INAlA TECHNOLOGIEs Installation Training:

Similar presentations


Presentation on theme: "INAlA TECHNOLOGIEs Installation Training:"— Presentation transcript:

1 INAlA TECHNOLOGIEs Installation Training:
ECS (Equipment Communications System) ECS (eth/e1) Commissioning Version 1.0

2 ECS (Eth/e1) Commissioning
Commissioning: ECS (eth/e1) Procedure

3 ECS (Eth / E1) - commissioning
Setting up of the unit: Power unit on Connect using the ITMS ECT Set-up the communication ports for the devices you are connecting to it Set-up the Sever IP address Click on set after making a change to save the configuration to the unit. Call to commission site with representative. ECS (E1/Eth) Communication Cable: A “Straight RS232” cable must be used between the ECS-L and the computer. (DB9 to IDC 10Way) Once Connected open the “ITMS-C ECT” software. Input User Name and Password, select “Serial Communication) and Click on Login Port Settings SAM1.5 = Physical port 8 – Virtual Port 310, Baud rate L&G = Physical port 10 – Virtual Port 309, Baud rate 19200 SAM2 & Access Control = Physical port RS485 – Virtual Port 301, Baud rate 9600 *Note – Check following slide for detail information of above procedure SAM Training

4 ECS (Eth / E1) – physical port numbers
Port 1 – RS232 * The physical port that is connected to the SAM or Access Control must be selected as the “UDP PORT” RS485 Port Earth 48vdc GND Port 10 – RS485 Port 9 – RS485 Port 8 – RS232 Port 7 – RS232 Port 6 – RS232 Port 5 – RS232 Port 4 – RS232 Port 3 – RS232 SP6 pluggable module Equipment Communications Controller (ECS) SAM Training

5 Software for Full ECS(Eth/E1) (Equipment Communication Controller)
Communication Controller Software (ECT): ECT Version is viewed on the top left corner as indicated with the yellow circle EG: “ITMS-C Ver 2.12” Firmware Version is viewed on the button left corner as indicated with the Red circle EG: “S/W: ” Set IP addresses as received from operator as indicated in the blue circle. After IP addresses has been completed, click on set to save them to the communications controller SAM Training

6 Software for Full ECS(Eth/E1) (Equipment Communication Controller) – port Setup
The ports should be set-up as per the screen shot for a standard Vodacom BTS site. PORT - This is the physical port on the unit Port No. - This is the virtual port number allocated to a specific device Port Name – You are able to label the port with the device you have connected to it. Baud rate – Select the appropriate baud rate for the device Flow Control – select the appropriate flow control for the device Protocol – Select the appropriate protocol for the device Physical Port Type of Port RS485 Port RS485 Port 1 RS232 Port 3 Port 4 Port 5 Port 6 Port 7 Port 8 Port 9 Port 10 SAM Training

7 Equipment Communication Controller – Port & server allocations
Virtual Port Allocations 301 SAM2 or SAM3 and Access Control 302 Rectifier A 303 Rectifier B 304 Generator 305 AVR 306 BMON 307 Fuel Cell 1 308 Fuel Cell 2 309 Energy Meter / Fire System 310 SAM 1.5 REC Vodacom Server Name Vodacom UDP Server IP UDP Server Port ZABLV CEN 299 ZABLV EAS ZABLV LIM ZABLV MPU ZABLV SGC ZABLV SGS ZABLV WES NGA Existing Server Telkom Server Name Telkom UDP Server IP UDP Server Port 2999 Operator Name APN Name Vodacom Vodameter Neotel internet Neotel Server Name Neotel UDP Server IP UDP Server Port 299 SAM Training

8 Equipment Communication Controller – Coms wiring
Communication Cable Consumables ECS (Eth/E1), ECS-L 1. 10 way Ribbon Cable 2. 10 way IDC connector for 10 way ribbon cable 3. DB9 IDC, male and female for 10 way ribbon cable ECS (Eth/GPRS), ECS (Eth/E1) & ECS-L 1. DB9, male and female, solder type 2. Milar cable used with point 1 above (Same as SAM2 Coms cross over cable) 1. RJ9 – small 4 way 2. RJ11 – large 4 way 3. RJ way 4. RJ45 – 8way 5. Cable for each above 6. CAT5 cable Possible Communication Cables needed 1. SAM1.5 2. SAM2, SAM3 & Access Control 3. Energy Meter (Landis & Gyrr) Rectifier 4. Rectifier (Battery Tech, Grintek, ASM, etc) 5. Generator (Lovato, Deep Sea, Intellilite, etc) 6. Fuel Cell (Idatech, Gencore, etc) SAM Training

9 ECS (Eth/e1) Communication wiring SAM2 & Access Control
SAM Training

10 ECS (Eth/e1) Communication wiring SAM1.5
SAM Training

11 ECS (Eth/e1) Communication wiring landis & Gyrr
SAM Training

12 ECS (Eth/e1) Communication wiring battery tech SM50
SAM Training

13 ECS (Eth/e1) Communication wiring battery tech SM65
SAM Training

14 ECS (Eth/e1) Communication wiring Grintek GT500
SAM Training

15 ECS (Eth/e1) Communication wiring Deep Sea
SAM Training

16 ECS (Eth/e1) Communication wiring Lovato
SAM Training

17 Thank you