1 California Emerging Technologies Statewide Program Dynamic Air Quality Solutions December 10, 2012

2 Fan horsepower accounts for approximately 40% of the total energy costs of HVAC (heating, ventilation and air conditioning) systems. Historically, high efficiency air filtration has been achieved by using a highly restrictive filter media, which both increased the cost of filtration as well as the energy required to push the air through the restrictive media. Dynamic technology eliminates the need for highly restrictive media by using an actively-polarized technology to create binding sites for sub-micron particles, reducing the bhp required and saving energy. Cost-savings are typically realized when replacing 85-95% efficient filters.

3 -+ Grounded screens +7,000 vdc applied to center screen Polarized media fibers + +++++++++++++++ + +++++++++++++++ ______________ ______________ + _ + -+ + _ -+ _ -+ Passive fiber Loading Characteristics Polarized fiber Passive mechanisms - because there is a media, there is passive collection Polarization and electrostatic attraction - polarized fibers collect polarized and charged particles charged center screen collects polarized and charged particles Agglomeration- Natural process (Brownian Motion) greatly accelerated by the field inside the air cleaner. Polarized particles attract each other and charged particles to form clusters that are more easily captured. How Dynamic Works

4

5 TSP Calculation 20,000 CFM unit Passive Filters Dynamic V8 + Pre Filters Dynamic V8 Pre Filter 50% Loaded0.65 0.00 Final Filter MERV13 50% L1.100.41 Heating Coil0.25 Cooling Coil0.85 ISP2.852.161.51 ESP2.15 TSP operating point5.004.313.66 BHP Required21.4618.9816.90 BHP (Delta compare to PF)0.00 ‐ 2.48 ‐ 4.56 Percentage of BHP / base0.00% ‐ 11.56% ‐ 21.25% TSP Reduction with Dynamic V8

6 In addition to energy savings… Increased efficiency in sub-micron particle removal >98% at 0.5 micron, single pass Independently tested – ASHRAE 52.2 Superior dust-loading 7-10X dust loading capacity of a cartridge filter Extends maintenance intervals Reduces landfill content Can reduce volatile organic compounds (odors) in ambient air streams, often eliminating costly carbon which also adds to energy costs

7 Projected Cost Costs vary with project size but a typical range would be $0.50 -0.80 per cfm – depending on the system and equipment Typical payback between 1.5 – 4 years, depending on building use and utility rates Energy costs to operate the 24 volt polarized system are extremely low – typically systems operate on a single 15 amp non-dedicated circuit or less. Media replacement costs are less than the passive high efficiency filters the polarized media replaces

8 Dynamic V8 Applications V8 in filter section Curb mount Built up air handler Stackable modules for side-access roof top units Stacked units

9 Dynamic Applications Available as 1 or 2 inch panels V-banks in a filter section V8 in filter section Angled filters in a field retrofit Curb mount Built up air handler

10 Miscellaneous Dynamic V8 is available in California through distributors working with consulting mechanical engineers, ESCOs and end users Retrofit and new construction All jobs evaluated on individual basis Savings are measurable and easily verified because results are based on fan laws ROI and Life Cycle Cost Analysis over base design available and generated by Dynamic

11 Thank you for your time! For additional information: www.DynamicAQS.com Ray Markey Environmental Dynamics Group Princeton, NJ 800 578-7873