1
Harmonics and PFC The love story By Pol Nisenblat
2
2 THE FUTURE OF POWER QUALITY DEFINITIONS PROBLEMS “DETUNED” SOLUTIONS TUNED SOLUTIONS HOW TO CHOOSE OPEN DISCUSSION
3
3 ELECTRICAL POWER SOURCE It is worldwide common practice to assume that utilities generate a near perfect sine wave voltage Typical electrical energy source is introduced by “voltage” source
4
4 DISTRIBUTION TRANSFORMER Typical Internal Impedance is only 2-7% of the fully loaded Secondary
5
5 IDEAL ENERGY SOURCE Simplified power control by periodical switching (chopping) Nonlinear load operation generates current waveform distortion
6
6 HARMONICS - DEFINITIONS Harmonics are integral multiples of some fundamental frequency that, when added together, result in a distorted waveform f(x) = sin(x) f(x) = sin(5x) 5 + f(x) = sin(x) + sin(5x) 5 =
7
7 HARMONICS - DEFINITIONS Harmonic order are MULTIPLES of the fundamental frequency. Typical Harmonics are the 3 rd, 5 th, and 7 th Where H3 = 150 Hz, H5 = 250 Hz, H7 = 300 Hz (at 50Hz world) In fact, any waveform may be constructed from a sine wave and some number of its harmonics like:
8
8 HARMONICS – MOST IMPORTANT DEFINITIONS Harmonics are originated at the load side! Harmonics are created in the current! Harmonic sources are - current sources
9
9 HARMONIC SOURCE High internal impedance The harmonic current is being PUSHED towards lowest external impedance path
10
10 HARMONIC CURRENT FLOW Typical harmonic current flow is towards distribution transformer 1 Ohm0.01 Ohm
11
11 HARMONICS – PROBLEMS? I 2 r losses + “skin” effect Voltage distortions Iron-core losses Cables/transformers overheat Upstream pollutions But, the real problems are yet to come
12
12 HARMONIC CURRENT WITH PFC Where the H5 current should go now?
13
13 PARALLEL RESONANCE Parallel resonance = Infinity impedance
14
14 PARALLEL RESONANCE High impedance at the resonance frequency The resonance frequency changes with changed number of capacitor groups (N)
15
15 PARALLEL RESONANCE
16
16 PARALLEL RESONANCE Harmonic current turns back to the loads Harmonic VOLTAGE raises dramatically Harmonic current circulates (ping pong) between capacitors and distribution transformer V
17
17 PARALLEL RESONANCE – WHAT TO DO? Xl1 reactor in series to the capacitor moving parallel resonance frequency downstream The new resonance frequency at: Xc=Xl+Xl1 Locate parallel resonance frequency below lowest dominant harmonic
18
18 PARALLEL RESONANCE FREQUENCY –”RULE OF THUMB” Where h r is the harmonic number of the parallel resonance Unfortunately, not accurate enough h r = kVA sc kVAC
19
19 HOW TO CALCULATE PARALLEL RESONANCE FREQUENCY? For those who love formulas:
20
20 HOW TO CALCULATE PARALLEL RESONANCE FREQUENCY? Unfortunately, Xl (Xtr) value which is actually the total distribution network inductance at the frequency of interest - is unknown But, we do know that the parallel resonance frequency would always be located downstream to the serial resonance frequency between Xl1- Xc
21
21 “DETUNED” SOLUTION
22
22 WHAT FREQUENCIES ARE SAFE? Even” harmonics are normally not present “Triple” harmonics are canceled on DELTA connected loads with balanced 3 rd harmonic On balanced loads and 3 phase DELTA capacitors cases, tuning in H3.5-H4.2 ranges are most popular
23
23 DETUNED SOLUTION - DEFINITIONS Tuned frequency is defined by serial resonance point Serial connected reactors are defined by % rather then Henries Reactor’s % defined as impedance at the fundamental frequency with respect to the capacitor’s impedance at the same frequency Reactor50Hz60HzHarmonic 7%189Hz227HzH3.78 6%204Hz245HzH4.08 14%134Hz160HzH2.67 5.67%210Hz252HzH4.2
24
24 7% “DETUNED” SOLUTION
25
25 TUNED SOLUTIONS - FILTERS Passive filters are “tuned” to just below the harmonic frequency Care should be taken – not to overload! Low impedance path at 5 th harmonic
26
26 TOO HIGH HARMONIC LEVELS? Disconnect ALL PFC capacitors and check again Significant difference? – Use detuned solution No difference? – Use tuned solution 2 nd and 4 th harmonics too high? - Check voltage converters Weak network? 14% detuned solutions are preferred Balanced 3 rd harmonic in current? – Use 5.67-7% solutions Unbalanced compensation? – Use 14% solutions only Voltage harmonics without current sources? Don’t use filters! Speak to utility.
27
Questions? Contact: Asaf Laifer Alaifer@elspec-ltd.com 972-4-6174127