MC-Series Holter Regelarmaturen GmbH & Co. KG © 20.11.2008 MC100 1 HORA MC-Series - the new generation of linear actuators Microcontroller equipped intelligent all-inclusive
2
MC-Series: Mounting on HVAC valves 2 Holter Regelarmaturen GmbH & Co. KG ©30/11/2009 MC100
3
MC-Series: Cover 3 Holter Regelarmaturen GmbH & Co. KG ©20.11.2008 MC100 Haubenfixierung in 4 Positionen, alle 90° Kein Verschrauben erforderlich
4
MC-Series: Electrical connection 4 Holter Regelarmaturen GmbH & Co. KG ©20.11.2008 MC100
5
MC-Series: 3-point control signal (on/off) 5 24 VAC 24 VDC 230 VAC Holter Regelarmaturen GmbH & Co. KG ©20.11.2008 MC100
6
MC-Series: Modulated control signal 6 24 VAC 24 VDC 230 VAC 0...10 VDC 2...10 VDC 0...20 mA 4...20 mA Holter Regelarmaturen GmbH & Co. KG ©20.11.2008 MC100
7
MC-Series: Calibration 7 Init Holter Regelarmaturen GmbH & Co. KG ©20.11.2008 MC100 Self-stroking Automatic compensation of the tolerances of the valve The entire stroke of the valve is passed by the maximum speed
8
MC100: DIP-switches 8 S1 X normalX inverted SwitchONOFF S30...10V (0...20mA)2...10V (4...20mA) S2Y normalY inverted S4hysteresis 0,15Vhysteresis 0,5V S5Autopause / Autotest onAutopause / Autotest off S6safety position bottomsafety position top Holter Regelarmaturen GmbH & Co. KG ©20.11.2008 MC100
9
MC100: Characteristic curves 9 Input signal Y [ % ] Stroke [ % ] 20 Jumper 1 open 20 X and Y signal are independently invertible Possibility of the realisation of an equal-% behaviour with a linear valve cone Jumper 1 connected Holter Regelarmaturen GmbH & Co. KG ©20.11.2008 MC100
10
MC100: Adjustable actuating time slow9 s/mm medium4 s/mm fast 1,9 s/mm very slow12 s/mm 10 Holter Regelarmaturen GmbH & Co. KG ©20.11.2008 MC100
11
MC-Series: Feedback signal 11 Holter Regelarmaturen GmbH & Co. KG ©20.11.2008 MC100 TRUE output signal 0..10V, real time optional 0..20mA / 4..20mA
12
MC-Series: Line break recognition 12 Holter Regelarmaturen GmbH & Co. KG ©20.11.2008 MC100 Automatic line break recognition in modulated mode (2...10V or 4... 20mA): When Y-Signal drops below 1V or 2mA, the actuator moves to the limit position set by coding switch S6 Control LED on board
13
MC-Series: Error detection 13 Holter Regelarmaturen GmbH & Co. KG ©20.11.2008 MC100 In case the valve becomes mechanically blocked, e.g. by a particle, the actuator returns briefly and tries up to seven times again to reach the required position. If the particle is still there then, the actuator stops. A control LED blinks.
14
MC-Series: Repeat back signal by manual actuation 14 Holter Regelarmaturen GmbH & Co. KG ©20.11.2008 MC100 24 VAC 24 VDC 230 VAC
15
HORA MC-Series: Advantages 15 MC-Series actuators are... Holter Regelarmaturen GmbH & Co. KG ©20.11.2008 MC100
16
HORA MC Series: Advantages 16 MC-Series actuators are... Flexible: 1. In series suitable for 3-point signal as well as for continuous control signal. 2. Possibility to change the speed on site by the simple use of DIP-switches. 3. DC is possible as well as AC in the 24V version. Note: The use of smoothed DC is possible with the MC103, MC253 and MC503. For the MC1003, the thrust is reduce by 20%, for the MC1503 by 10% and for the MC163 by 20%. For the MC403, the actuating speed has to be reduced. The use of the MC103-SE with 24V smoothed DC is not recommended. The use of smoothed DC always has to be stated in the order. Holter Regelarmaturen GmbH & Co. KG © 20.11.2008 MC100
17
HORA MC Series: Advantages 17 MC-Series actuators are... Flexible: 4. Prepared for looping-in of an external binary signal, e.g. a frost protection sensor 5. Prepared for additional options (position switches…) Holter Regelarmaturen GmbH & Co. KG © 20.11.2008 MC100