Presentation is loading. Please wait.

Presentation is loading. Please wait.

Quiz in Progress 1)Homework 1 was? Easy Hard Easy except for problem 1

Similar presentations


Presentation on theme: "Quiz in Progress 1)Homework 1 was? Easy Hard Easy except for problem 1"— Presentation transcript:

1 Quiz in Progress 1)Homework 1 was? Easy Hard Easy except for problem 1

2 Selecting Electrical Systems
MLO/MCB Aluminum wiring

3 2) Why do we need a transformer for panel D?
Lower voltage power is more efficient Lower voltage power reduces peak demand Lower voltage power is required for duplexes Lower voltage power is safer Transformer manufacturers lobbied to make transformers required under the NEC.

4 Panel D Duplexes (receptacles) Main Lugs Only (remote protection)
Phase total 60 kVA 14 kVA (neutral) 30 poles

5 Panel D Duplexes (receptacles) Main lugs only (remote protection)
3 Phase total 60 kVA, 14kVA (neutral) 30 poles 60 kVA / (208V √3 ) = 167A 200A panel (standard size) Neutral 14000/120 = 117A Text Table 12.2, NEC, Tao and Janis (2001) Table 11-2 Hot wires should be 250 MCM, Neutral #2/0 aluminum 2½ inch conduit

6 3) How do you calculate current flow through a neutral conductor in a 3 system?
I =√3 E P I =P/ (√3 E ) I =P/ E I= E P

7 4) Why is neutral load not 1/3 of hot load?
Because not all power goes through the neutral conductor Because there can be different amounts of current on each hot conductor Because the neutral is oversized for safety reasons A. and B. A., B., and C.

8 Selecting Electrical Systems
MLO/MCB Aluminum wiring

9 5) What is the current in the hot conductors upstream of the transformer (I1)?
E1 = V1 = 480V, E2 = V2 = 208V, I2 = 200A 86 A 100 A 462 A Can’t be determined 149 A

10 Transformer capacity 200∙208∙√3 = 72 kVA ~ 75 kVA 200∙208 / 480 = 86 A
100 A switch Neutral 117*120/277 = 50 A Three #2 and one #6 aluminum (could use #4) 1¼ inch conduit (probably actually 1½ inch) 100A fuse - could use 90, but likely same price

11 Selecting Electrical Systems
MLO/MCB Aluminum wiring

12 6) What is lighting panel hot conductor current?
65kVA/(480V∙√3) = 78 A 65kVA/(480V) = 135 A 65kVA/(277V∙√3) = 135 A 65kVA/(277V) = 235 A

13 7) Does the neutral conductor carry more or less current than the hot conductor?
More current in neutral Less current in neutral No current in neutral

14 Lighting Panel 100A MLO 20 pole spaces
Hot: 65kVA/(480V∙√3) = 78 A - #2 Aluminum Neutral: 22 kVA /277V = 79 A - #2 Aluminum 100 A three pole fused switch 1½ inch conduit

15 Selecting Electrical Systems
MLO/MCB Aluminum wiring

16 8) The power panel has no neutral and therefore has how many wires in the conduit at point 4
3 hot + 1 neutral from panel = 4 3 hot + 1 ground = 4 3 hot = 3 3 hot + 1 ground + 1 neutral = 5 1 hot = 1

17 Power Panel No neutral? – all three pole circuits
33 poles required – chose 42 standard size and allows for expansion 165kVA/(480 √3) = 198 A Choose 225A switch (could use 200 A) 3 300 MCM aluminum wires – 2 inch conduit

18 Wireway 198A + 86 A + 79 A = 363A 400A would allow for some expansion, some would probably go to 600A 400A three-pole switch Six 250 MCM (unlikely to find conductors big enough to just have 3) and one #3/0 aluminum Neutral current = 130A

19 Summary Panel Sizing Find panel power usage and neutral usage (we will learn how to calculate in a minute) Size panel conductors and associated conduit and switches

20 NEC summary (Handout) Minimum capacity Grounding necessary
Only approved wires (voltage/temperature/location) 200, 210, 215, 220 demand calculations Conduits, raceways required in commercial buildings (usually rigid) 310 - Number of conductors in raceway Restrictions (to residential) on use of NM and NMC conductors Connections and splices must be approved and inspectable Need overcurrent/overvoltage/and overload protection Need disconnect switches (also 11.) Not too many wires in a conduit

21 Branch Circuits (Handout)
From panel to loads Balance loads on each phase of three phase panel NEC 430

22 Design Guidelines No wire smaller than 14 AWG in residential
12 AWG for commercial (2) Continuous load per 120 V circuit limited to 1.2kW for 15 A and 1.5kW for 20 A breaker Continuous load for heavy duty circuits Demand (kW) Conductor Size (AWG) 2 10 2.5 8 3 6

23 Do not exceed branch circuit rating by:
Panelboard to first lighting outlet Use next highest conductor size if >75 ft Only allowed >100 ft if <2% voltage drop (7) Panelboard to first receptacle If >100ft, use bigger than 10 AWG conductors Can’t use branch circuit for convenience outlets and display lighting 80 % Portable appliances 70 % Inductive lighting 50 % Fixed appliances

24 Ref: Tao and Janis (2001)

25 Ref: Tao and Janis (2001)


Download ppt "Quiz in Progress 1)Homework 1 was? Easy Hard Easy except for problem 1"

Similar presentations


Ads by Google