ME 322: Instrumentation Lecture 37 April 22, 2015 Professor Miles Greiner Proportional control characteristics, Shift register and integral control program
2
Announcements/Reminders HW 12 Due Friday X2 (write a Proportional Control VI) HW 13 Due Monday L12PP (on/off, proportional and integral control) HW 14 Due Wednesday X3 Review for final (Next Wed. & Fri.) Open Lab Practice (Next Saturday and Sunday) Lab Practicum Finals (Schedule on WebCampus) – Guidelines http://wolfweb.unr.edu/homepage/greiner/teaching/MECH322Instrumentation/Tests/Index.htm This week: Lab 11 Unsteady Karmon Vortex Speed One-hour periods with your partner How is it going?
3
Lab 12 Setup Measure the beaker water temperature using a thermocouple/conditioner/myDAQ/VI Use myDAQ analog output (AO) to turn heater on/off to control the water temperature – Use Fraction of Time On (FTO) to control heater power
4
Proportional Control Current Temperature
5
Proportional Control VI construction (start at midpoint)midpoint
7
Set-Point, Lower-Control, and Measured Temperatures vs Time
8
Unsteadiness and Error versus DT Unsteadiness T RMS decreases as DT increases – And as T SP decreases – Want this to be zero The average steady-state error e = T SS -T SP – Is positive for DT = 0, but decreases as DT increases – Magnitude increases as DT increases – Want this to be zero
9
Proportional Control is Flawed Proportional control is able to eliminate unsteadiness. But, we found that if DT is large enough to make the temperature steady, then the steady-state temperature is below the desired set-point value What should Q (and FTO) be?
10
Energy Balance T Q IN = FTO(Q MAX ) Q OUT = hA(T-T ENV ) T ENV
11
Integrate Error If T-T SP > 0, then Decrease FTO If T-T SP < 0, then Increase FTO
12
How to implement this in LabVIEW
14
Figure 2 VI Block Diagram
15
Figure 1 VI Front Panel Plots help the user monitor the measure and set- point temperatures T and T SP, temperature error T– T SP, and control parameters
16
Figure 3 Measured, Set-Point, Lower-Control Temperatures and DTi versus Time Data was acquired for 40 minutes with a set-point temperature of 85°C. The time-dependent water temperature is shown with different values of the control parameters DT and DTi. Proportional control is off when DT = 0 Integral control is effectively off when DTi = 10 7 (10log(DTI) = 70)