1 Product Presentation 2007 SKY AIR Launch of new Non-Inverter + Duct (R22) series

2 2 3-Nov-15 Public and Medium Static Pressure Duct FDYM NEW Low Static Pressure Duct FDYB NEW Sky Non-Inverter R22 Heat Pump RY-series +

3 3 3-Nov-15 Public Overview 1.Product Line-up 1.1 Product Range 1.2 Combination Table 1.3 Nomenclature 2.Benefits & Features 3.Product Characteristics 3.1 General Specifications 3.2 Operation Range 3.3 Refrigerant Circuit Diagrams 3.4 McQuay/Daikin Name Cross-over 4.Conclusion

4 4 3-Nov-15 Public 1.1 Product Range The Non-Inverter RY R22 outdoor series will be available: in combination with low/medium static pressure duct in heat pump and with R22 refrigerant in 1 and 3 phase power supply 1. Product Line-up

5 5 3-Nov-15 Public 1.2 Combination Table The indoor/outdoor combination will be available: in a wide capacity range (2.7kW to 16.4kW) in only Pair connection 1. Product Line-up

6 6 3-Nov-15 Public 1.3 Nomenclature: Outdoor 30CV1 Model Name & Type R : Outdoor Y : Heat Pump Capacity 30 : kW x 10 Series C : C series Power Supply V1 : 220-240V, 1ph, 50Hz Y1 : 380-415V, 3ph, 50Hz RY 1. Product Line-up

7 7 3-Nov-15 Public 1.3 Nomenclature: Indoor 30C Model Name F : Indoor D : Ceiling concealed Y : Heat Pump Capacity 30 : kW x 10 Series C : C series FDYB M - Model Type B : Low static duct M : Medium static duct - Note: Indoors are 220-204V, 1ph, 50Hz 1. Product Line-up

8 8 3-Nov-15 Public Double Protection Drainage System By introducing ‘Built In’ double drain pans solution, i.e. primary drain pan and secondary drain pan, water leaking will not be a problem anymore. A drain socket is supplied to connect both drain pans to the drainage pipe. The secondary drain pan will act as a drip pan to block any water that might be dripped down, thus offering an additional protection to the ceiling. So additional drain pan will not be necessary during installation which means more cost saving and easy installation at site. Secondary Drain Pan (with insulation) Primary Drain Pan (Polystyrene with High Impact Polystyrene cover) Space Saving with Easy & Flexible Installation The height of the unit is low, between 261mm (lowest) and 378mm (highest). Therefore it is offering greatest flexibility in selecting installation location above ceiling. Moreover with its special designed ducting, the installation job becomes easy and the conditioned air can be effectively distributed to every corner of the room to ensure a better air distribution and more pleasant environment for comfort living. 2. Benefits & Features

9 9 3-Nov-15 Public Easy Maintenance The simple design concept has a friendly maintenance and servicing in mind. By just removing the secondary drain pan and drain guide, you can access to all the internal parts from the bottom of the unit. No water will flow down when removing the secondary drain pan, making the servicing work very easy. Elegance and Low Noise Level The indoor unit is installed above the ceiling with only the supply and return air grille exposed to view. This ceiling concealed type of design has made it an elegant model without sacrificing the precious floor space, the air-conditioned space will appear as elegant and prestigious as centralized air-conditioned area, but with only a fraction of the cost. Further the casing is well insulated internally to reduce noise level. Versatility Different layouts can be ‘created’ so that multiple rooms can be cooled together at the same time by using just one indoor unit. Room Layout 1Room Layout 3 Room Layout 2 2. Benefits & Features

10 10 3-Nov-15 Public Electrical Control Capability All series are equipped with a wired Electronic SLM Remote Controller. The SLM features: an ON/OFF switch, temperature setting (16°C to 30°C), operation modes (auto/cool/dry/heat/fan), fan speed selection, timer (setting range between 1 to 10 hours), air swing and ‘Sleep Mode’. It is possible to make use of the AC-5300 infrared Remote Controller (in option) to communicate with the SLM Remote Controller. 2. Benefits & Features

11 11 3-Nov-15 Public 3.1 General Specifications Outdoor Unit RY30CV1 RY40CV1RY60CV1RY71CV1 Indoor Unit FDYB30CFDYB40CFDYB60CFDYB71C Power source 220 - 240V / 1ph / 50Hz Capacity in coolingkW2.783.615.576.74 in heatingkW2.783.525.807.33 Input power in coolingkW0.8761.2221.8372.286 in heatingkW0.8411.0621.7462.260 EER 3.17 (B)2.95 (C)3.03 (B)2.95 (C) COP 3.31 (C) 3.32 (C)3.24 (C) Running current in coolingA3.85.48.410.0 in heatingA3.74.87.89.6 Air flow Highm³/h4579181.1051.307 Mediumm³/h4258001.0911.224 Lowm³/h356594968986 External static pressure Pa4.9 / 9.8 / 20 9.8 / 20 / 295 / 15 / 25 Sound pressure level dB(A)26 / 30 / 3329 / 34 / 3734 / 36 / 3836 / 39 / 40 Dimensions Heightmm261 Widthmm765 1.0651.200 Depthmm411 Weight kg17212225 Condensate drain size mm19.05 Air flow m³/h1.4251.6302.2102.480 Sound pressure level dB(A)464952 Dimensions Heightmm540 648750 Widthmm700 855 Depthmm250 328 Weight kg32 5962 Refrigerant charge kg0.880.981.702.18 Max piping length m12 15 Max height differencem5588 OUTDOOR Low Static Pressure Duct – 1 phase INDOOR GENERAL 3. Product Characteristics

12 12 3-Nov-15 Public 3.1 General Specifications Outdoor Unit RY80CV1 RY90CV1RY100CV1RY125CV1 Indoor Unit FDYB90CFDYB125C Power source 220 - 240V / 1ph / 50Hz Capacity in coolingkW8.608.799.8211.72 in heatingkW8.508.7910.2611.72 Input power in coolingkW3.1243.1163.2103.673 in heatingkW2.7003.0863.2103.383 EER 2.75 (D)2.82 (C)3.06 (B)3.19 (B) COP 3.15 (D)2.85 (D)3.20 (D)3.46 (B) Running current in coolingA15.314.816.117.7 in heatingA13.614.716.116.3 Air flow High (super)m³/h1.494 (1.598)1.800 (2.023) Mediumm³/h1.3431.700 Lowm³/h1.2561.649 External static pressurePa20 / 29 / 39 / 49 Sound pressure leveldB(A)38 / 42 / 46 / 4941 / 45 / 49 / 51 Dimensions Heightmm378 Widthmm9291.045 Depthmm541 Weight kg3942 Condensate drain sizemm19.05 Air flow m³/h2.6685.778 Sound pressure leveldB(A)5458 Dimensions Heightmm750850 Widthmm8551.030 Depthmm328400 Weight kg6895 100 Refrigerant chargekg2.402.152.60 Max piping lengthm1545 Max height differencem825 OUTDOOR Low Static Pressure Duct – 1 phase INDOOR GENERAL 3. Product Characteristics

13 13 3-Nov-15 Public 3.1 General Specifications Outdoor Unit RY90CY1 RY125CY1RY140CY1RY160CY1 Indoor Unit FDYB90CFDYB125CFDYB140CFDYB160C Power source 380 - 415V / 3ph / 50Hz Capacity in coolingkW8.7911.7214.6516.41 in heatingkW8.7911.7215.5316.41 Input power in coolingkW3.0963.6435.0705.884 in heatingkW3.0663.3534.4704.854 EER 2.84 (C)3.22 (A)2.89 (C)2.79 (D) COP 2.87 (D)3.50 (B)3.47 (B)3.38 (C) Running current in coolingA5.15.39.09.8 in heatingA5.03.96.08.6 Air flow High (super)m³/h1.494 (1.598)1.800 (2.023)2.260 (2.567)2.754 (2.887) Mediumm³/h1.3231.7002.2252.581 Lowm³/h1.2561.6492.1562.495 External static pressurePa20 / 29 / 39 / 49 20 / 39 / 59 / 7820 / 29 / 49 / 69 Sound pressure leveldB(A)38 / 42 / 46 / 4941 / 45 / 49 / 5147 / 50 / 52 / 5347 / 50 / 53 / 55 Dimensions Heightmm378 Widthmm9291.0451.2991.499 Depthmm541 Weight kg39425462 Condensate drain sizemm19.05 Air flow m³/h5.778 6.455 Sound pressure leveldB(A)58 61 Dimensions Heightmm850 Widthmm1.030 Depthmm400 460 Weight kg95100105108 Refrigerant chargekg2.152.62.755.00 Max piping lengthm45 35 Max height differencem25 15 OUTDOOR Low Static Pressure Duct – 3 phase INDOOR GENERAL 3. Product Characteristics

14 14 3-Nov-15 Public 3.1 General Specifications Outdoor Unit RY30CV1 RY40CV1RY60CV1RY71CV1 Indoor Unit FDYM30CFDYM40CFDYM60CFDYM71C Power source 220 - 240V / 1ph / 50Hz Capacity in coolingkW2.783.605.576.89 in heatingkW2.783.605.807.03 Input power in coolingkW0.9001.2671.8952.616 in heatingkW0.7901.0621.8452.536 EER 3.09 (B)2.84 (C)2.94 (C)2.63 (D) COP 3.52 (B)3.39 (C)3.14 (D)2.77 (E) Running current in coolingA4.05.78.311.7 in heatingA3.54.88.111.5 Air flow Highm³/h5118681.1381.375 Mediumm³/h4437491.0871.292 Lowm³/h3746121.0011.037 External static pressure Pa29 / 39 / 4920 / 39 / 4942 / 65 / 6918 / 31 / 41 Sound pressure level dB(A)26 / 30 / 3329 / 34 / 3734 / 36 / 3836 / 39 / 40 Dimensions Heightmm261 Widthmm7659051.0651.200 Depthmm411 Weight kg17212225 Condensate drain sizemm19.05 Air flow m³/h1.4251.6302.2102.718 Sound pressure leveldB(A)46495152 Dimensions Heightmm540 648750 Widthmm700 855 Depthmm250 328 Weight kg32 5962 Refrigerant chargekg0.630.601.351.50 Max piping lengthm12 15 Max height differencem5588 OUTDOOR Medium Static Pressure Duct – 1 phase INDOOR GENERAL 3. Product Characteristics

15 15 3-Nov-15 Public 3.1 General Specifications Outdoor Unit RY80CV1 RYC90CV1 Indoor Unit FDYM80CFDYM90CFDYM80CFDYM90C Power source 220 – 240V, 1ph, 50Hz Capacity in coolingkW7.918.608.79 in heatingkW8.218.508.79 Input power in coolingkW3.0913.1533.0903.145 in heatingkW2.6382.7293.0603.115 EER 2.56 (E)2.73 (D)2.84 (C)2.79 (D) COP 3.11 (D) 2.87 (D)2.82 (D) Running current in coolingA15.115.514.715.0 in heatingA13.413.814.614.9 Air flow High (super)m³/h 1.375 (1.444)1.410 (1.530)1.375 (1.444)1.410 (1.530) Mediumm³/h 1.3071.2921.3071.292 Lowm³/h 1.206 External static pressure Pa59 / 68 / 78 / 9888 / 127 / 167 / 20659 / 68 / 78 / 9888 / 127 / 167 / 206 Sound pressure level dB(A)34 / 38 / 41 / 4438 / 42 / 46 / 4934 / 38 / 41 / 4438 / 42 / 46 / 49 Dimensions Heightmm 285378285378 Widthmm 1.0079291.007929 Depthmm 600541600541 Weight kg38393839 Condensate drain size mm19.05 Air flow m³/h2.6685.778 Sound pressure level dB(A)5458 Dimensions Heightmm 750850 Widthmm 8551.030 Depthmm 328400 Weight kg6895 Refrigerant chargekg2.402.15 Max piping lengthm1545 Max height differencem825 OUTDOOR INDOOR GENERAL Medium Static Pressure Duct – 1 phase 3. Product Characteristics

16 16 3-Nov-15 Public 3.1 General Specifications Outdoor Unit RY100CV1 RY125CV1 Indoor Unit FDYM100CFDYM125CFDYM100CFDYM125C Power source 220 – 240V, 1ph, 50Hz Capacity in coolingkW10.269.8211.1411.72 in heatingkW10.5510.2611.2811.72 Input power in coolingkW3.3033.2653.7663.728 in heatingkW3.3033.2653.4763.238 EER 3.11 (B)3.01 (B)2.96 (C)3.14 (B) COP 3.19 (D)3.14 (D)3.25 (C)3.62 (A) Running current in coolingA 16.516.418.118.0 in heatingA 16.516.416.716.6 Air flow High (super)m³/h 2.500 (2.617)1.800 (1.868)2.500 (2.617)1.800 (1.868) Mediumm³/h 2.4121.6802.4121.680 Lowm³/h 2.2931.5302.2931.530 External static pressure Pa88 / 108 / 118 / 13793 / 127 / 176 / 20688 / 108 / 118 / 13793 / 127 / 176 / 206 Sound pressure level dB(A)45 / 48 / 51 / 5541 / 45 / 49 / 5145 / 48 / 51 / 5541 / 45 / 49 / 51 Dimensions Heightmm 305378305378 Widthmm 1.3021.0451.3021.045 Depthmm 638541638541 Weight kg41424142 Condensate drain size mm19.05 Air flow m³/h5.778 Sound pressure level dB(A)58 Dimensions Heightmm 850 Widthmm 1.030 Depthmm 400 Weight kg95100 Refrigerant charge kg2.60 Max piping length m45 Max height differencem25 OUTDOOR INDOOR GENERAL Medium Static Pressure Duct – 1 phase 3. Product Characteristics

17 17 3-Nov-15 Public 3.1 General Specifications Outdoor Unit RY90CY1 RY125CY1 Indoor Unit FDYM80CFDYM90CFDYM100CFDYM125C Power source 380 – 415V, 3ph, 50Hz Capacity in coolingkW8.79 11.1411.72 in heatingkW8.79 11.2811.72 Input power in coolingkW3.0703.1253.7363.698 in heatingkW3.0403.0953.4363.208 EER 2.86 (C)2.81 (C)2.98 (C)3.17 (B) COP 2.89 (D)2.84 (D)3.28 (C)3.65 (A) Running current in coolingA5.15.25.4 in heatingA5.05.13.04.0 Air flow High (super)m³/h 1.375 (1.444)1.410 (1.530) 2.500 (2.617)1.800 (1.868) Mediumm³/h 1.3071.292 2.4121.680 Lowm³/h 1.206 2.2931.530 External static pressure Pa59 / 68 / 78 / 9888 / 127 / 167 / 20688 / 108 / 118 / 13793 / 127 / 176 / 206 Sound pressure level dB(A)34 / 38 / 41 / 4438 / 42 / 46 / 4945 / 48 / 51 / 5541 / 45 / 49 / 51 Dimensions Heightmm 285378 305378 Widthmm 1.007929 1.3021.045 Depthmm 600541 638541 Weight kg38394142 Condensate drain size mm19.05 Air flow m³/h5.778 Sound pressure level dB(A)58 Dimensions Heightmm 850 Widthmm 1.030 Depthmm 400 Weight kg95100 Refrigerant charge kg2.152.60 Max piping length m45 Max height difference m25 OUTDOOR INDOOR GENERAL Medium Static Pressure Duct – 3 phase 3. Product Characteristics

18 18 3-Nov-15 Public 3.1 General Specifications Outdoor Unit RYL140AY1 RYL160AY1 Indoor Unit FDYML140AFDYML160A Power source 380 – 415V, 3ph, 50Hz Capacity in coolingkW14.6516.41 in heatingkW15.5316.41 Input power in coolingkW5.0476.010 in heatingkW4.4474.980 EER 2.90 (C)2.73 (D) COP 3.49 (B)3.30 (C) Running current in coolingA9.010.0 in heatingA6.08.8 Air flow High (super)m³/h 2.344 (2.700)2.600 (2.805) Mediumm³/h 2.1752.430 Lowm³/h 2.0552.192 External static pressure Pa108 / 137 / 157 / 17698 / 137 / 157 / 176 Sound pressure level dB(A)47 / 50 / 52 / 5347 / 50 / 53 / 55 Dimensions Heightmm 378 Widthmm 1.2991.499 Depthmm 541 Weight kg5462 Condensate drain size mm19.05 Air flow m³/h5.7786.455 Sound pressure level dB(A)5861 Dimensions Heightmm 850 Widthmm 1.030 Depthmm 400460 Weight kg105108 Refrigerant charge kg2.755.00 Max piping length m4535 Max height differencem2515 OUTDOOR INDOOR GENERAL Medium Static Pressure Duct – 3 phase 3. Product Characteristics

19 19 3-Nov-15 Public 3.2 Operation Range In cooling: +19°C / +46°C In heating: -9°C / +18°C Heating Cooling 3. Product Characteristics

20 20 3-Nov-15 Public FDYB/M30C RY30CV1 3.3 Refrigerant Circuit Diagrams 3. Product Characteristics

21 21 3-Nov-15 Public FDYB/M40C RY40CV1 3.3 Refrigerant Circuit Diagrams 3. Product Characteristics

22 22 3-Nov-15 Public FDYB/M60C RY60CV1 3.3 Refrigerant Circuit Diagrams 3. Product Characteristics

23 23 3-Nov-15 Public FDYB/M71C RY71CV1 3.3 Refrigerant Circuit Diagrams 3. Product Characteristics

24 24 3-Nov-15 Public FDYM80C FDYB/M90C RY80CV1 3.3 Refrigerant Circuit Diagrams 3. Product Characteristics

25 25 3-Nov-15 Public 3.3 Refrigerant Circuit Diagrams FDYM80C FDYB/M90C RY90CV/Y1 FDYM100C FDYB/M125C RY100CV1 RY125CV/Y1 FDYB/M140C RY140CY1 3. Product Characteristics

26 26 3-Nov-15 Public 3.3 Refrigerant Circuit Diagrams FDYB/M160C RY160CY1 3. Product Characteristics

27 27 3-Nov-15 Public 3.4 McQuay/Daikin Name Cross-over 3. Product Characteristics

28 28 3-Nov-15 Public An indoor unit that is elegant, space saving (lowest height is 261mm), with 4 fan speeds and a well insulated casing to reduce noise level. Moreover it has a ‘Double Protection Drainage System’ to offer an additional protection to the ceiling and easy maintenance. With the introduction of the new Non-inverter (R22) Heat Pump RY-series in combination with the Low & Medium Static Pressure Duct (FDYB/FDYM), Daikin extends its Sky Air product portfolio for R22 refrigerant and widens its choice for ceiling concealed applications in area’s using R22 units. Mainly the RY + FDYB/M series will provide: A product combination with a wide capacity range going from class 30 to 160 (2.7kW to 16.4kW) offering comfort living, greatest flexibility and easiness in installation locations, good COP/EER and static pressure. An outdoor unit with a wide operation range (to +46°C in cooling and -9°C in heating), combinable with low / medium static indoors and available in 1 and 3 phase power supply versions. 4. Conclusion