TECHNICAL TRAINING 2007
3
CONTROLLER PROGRAM UPGRADE
4
PCB Program Upgrade 3 types program upgrade: ID PCBID PCB A type OD PCBA type OD PCB B type OD PCBB type OD PCB
5
Turn off the ID PCB power Power on ID PCB Upgrade 1. Short the Jumper JP1, JP3 ~ JP6 on the PCB 2. Connect the ID PCB and Gateway Turn on the upgrade software in PC and select parameters Upgrade Revert the jumpers back to factory default setting after the completion of upgrade
6
Turn off the OD PCB power Power on Upgrade 1. Short the Jumper P1, P3 ~ P5 on the PCB 2. Connect the OD PCB and Gateway A Type OD PCB Upgrade Turn on the upgrade software in PC and select parameters Revert the jumpers back to factory default setting after the completion of upgrade
7
Turn off the OD PCB power Upgrade Install the MCU board & power on B Type OD PCB Upgrade Turn on the upgrade software in PC and select parameters 1. Remove MCU board & short the Jumper P1 ~ P5 on the PCB 2. Connect the OD PCB and Gateway Revert the jumpers back to factory default setting after the completion of upgrade
8
1. Smart Commander connecting A Series unit 2. Smart Commander connecting B Series unit Starting Up & Monitoring Software
9
Connection of OD and PCConnection of OD and PC Start Smart Commander, select parametersStart Smart Commander, select parameters Connect communicationConnect communication Monitor dataMonitor data Monitoring Software with A series
10
Monitoring Software with B Series Connection of OD and PCConnection of OD and PC Start Smart Commander, select parametersStart Smart Commander, select parameters Connect communicationConnect communication Monitor dataMonitor data
11
Common Problems & Solutions Possibilities of unsuccessful of upgrade: Monitoring Software is still connectingMonitoring Software is still connecting Wrong serial port is being selectedWrong serial port is being selected Wrong crystal frequency is being selectedWrong crystal frequency is being selected Wrong ID & OD jumper settingWrong ID & OD jumper setting Wrong jumper setting of GatewayWrong jumper setting of Gateway The transformer of Gateway is abnormalThe transformer of Gateway is abnormal The Gateway is abnormalThe Gateway is abnormal ID & OD PCB is abnormalID & OD PCB is abnormal
12
Common Problems & Solutions Operation of Smart Commander problems: Wrong serial port is being selectedWrong serial port is being selected Wrong baud rate is being selectedWrong baud rate is being selected Wrong ID & OD jumper settingWrong ID & OD jumper setting Wrong OD address settingWrong OD address setting Wrong jumper setting of GatewayWrong jumper setting of Gateway The transformer of Gateway is abnormalThe transformer of Gateway is abnormal Gateway is abnormalGateway is abnormal
13
Common Problems & Solutions Malfunction of ID & OD communication: Incorrect ID & OD jumper settingIncorrect ID & OD jumper setting Incorrect polarity of communication wireIncorrect polarity of communication wire JP7 is not shorted for the last IDJP7 is not shorted for the last ID No power supply for IDNo power supply for ID Incompatible of ID & OD program versionIncompatible of ID & OD program version ID or OD PCB is abnormalID or OD PCB is abnormal Communication wire is too long. Should not more than 1000mCommunication wire is too long. Should not more than 1000m
14
Precaution: Complete jumper setting before power on, if not the setting will not be changedComplete jumper setting before power on, if not the setting will not be changed Connect the communication wire before power on, don’t insert or pull out it when power onConnect the communication wire before power on, don’t insert or pull out it when power on Pull out the signal output slot when testingPull out the signal output slot when testing Ensure the pin and socket is corresponded when installing the PCBEnsure the pin and socket is corresponded when installing the PCB Incompatible of ID & OD program versionIncompatible of ID & OD program version Ensure the dip-switch setting is correctEnsure the dip-switch setting is correct Follow the regulations & instructions in IMFollow the regulations & instructions in IM
15
Thank You
16
Short JP1, JP3 ~ JP5 Graphic of ID PCB Connect to Gateway
17
ID Jumper Setting Factory Default Setting Jumpers being shorted
18
Gateway Connection 9Vdc power supply Serial port Connect to ID PCB Open jumper J11 & J13 RS-485 Connection
19
Selection of Parameters 1. MCU selection. MB89F538/L is being used. 2. The frequency of ID is 8MHz. 3. Select ID programming file. 5. Click to run full operation. 4. Select serial port.
20
Upgrade Process Upgrade process complete Upgrade in progress Start to upgrade
21
Graphic of the A Type OD PCB Connect to Gateway MCU Short P1, P3 ~ P5
22
A Type OD Jumper Setting Factory Default Setting Jumpers being shorted
23
Selection of Parameters 1. MCU selection. MB89F538/L is being used. 2. The frequency of OD is 4.9152MHz. 3. Select ID programming file. 5. Click to run full operation. 4. Select serial port.
24
Graphic of B Type OD PCB Connect to Gateway MCU Short JP1~ JP5 MCU board
25
B Type OD Jumper Setting Factory Default Setting Jumpers being shorted
26
Selection of Parameters 1. MCU selection. MB89F538/L is being used. 2. The frequency of OD is 4.9152MHz. 3. Select ID programming file. 5. Click to run full operation. 4. Select serial port.
27
Wiring Connection (A Series) A type OD PCB Electrical outlet 9Vdc power supply Gateway Serial port ID & OD communication wire * A to A ; B to B Red & Black pairs connect to A; Yellow & Green pairs connect to B Communication wires of Monitoring Software
28
Selection of Parameters 1. Select the correct serial port 2. Select baud rate (19200) 3. Select the numbers of OD 4. Select data record cycle 5. Click the button
29
Graphic Interface of Monitoring Software Discharge Temp Ambient Temp Suction Temp Total required capacity Output % of digital comp. Opening of OD EXV To check ID Inlet Temp of OD condenser Midlet Temp of OD condenser Outlet Temp of OD condenser
30
Graphic Interface of Monitoring Software Starting status of compressor OD fan speed 4WV status Defrost parameters To monitor slave unit OD setting parameter
31
Parameters can be observed for ID ID selection column Single ID required capacity Selection of operating parameters Click “Apply” to operate Monitor Data
32
Selection of OD Parameters EXV opening setting Adjust target super heat. The default value for R22 is 5 whereas 3 for R410A Critical point of defrost curve Defrost stop when reach this temp (TH9) If TH9 ≤ TscA1, target sub-cool is TscT1 If TscA1 < TH9 < TscA2, target sub-cool is TscT2 If TH9 ≥ TscA2, target sub-cool is TscT3 Heating EXV motion coefficient. Connecting pipe compensate coefficient Midlet temp setting for all ID (heating)
33
Special Command Button Manual defrost. The master unit will turn into defrost mode All EXV will open to 480 steps.
34
Selection of Parameters (Slave OD) Change slave unit parameter
35
Wiring Connection (B Series) B type OD PCB 9Vdc power supply Serial port ID & OD communication wire * A to A ; B to B Communication wires of Monitoring Software
36
Signal Output Slot Remove the Signal Output Slot when testing