MFW Pump Discharge Check Valve OE Follow Up Dominion North Anna Power Station Gary W. Liffick FW System Engineer FSRUG, Feb 21-24, 2011
2
Application Overview Background of OE31369 (update of OE29594) Corrective Action Current Status Outline North Anna Power Station: MFW Pump Discharge Check Valve
3
Application Overview PWR, 963 MWe, Westinghouse NSSS Operational Since: −June 1978 Unit 1 −Dec 1980 Unit 2 Application is Main Feedwater Pump Discharge –3 Pump Circuit, 2 Active, 1 Standby NozzleCheck Replaced the Tilting Disk Check –October 2007 at 1-FW-19 Feedwater Normal Conditions: –390 F, 1,180 psi, 15,000 GPM per Feedwater Pump Enertech Supplied: –type DRV-B,18”-900#, RF Flanges, Commercial Grade North Anna Power Station: MFW Pump Discharge Check Valve
4
Application Overview Enertech Supplied Type DRV-B: 18”-900# RF Flanges Commercial Grade WC6 body ASTM A351 CF8M Diffuser and Disk Inconel X-750 Spring North Anna Power Station: MFW Pump Discharge Check Valve
5
OE31369, MFW Pump Discharge check valve failed to fully close. Original OE29594. During March 2009 Outage, backflow detected through check valve. Disassembly showed 1 broken spring and 2 with visible wear of spring coils due to friction. Remaining Components indicate normal wear. Factory installed new springs, radial guide assembly, performed seat leak test. Returned to site as spare North Anna Power Station: MFW Pump Discharge Check Valve
6
Corrective Action Increased clearance of spring holder and spring cavity. Eliminate possible solid height of spring No change to spring design Improve check valve reliability without changing Vmin or disk closure force with zero flow North Anna Power Station: MFW Pump Discharge Check Valve
7
NozzleCheck Valve, Type DRV-B 18”-900# RF North Anna Power Station: MFW Pump Discharge Check Valve
8
DRV-B Cutaway North Anna Power Station: MFW Pump Discharge Check Valve
9
NozzleCheck Valve, Animation, Type DRV-B 18”-900# RF North Anna Power Station: MFW Pump Discharge Check Valve
10
Spring Holder and Spring
11
Spring holder wear Spring coil wear Spring Holder and Spring North Anna Power Station: MFW Pump Discharge Check Valve
12
Spring coil wear Spring Holder and Spring North Anna Power Station: MFW Pump Discharge Check Valve
13
Valves incorporating design changes were installed in all six check valve locations (3 per unit) during 2010 Two valves removed for modification & refurbishment Sept. 2010 Factory evaluation shows spring wear after 12 months and 18 months of service Valves with the modification are operating per design Current Status North Anna Power Station: MFW Pump Discharge Check Valve
14
Conclusion Final conclusion is pending the removal of the check valves from service to confirm spring wear has been eliminated Current PM frequency is 4.5 years Next valve scheduled for removal/PM is during Spring 2012 Status as of Jan 2011 North Anna Power Station: MFW Pump Discharge Check Valve
15
Gary W. Liffick, FW System Engineer Dominion – North Anna Power Station PH 540 894-2429 Gary.Liffick@dom.com Questions? North Anna Power Station: MFW Pump Discharge Check Valve