Presentation is loading. Please wait.

Presentation is loading. Please wait.

* Critical in the sense of fast intervention SIEMENS – CERN EN/ICE annual meeting Nuremberg, December the 13 th 2012 Industrial Controls Engineering Department.

Similar presentations


Presentation on theme: "* Critical in the sense of fast intervention SIEMENS – CERN EN/ICE annual meeting Nuremberg, December the 13 th 2012 Industrial Controls Engineering Department."— Presentation transcript:

1 * Critical in the sense of fast intervention SIEMENS – CERN EN/ICE annual meeting Nuremberg, December the 13 th 2012 Industrial Controls Engineering Department

2 Outline Purpose Follow-up problems Follow-up and participate in product evolution Meeting structure Software usage and purchase statistics Technical and commercial issues Technical presentations * Critical in the sense of fast intervention Industrial Controls Engineering Department

3 Siemens software usage and statistics * Critical in the sense of fast intervention YEARUSERS Purchase ( KCHF) SOFTWARE USAGE (number of PCs running the software) STEP 7MICROWINWINCC FLEXIBLEHIGRAPHCFCS7-PDIAGSimaticNET 1998--------- 1999-404------- 2000-850------- 200122964------- 200282676------- 2003107949144-7---- 20041491414179-54---- 20051513321228-57---- 20061722930192595---- 200719019551615103---- 20082421077169964249- 200923812152062289189- 2010246992228239011116- 20112601246275251123122355 20122821171322281853153468 Industrial Controls Engineering Department

4 CERN Users * Critical in the sense of fast intervention Industrial Controls Engineering Department

5 Siemens equipment purchase * Critical in the sense of fast intervention Industrial Controls Engineering Department

6 Siemens software usage * Critical in the sense of fast intervention Industrial Controls Engineering Department

7 Commercial Additional discount for orders above 25000 EUR. Still finding a procedure to follow in order to get this extra 4% discount. Latest years this discount has not been applied. SIMBA box. Siemens has offered a 12 % discount, far from the 25 % (average) for most of the products included in the contract. * Critical in the sense of fast intervention Industrial Controls Engineering Department

8 Technical support HiGRAPH is out phased and not supported anymore. Special Keyword for support requests. For high priority cases Siemens offers 1000 credits Value Card to reach directly the highest level in the Siemens support line. New Siemens support webpage. Presentation to be scheduled Open Issues: RAMSES case closed and now reopened due to other problems detected. Problem handled by the external company who delivered the system WinCCOA vs. S7-1500 and S7-1200. Compatibility mode available in PVSS to connect to those PLCs by using absolute addresses. Symbolic addressing available in long term. TIA Portal migration errors. With latest version of TIA portal the migration seems to work better even if there still errors in the PID Siemens library. Touch Panel performance. Performance issues presented to Siemens. Siemens will analyse one of our projects to see what is the source of the problem. Industrial Controls Engineering Department

9 Operator panels performance * Critical in the sense of fast intervention Industrial Controls Engineering Department

10 HMI Many panels will be phased-out in 2014 (6 years spare parts ensured) Video support (IP cameras inside) Panels Diagnostics through the PLC (life bit) Multi Touch functionality Memory card or USB stick can load the HMI panel application Request form CERN: Diagnostic facilities to be improved. Industrial Controls Engineering Department

11 OPC UA CERN interested in the evolution of OPC UA especially embedded in PLC. OPC UA server in redundant mode possible (only 2008 Server available). Industrial Controls Engineering Department

12 PLC roadmap S7-1200 Significant increase of memory for S7-1200 up to 125 Kb in 2013. 2 Mb Memory card available. CAN interface available, 3 cards maximum 16 nodes each. Wi-Fi embedded for short distance (1m). Industrial Controls Engineering Department

13 PLC roadmap S7-1500 Security increased. New S7 protocol enhanced. Old S7 protocol still supported. Small display at the front with diagnostics ad commands. Foldable, replaceable hot swap. MPI interface removed. Profinet interface by default. Two integrated Ethernet interfaces. External Ethernet cards available. With VPN. Internal archive until 26 different measurements. Hot swappable modules with active backplane. Modules not compatible with S7 300. Industrial Controls Engineering Department

14 Industrial Controls Engineering Department

15 IPC Availability: 6 years guaranteed on the market and 5 years spare parts. Nanobox IPC227D: Intel Atom Micro: 600 MHz - 1.3 GHz Microbox IPC427D: Intel i7 1.5 GHz, Turbo boost included. CERN request: Windows embedded. Operating system updates not frequent. Windows embedded roadmap stable. Industrial Controls Engineering Department

16 WinAC WinAC RTX runs as a driver in Windows. Siemens foresees to decouple as much as possible Windows and WinAC. Currently WinAC RTX can survive to a blue screen from Windows. (OB84 is triggered). Performance of WinAC not dependant on storage media. ODK (Open development kit) available to allow interaction between PC and controller. It can run on the real-time side of windows. WinAC RTX can run in normal PC. Simulation possible. Industrial Controls Engineering Department

17 TIA Portal roadmap V12 end of January 2013 >> V12 SP1 in Q2 2013 >> V12.5 end of 2013 >> New version end 2014. Features V12: SCL as standard programming language for all controllers. Size of the blocks increased and bigger than 64K Versioning can be applied to libraries. Automatic update of project when library changes. Features V12.5 Importing Source files via API to import/export sources in xml format. Features version > V12.5: Object orientation (e.g. inheritance) Multiuser Versioning SVN integrated Full API to Open project, Compile, import (even hardware). Industrial Controls Engineering Department

18 PROFINET redundancy Industrial Controls Engineering Department

19 PROFINET redundancy Industrial Controls Engineering Department

20 PROFINET redundancy Industrial Controls Engineering Department

21 SIMIT Includes a Software PLC simulator which is ready to be in the market. SIMIT can interface a third party simulator tool (OPC or shared memory in the future). SIMIT focus on Simatic (simulator for automation). Templates are based on PCS7 but can be adapted (e.g. UNICOS). Symbols for the periphery to be used. UNICOS does not create symbols for I/O. Industrial Controls Engineering Department