Download presentation
Presentation is loading. Please wait.
Published byBritney Charles Modified over 9 years ago
1
1 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov Zone Pressure Diagnostics WEATHERIZATION ENERGY AUDITOR SINGLE FAMILY WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012
2
2 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov By attending this session, participants will be able to: Demonstrate the strengths and limitations of zone pressure diagnostics (ZPD). Assess when to use zone pressure diagnostics. Demonstrate the use of ZPD charts. Learning Objectives ZONE PRESSURE DIAGNOSTICS
3
3 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov Zone Pressure Diagnostics #1 Conduct zone pressure diagnostics and interpret results to determine: Location and effectiveness of the air barrier. Alignment of air barrier and thermal boundary. Leakage between zones. Photo courtesy of PA Weatherization Training Center Photos courtesy of PA WTC ZONE PRESSURE DIAGNOSTICS
4
4 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov Necessary Equipment Photos courtesy of the U.S. Department of Energy ZONE PRESSURE DIAGNOSTICS
5
5 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov Practical Applications Determine relative leakiness. Prioritize air sealing activities. Evaluate completed air sealing measures. ZONE PRESSURE DIAGNOSTICS
6
6 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov Pressure house to attic = 37Pa Pressure attic to exterior must be 13Pa (50Pa – 37Pa = 13Pa) Q: What does this tell us? 1850 CFM50 50Pa 37Pa ? Pa ZONE PRESSURE DIAGNOSTICS Relative Leakiness Graphic developed for the U.S. DOE WAP Standardized Curricula
7
7 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov Ratio of Pressure to Leakage Zone Pressures Relative Size of Leaks Zone-HouseZone-Out 1238 25 3713 419 455 482 491 Zone-HouseZone-Out 21 11 1/21 1/31 1/41 1/81 1/131 TO ZONE PRESSURE DIAGNOSTICS
8
8 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov Probing Cavities What if we stick a probe into the first floor ceiling cavity and read 41Pa? Let’s put a probe into the cellar. What does 25Pa mean? 50Pa37Pa 25Pa 41Pa ZONE PRESSURE DIAGNOSTICS Graphic developed for the U.S. DOE WAP Standardized Curricula
9
9 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov Changing Pressures If we open the cellar door to the house and put a probe into the attic we might find the attic 37Pa has dropped to 25Pa. 50Pa25Pa 0Pa The pressure between the house and basement will now be zero. Why? ZONE PRESSURE DIAGNOSTICS Graphic developed for the U.S. DOE WAP Standardized Curricula
10
10 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov Simple Zone Pressure Diagnostics #1 Pressure difference of attic with reference to the house should be close to -50 Pa. Blower Door ΔP = -50 Pa ZONE PRESSURE DIAGNOSTICS Graphic developed for the U.S. DOE WAP Standardized Curricula
11
11 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov Simple Zone Pressure Diagnostics #2 ΔP = 0 Pa Pressure difference of interior wall with reference to the house should be close to 0 Pa. Blower Door ZONE PRESSURE DIAGNOSTICS Graphic developed for the U.S. DOE WAP Standardized Curricula
12
12 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov Where Is the Air Barrier? #1 Cape Cod 1½ Story House ZONE PRESSURE DIAGNOSTICS Graphic developed for the U.S. DOE WAP Standardized Curricula
13
13 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov Where Is the Air Barrier? #2 Pressure difference of the floor cavity with reference to the house should be 0 Pa. But, is it? 48 ZONE PRESSURE DIAGNOSTICS Graphic developed for the U.S. DOE WAP Standardized Curricula
14
14 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov Two-story balloon-framed house with one-story addition and unheated porch over unconditioned basement Where Is the Air Barrier? #3 Unsealed/Uninsulated ZONE PRESSURE DIAGNOSTICS Graphic developed for the U.S. DOE WAP Standardized Curricula
15
15 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov Where Is the Air Barrier? #4 Air-sealed/Insulated with air barrier and insulation in alignment Sealed/Insulated ZONE PRESSURE DIAGNOSTICS Graphic developed for the U.S. DOE WAP Standardized Curricula
16
16 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov Can We Size The Holes? 50Pa25Pa 0Pa Pressure is gradually reduced by each layer of wall or ceiling between inside and outside. Collecting CFM 50 and pressure across each configuration lets us calculate hole size in each surface. ZONE PRESSURE DIAGNOSTICS Graphic developed for the U.S. DOE WAP Standardized Curricula
17
17 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov 1850 CFM50 50Pa 2200 CFM50 25Pa 50Pa 0Pa 50Pa Basement door closed Basement door open ZONE PRESSURE DIAGNOSTICS Here is what we know Graphics developed for the U.S. DOE WAP Standardized Curricula
18
18 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov Open A Door – Zone To Main Body 25Pa18502200350 2.7696697 sq” 3502.7696697 sq” 3501.76 616 CFM50 ZONE PRESSURE DIAGNOSTICS
19
19 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov What Do The Results Mean? H/Z 350 x 2.76 = 966 CFM 50 = 96.6 sq” of hole in the floor Z/O 350 x 2.76 = 966 CFM 50 = 96.6 sq” hole in basement walls T/P 350 x 1.76 = 616 CFM 50 is attributable to the path 50Pa ZONE PRESSURE DIAGNOSTICS Graphic developed for the U.S. DOE WAP Standardized Curricula
20
20 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov Open A Door – Zone To Outside ZONE PRESSURE DIAGNOSTICS
21
21 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov At 1850 CFM 50, house to attic pressure = 37Pa. Open attic hatch enough to create at least 6Pa change. Bring the blower door back to 50Pa. CFM 50 is now 2500 House to attic press ure is now 20Pa. 50Pa 20Pa ZONE PRESSURE DIAGNOSTICS No Door on the Zone? Graphic developed for the U.S. DOE WAP Standardized Curricula
22
22 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov Flow Method: Hole – Zone To House #1 ZONE PRESSURE DIAGNOSTICS
23
23 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov Flow Method: Hole – Zone To House #2 1850 37Pa 2500 20Pa 650 1.38 884 ZONE PRESSURE DIAGNOSTICS
24
24 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov Flow Method: Hole – Zone To Outside ZONE PRESSURE DIAGNOSTICS
25
25 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov Of 1850 CFM 50 : Through attic ≈ 900 Through basement ≈ 600 Walls (remainder) ≈ 350 50Pa ZONE PRESSURE DIAGNOSTICS What Did We Learn Overall? Graphic developed for the U.S. DOE WAP Standardized Curricula
26
26 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov How about a garage? Any space that will accept a probe can be checked for pressure. ZPD requires being able to change the pressure over the surface to determine hole size. 48Pa50Pa 2Pa ZONE PRESSURE DIAGNOSTICS Checking Air Sealing Graphic developed for the U.S. DOE WAP Standardized Curricula
27
27 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov Not great for excessively leaky buildings Requires being able to change the pressure over the tested surface to determine hole size Not great in windy conditions Time consuming Limitations ZONE PRESSURE DIAGNOSTICS
28
28 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov Practice!
29
29 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov Open A Door – Zone To Main Body 40Pa20502550500 ZONE PRESSURE DIAGNOSTICS
30
30 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov Open A Door – Zone To Main Body 40Pa20502550500 0.63 315 31.5 sq” 1.54 770 77 sq” 0.54 270 CFM50 ZONE PRESSURE DIAGNOSTICS
31
31 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov Flow Method: Hole – Zone To House 1200 45Pa 1850 18Pa 650 ZONE PRESSURE DIAGNOSTICS
32
32 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov Flow Method: Hole – Zone To House 1200 45Pa 1850 18Pa 650 0.43 280 ZONE PRESSURE DIAGNOSTICS
33
33 | WEATHERIZATION ASSISTANCE PROGRAM STANDARDIZED CURRICULUM – December 2012eere.energy.gov ZPD can help you determine the relative leakiness of a home, prioritize air sealing activities, and evaluate completed air sealing measures. ZPD requires a computer or charts to do the calculations. The calculations can be time consuming, so use ZPD only when needed to prioritize or verify critical air sealing activities. ZPD does not work well in extremely leaky homes or when it’s very windy. ZPD requires being able to change the pressure over the tested surface to determine hole size. Summary ZONE PRESSURE DIAGNOSTICS
Similar presentations
© 2024 SlidePlayer.com. Inc.
All rights reserved.