this drill because the questions are taken from articles and bunched together so find the answer will not take as long.

3 Click to Proceed

4 Equipment not identified for outdoor use and equipment identified for indoor use only shall be protected against _______________ damage from the weather during building construction. Copyright 2005 Ted "Smitty" Smith

5 Permanent 110.12

6 Unused opening in equipment and boxes, other than those intended for the operation of equipment, those intended for mounting purposes, or those permitted as part of __________ of listed equipment, shall be closed to afford protection substantially equivalent to the wall of the equipment. Copyright 2005 Ted "Smitty" Smith

7 The design 110.12(A)

8 The temperature rating as associated with the ampacity of a conductor shall be selected and coordinated so as not to exceed the lowest temperature rating of any connected termination, conductor, or ________. Copyright 2005 Ted "Smitty" Smith

9 Device 110.14(C) Copyright 2005 Ted "Smitty" Smith

10 The enclosures listed in Table 110.20 are not intended to protect against condensation, icing, corrosion or contamination that may occur within the enclosure or enter via the conduit or unsealed openings. True or False Copyright 2005 Ted "Smitty" Smith

11 True 110.20 Copyright 2005 Ted "Smitty" Smith

12 Where equipment rated 1200 A or more contains overcurrent devices, switching devices, or control devices is installed and there is a personnel door intended for entrance to and egress from the working space less that is 30 feet from the nearest edge of the working space, the doors are required to open in the direction of egress and be equipped with a panic bar. True or False

13 False 110.26(C)(3)

14 Sprinkler protection shall be permitted for the dedicated space above electrical equipment where the piping is provided with protection to avoid damage to the electrical equipment from condensation, leaks or breaks. True or False

15 True 110.26(F)(1)(c)

16 What is the minimum required working space between the front of a 480V switchgear and the front of a 120V Fire alarm control panel mounted directly across from it?

17 4 feet Condition three applies to the switch gear and fire alarm control panel. The highest voltage rating must be used. Table 110.26(A)(1)

18 What is the minimum amount of clear work space that must be provided in a manhole where cables are located on both sides of the manhole. Copyright 2008 Ted "Smitty" Smith

19 3 feet 110.72

20 Click Here to Proceed

21 The continuity of the grounded conductor shall not depend on a connection to a metallic enclosure, raceway or ________________.

22 Cable armor 200.2(B)

23 If part of a cable assembly, the white conductor may be used as something other than a grounded if it is permanently re-identified by painting or some other means at its termination and at _________________. A. each location the conductor is visible and accessible B. at the panel board by means of a brass tag C. at all motor connections by means of a tag D. none of the above Copyright 2005 Ted "Smitty" Smith

24 A. each location it is visible and accessible 200.7(C)(1) Copyright 2005 Ted "Smitty" Smith

25 Click Here to Proceed

26 Each multiwire branch circuit shall be provided with a means that will simultaneously disconnect all ungrounded conductors at the point where the branch circuit _____________. A. terminates B. originates C. has overcurrent protection D. none of the above Copyright 2005 Ted "Smitty" Smith

27 B. originates 210.4(B) Copyright 2005 Ted "Smitty" Smith

28 The ungrounded and grounded conductors of each multiwire branch circuit shall be grouped by ________________ or other similar means in at least one location within the panelboard or other point of origin

29 Wire ties 210.4(D)

30 All 120V, single phase, 15 and 20 ampere branch circuits supplying outlets installed in dwelling unit family rooms, dining rooms, living rooms, parlors, ______________, dens, bedrooms, sunrooms, recreation rooms, closets, hallways, or similar rooms or areas shall be protected by a listed arc-fault circuit interrupter, combination type, installed to provide protection of the branch circuit.

31 Libraries 210.12(B)

32 480v may be used to supply luminaires that are powered from direct current systems and contain a listed, dc rated ballast that provides isolation between the dc power and the lamp circuit and protection from electric shock when changing lamps. True or False

33 True 210.6(D)

34 A GFCI protected receptacle is required in a commercial building if the receptacle is to be placed within _____________ of a sink.

35 6 feet 210.8(B)(5)

36 A branch circuit is operating at 16 amperes. The load is expected to operate in excess of three hours continuously.. The branch circuit is protected by a single phase inverse time circuit breaker rated at 75 degrees C and 20 amperes. The circuit is a 120v single phase circuit. The branch circuit ungrounded conductor is THHN 12 AWG and the branch circuit grounded conductor is THHN 14 AWG. The load has a temperature rating of 60 degrees C. Is this an acceptable installation?

37 Yes 310.16 Table 110.14(C) 210.19(A)(1) and Exception No. 2

38 Where a counter mounted cook top is installed in an island countertop and the width of the countertop behind the cook top is less than ___________ the cook top is considered to divide the countertop into two separate countertop spaces.

39 12 inches 210.52(C)

40 This is the end of the presentation. You can now review the slides and answers without the timer. Click the slide to advance to the next slide

41 Click to Proceed

42 Equipment not identified for outdoor use and equipment identified for indoor use only shall be protected against _______________ damage from the weather during building construction. Copyright 2005 Ted "Smitty" Smith

43 Permanent 110.12

44 Unused opening in equipment and boxes, other than those intended for the operation of equipment, those intended for mounting purposes, or those permitted as part of __________ of listed equipment, shall be closed to afford protection substantially equivalent to the wall of the equipment. Copyright 2005 Ted "Smitty" Smith

45 The design 110.12(A)

46 The temperature rating as associated with the ampacity of a conductor shall be selected and coordinated so as not to exceed the lowest temperature rating of any connected termination, conductor, or ________. Copyright 2005 Ted "Smitty" Smith

47 Device 110.14(C) Copyright 2005 Ted "Smitty" Smith

48 The enclosures listed in Table 110.20 are not intended to protect against condensation, icing, corrosion or contamination that may occur within the enclosure or enter via the conduit or unsealed openings. True or False Copyright 2005 Ted "Smitty" Smith

49 True 110.20 Copyright 2005 Ted "Smitty" Smith

50 Where equipment rated 1200 A or more contains overcurrent devices, switching devices, or control devices is installed and there is a personnel door intended for entrance to and egress from the working space less that is 30 feet from the nearest edge of the working space, the doors are required to open in the direction of egress and be equipped with a panic bar. True or False

51 False 110.26(C)(3)

52 Sprinkler protection shall be permitted for the dedicated space above electrical equipment where the piping is provided with protection to avoid damage to the electrical equipment from condensation, leaks or breaks. True or False

53 True 110.26(F)(1)(c)

54 What is the minimum required working space between the front of a 480V switchgear and the front of a 120V Fire alarm control panel mounted directly across from it?

55 4 feet Condition three applies to the switch gear and fire alarm control panel. The highest voltage rating must be used. Table 110.26(A)(1)

56 What is the minimum amount of clear work space that must be provided in a manhole where cables are located on both sides of the manhole. Copyright 2008 Ted "Smitty" Smith

57 3 feet 110.72

58 Click Here to Proceed

59 The continuity of the grounded conductor shall not depend on a connection to a metallic enclosure, raceway or ________________.

60 Cable armor 200.2(B)

61 If part of a cable assembly, the white conductor may be used as something other than a grounded if it is permanently re-identified by painting or some other means at its termination and at _________________. A. each location the conductor is visible and accessible B. at the panel board by means of a brass tag C. at all motor connections by means of a tag D. none of the above Copyright 2005 Ted "Smitty" Smith

62 A. each location it is visible and accessible 200.7(C)(1) Copyright 2005 Ted "Smitty" Smith

63 Click Here to Proceed

64 Each multiwire branch circuit shall be provided with a means that will simultaneously disconnect all ungrounded conductors at the point where the branch circuit _____________. A. terminates B. originates C. has overcurrent protection D. none of the above Copyright 2005 Ted "Smitty" Smith

65 B. originates 210.4(B) Copyright 2005 Ted "Smitty" Smith

66 The ungrounded and grounded conductors of each multiwire branch circuit shall be grouped by ________________ or other similar means in at least one location within the panelboard or other point of origin

67 Wire ties 210.4(D)

68 All 120V, single phase, 15 and 20 ampere branch circuits supplying outlets installed in dwelling unit family rooms, dining rooms, living rooms, parlors, ______________, dens, bedrooms, sunrooms, recreation rooms, closets, hallways, or similar rooms or areas shall be protected by a listed arc-fault circuit interrupter, combination type, installed to provide protection of the branch circuit.

69 Libraries 210.12(B)

70 480v may be used to supply luminaires that are powered from direct current systems and contain a listed, dc rated ballast that provides isolation between the dc power and the lamp circuit and protection from electric shock when changing lamps. True or False

71 True 210.6(D)

72 A GFCI protected receptacle is required in a commercial building if the receptacle is to be placed within _____________ of a sink.

73 6 feet 210.8(B)(5)

74 A branch circuit is operating at 16 amperes. The load is expected to operate in excess of three hours continuously.. The branch circuit is protected by a single phase inverse time circuit breaker rated at 75 degrees C and 20 amperes. The circuit is a 120v single phase circuit. The branch circuit ungrounded conductor is THHN 12 AWG and the branch circuit grounded conductor is THHN 14 AWG. The load has a temperature rating of 60 degrees C. Is this an acceptable installation?

75 Yes 310.16 Table 110.14(C) 210.19(A)(1) and Exception No. 2

76 Where a counter mounted cook top is installed in an island countertop and the width of the countertop behind the cook top is less than ___________ the cook top is considered to divide the countertop into two separate countertop spaces.

77 12 inches 210.52(C)

78 This is the end of the presentation. You can now review the slides and answers without the timer. Click the slide to advance to the next slide


Download ppt "©Ted “Smitty” Smith 2008. This speed drill focuses on subjects that will be required for the journeyman and masters examination arranged by chapter of."

Similar presentations


Ads by Google