Download presentation
1
CIP Modbus Object Read Example
Quantum 140NOC7800 using Explicit unconnected_send request via MBP_MSTR to a 140NOC78000 Dec. 17, 2012 Rev 1.0 test
2
PLC Hardware Configuration
140NOC78000 client ( ) to query 140NOC78000 server ( ) with Explicit Messaging CIP Modbus Object READ holding register. The USB connection is for Unity to PLC communications.
3
Quantum Client Unity Program
Note to add the ‘Pin negation’ on the AND_BOOL IN1 input.
4
EIP_ControlBuf CIP Request
EIP_ControlBuf(1) and EIP_ControlBuf(8) are Read Only and written by the PLC. EIP_ControlBuf(8), Length of Received Response, will toggle between 0 and E (hex) when it is operational.
5
EIP_DataBuf CIP Request
header 28 bytes message footer Length of data to send in EIP_ControlBuf[7]
6
Control and Status Variables
Set Enable to a value of 1 to start the messaging. In a successful implementation, EMActive, EMStart, and EMSuccess will flash between 0 and 1.
7
Example Program in Quantum server PLC
This data is incrementing every sec in the PLC to observe the data changing in the response. CIP Response
Similar presentations