1
ALICE-TRD gas system 1/4/2015R. Guida PH-DT-DI1
2
TRD gas system Few numbers: Total number of modules/racks: 20 (max leak rate certified at construction 0.1 l/h per rack) Total pipe length: 2.5 km ~ 400 welds Gas connections/connectors: ~1200 Safety release valves: 22 (gas system) + 2 (gas supply) Budget considerations: Gas “value” in the detector & gas system: ~ 500 kCHF Gas “value” just in the gas system high pressure: ~ 40 kCHF Gas “value” in the Xe gas supply (1 cylinder): ~ 100 kCHF 1/4/2015R. Guida PH-DT-DI2
3
TRD gas system 1/4/2015R. Guida PH-DT-DI3 X i.e.: 80 kCHF/h i.e.: 30 kCHF/h X A different perspective:
4
Failure risk evaluation 1/4/2015R. Guida PH-DT-DI4
5
Actions 1/4/2015R. Guida PH-DT-DI5 Standard maintenance (as for all LHC gas systems) Upgrades/Consolidations are needed. Example: ▫New Xe recuperation module (2012): ∙30 kCHF (i.e. 2 m 3 Xe) paid by PH-DT-Gas Service using M&O ∙Improved Xe recuperation Follow-up after last incident: ▫Investigate the possibility to remove the safety valves ∙in the input of the gas distribution racks (200-300 mbar set value, indeed chambers already break at 2 mbar) ∙in the purifier module by reducing the purge gas pressure and adding the safety on purge and regeneration gases ∙in the exhaust module discussion ongoing (timescale: ~ months including implementation)
6
Actions 1/4/2015R. Guida PH-DT-DI6 Follow-up after last incident: ▫Reduce mixture loss due to the purifier changeover ∙New moisture analyser to be validated with respect to potential ageing effects ∙Pump to be used in the purifier to be validated with respect to potential ageing effects ∙Modification in the purifier operation sequence Work ongoing (timescale: ~ months depending on results) ▫Install weighting scale for Xe Discussed with EN-MEF (waiting for timescale and cost estimate) ▫Different procedure for Xe supply ∙Connect only cylinder with Xe gas (max 1 m 3 ) To be discussed with detector experts Monitoring tools available since beginning (gas flow + all parameters available through pvss and DIP exchange)
7
Conclusions 1/4/2015R. Guida PH-DT-DI7 Follow-up of all action proposed General consideration: ▫The amount of Xe can justify investment (beyond standard M&O) to secure the Xe-capital