1 Device Capabilities Yokogawa vs. Emerson
May 19, 2006 3051: cff 3095: cff 3244: cff 3144: cff 0644: cff 0848: cff 8800: cff 8742: cff 2700: cff 5420 (DVC5000sc): cff 4601 (DVC6000f): cff 4081 (4081pH): cff 4085 (5081pH): cff Xmt-P-FF (4088pH): cff 4082 (4081C/T): cff 4084 (5081C/T): cff Xmt-C/T-FF (4087C/T): cff 0752: cff

2 Proprietary info goes here…
Current Consumptions 1 INTERNAL USE Yokogawa Emerson Pressure, d/p transmitter EJX 15 mA max. (+ 9 mA SDL*) 3051S 18 mA max. EJA 16.5 mA max. (+ 24 mA SDL*) 3095MV 21 mA max. Temperature transmitter YTA 3244MV 3144 12 mA max. YTA80 11 mA max. 644 Temp. multiplexer F2D0-TI-Ex8.FF (P+F) 26 mA max. 848T 22 mA max. Vortex flowmeter DYF 8800A YEWFLO Style E 19 mA max. Magnetic flowmeter ADMAG AXF 15 mA max. (4-wire) 8742 Coriolis flowmeter ROTAMASS 2700 Positioner YVP/YPK 17 mA max. DVC5000f-SC DVC6000f *The value shows the additional current consumption which is needed at software download (SDL). Proprietary info goes here…

3 Proprietary info goes here…
Current Consumptions 2 INTERNAL USE Yokogawa Emerson pH/ORP transmitter PH202 22 mA max. 4081pH 18 mA max. 5081pH 21 mA max. Xmt-P-FF 13 mA max. Conductivity transmitter SC202 ISC202 4081C/T 5081C/T Xmt-C/T-FF Dissolved O2 meter DO202 --- Averaging Converter for O2 AV550G 15 mA max. Fieldbus display BA488CF (BEKA) 10 mA max. 752 Paperless recorder DAQSTATION MobileCorder 16.5 mA max. Proprietary info goes here…

4 Maximum Response Delay x Slot Time
INTERNAL USE Yokogawa Emerson Pressure, d/p transmitter EJX 12 3051S 24 EJA 3095MV 16 Temperature transmitter YTA 3244MV 3144 YTA80 20 644 Temp. multiplexer F2D0-TI-Ex8.FF (P+F) 848 Vortex flowmeter DYF 8800A YEWFLO Style E Magnetic flowmeter ADMAG AXF 8742 Coriolis flowmeter ROTAMASS 2700 Positioner YVP DVC5000f-SC YPK DVC6000f pH/ORP transmitter PH202 4081pH 5081pH Xmt-P-FF Conductivity transmitter SC202/ISC202 4081C/T 5081C/T Xmt-C/T-FF Dissolved O2 meter DO202 --- Averaging converter for O2 AV550G Fieldbus display BA488CF (BEKA) 752 Paperless recorder DAQSTATION MobileCorder Proprietary info goes here…

5 Block Execution Time <1>
INTERNAL USE Yokogawa Emerson Pressure, d/p transmitter EJX AI: 30 ms max. PID: 45 ms max. SC: 30 ms max. IT: 30 ms max. IS: 30 ms max. AR: 30 ms max 3051S AI: 30 ms PID: 44 ms SC: 40 ms IT: 35 ms IS: 30 ms AR: 35 ms EJA AI: 100ms max. PID: 160ms max. 3095MV AI: 90 ms AO: 90 ms PID: 120 ms SC: 90 ms IT: 90 ms IS: 90 ms AR: 90 ms CS: 90 ms OS: 90 ms Temperature transmitter YTA AI: 50 ms max. PID: 100 ms max. DI: 30 ms max. 3244MV AI: 50 ms PID: 100 ms SC: 100 ms AR: 100 ms 3144 AI: 60 ms PID: 90 ms SC: 60 ms IS: 65 ms AR: 60 ms YTA80 PID: 70 ms max. 644 AI: 45 ms PID: 60 ms Temp. multiplexer F2D0-TI-Ex8.FF (P+F) AI: 40 ms max. MAI: 40 ms Max. 848 MAI: 75 ms IS: 45 ms Vortex flowmeter DYF AI: 29 ms max. PID: 44 ms max. DI: 25 ms max. 8800A AI: 20 ms PID: 30 ms IT: 20 ms YEWFLO Style E AI: 100 ms max. PID: 160 ms max. Proprietary info goes here…

6 Block Execution Time <2>
INTERNAL USE Yokogawa Emerson Magnetic flowmeter ADMAG AXF AI: 30 ms max. PID: 50 ms max. DI: 25 ms max. IT: 30 ms max. AR: 30 ms max. 8742 AI: 30 ms PID: 35 ms AR: 35 ms IT: 25 ms Coriolis flowmeter ROTAMASS 2700 AI: 50 ms AO: 50 ms PID: 60 ms IT: 40 ms Positioner YVP110 AO: 95 ms max. PID: 120 ms max. DI: 40 ms max. OS: 95 ms max. DVC5000f-SC AO: 60 ms PID: 120 ms IS: 25 ms YPK110 AO: 105 ms max. DVC6000f AI: 25 ms MAI: 40 ms AO: 25 ms DI: 20 ms DO: 25 ms PID: 30 ms OS: 25 ms pH/ORP transmitter PH202 AI: 100 ms max. 4081pH PID: 150 ms 5081pH PID: 75 ms Xmt-P-FF Conductivity transmitter SC202 ISC202 4081C/T AI: 75 ms PID: 150ms 5081C/T Xmt-C/T-FF Dissolved O2 meter DO202 --- Proprietary info goes here…

7 Block Execution Time <3>
INTERNAL USE Yokogawa Emerson Averaging converter for O2 AV550G AI: 29 ms max. DI: 25 ms max. MAI: 29 ms max. MAO: 35 ms max. --- Fieldbus display BA488CF (BEKA) MAO: 50 ms max. 752 PID: 25 ms IS: 20 ms SC: 20 ms AR: 20 ms IT: 20 ms Paperless recorder DAQSTATION MobileCorder AI: 30 ms max. MAI: 30 ms max. MAO: 30 ms max. Proprietary info goes here…

8 Function Block and Device Class <1>
INTERNAL USE Yokogawa Emerson Model Function block Device class Pressure, d/p transmitter EJX AIx3, PIDx1, ISx1, SCx1, ARx1, ITx1 LINK MASTER 3051S Block Instantiation EJA AIx2, PIDx1 3095MV AIx5, PIDx1, AOx1, SCx1, ITx1, ISx1, ARx1, OSx1, SELx1 BASIC Temperature transmitter YTA AIx4, DIx4, PIDx2 3244MV 3144 YTA80 644 Temp. multiplexer F2D0-TI-Ex8.FF (P+F) AIx8, MAIx1 848 Vortex flowmeter DYF AIx2, DIx2, PIDx1 8800A AIx2, PIDx1, ITx1 YEWFLO Style E AIx1, PIDx1 Magnetic flowmeter ADMAG AXF AIx1, PIDx1, DIx2, ITx2, ARx1 8742 AIx1, PIDx1, ITx1 Coriolis flowmeter ROTAMASS AIx6, PIDx1, ITx2, 2700 AIx4, PIDx1, AOx1, ITx1 Proprietary info goes here…

9 Function Block and Device Class <2>
INTERNAL USE Yokogawa Emerson Model Function block Device class Positioner YVP/YPK AOx1, DIx2, PIDx1, OSx1 LINK MASTER DVC5000f-SC AOx1, PIDx1, ISx1 BASIC DVC6000f AOx1, PIDx1, AIx1, MAIx1, DOx1, DIx4, ISx1, OSx1 pH/ORP transmitter PH202 AIx3 4081pH AIx2, PIDx1 5081pH AIx4, PIDx1 Xmt-P-FF Conductivity transmitter SC202 ISC202 4081C/T AIx3, PIDx1 5081C/T Xmt-C/T-FF Dissolved O2 meter DO202 --- Averaging converter for O2 AV550G AIx3, DIx2 MAIx1, MAOx1 Fieldbus display BA488CF (BEKA) MAOx1 752 Block Instantiation Paperless recorder DAQSTATION MobileCorder AIx8, MAIx1, MAOx1 Proprietary info goes here…

10 Channels for I/O <Yokogawa’s Devices>
INTERNAL USE 1 2 3 4 5 6 7 8 9 10 EJX Pressure Static pressure (H) Static pressure (L) Capsul temp. Amplifier temp. --- EJA Static pressure YTA Sensor1 temp. Sensor2 temp. Terminal temp. Diff. temp. Average temp. Back up temp. Temp. limit sw. 1 Temp. limit sw. 2 Temp. limit sw. 3 Temp. limit sw. 4 YTA80 Primary Value Sensor 1 Value Sensor 2 Value Internal Temp. F2D0-TI-Ex8.FF Sensor 1 for AI Sensor 2 for AI Sensor 3 for AI Sensor 4 for AI Sensor 5 for AI Sensor 6 for AI Sensor 7 for AI Sensor 8 for AI Sensor 1-8 for MAI Body Temp. for AI DYF Flowrate Temp. Limit sw. YEWFLO Style E ADMAG AXF Limit Sw. 1 Limit Sw. 2 Switch 1 Switch 2 ROTAMASS Mass Flow Volume Flow Density Concent-ration Net Flow YVP Position setpoint, readback High limit sw. Low limit sw. YPK PH202 pH ORP SC202 ISC202 Conduc-tivity 2nd Conduc-tivity Concen-tration DO202 Dissolved O2 % Saturation Cell current AV550G Average A Average B Average C Alarm Switch Error Input for MAI Output for MAO BA488CF Output channel of MAO DAQSTATION MobileCorder Input for AI Input for MAI Output for MAO Proprietary info goes here…

11 Channels for I/O <Emerson’s Devices>
INTERNAL USE 1 2 3 4 5 6 7 3051S Pressure Sensor temp. --- 3095MV Differential Pressure Static Pressure Process Temperature Body Temperature Mass Flow Rate 3244MV Sensor1 Terminal Temperature Sensor2 Differential Temperature 3144 Sensor1 Temperature Sensor2 Temperature 644 Sensor 1 Temperature 848T 1=Sensor 1, 2=Sensor 2, 3=Sensor 3, 4=Sensor 4, 5=Sensor 5, 6=Sensor 6, 7=Sensor 7, 8=Sensor 8, 9=Differential Transducer 1, 10=Differential Transducer 2, 11=Differential Transducer 3, 12=Differential Transducer 4, 13=Housing Temperature 8800A Flow Signal Strength 8742 Flowrate 2700 1=Mass Flow, 2=Temperature, 3=Density, 4=Volume Flow, 5=Drive Gain, 6=Pressure, 7=API Corr Density, 8=API Corr Volume Flow, 9=API Ave Density, 10=API Ave Temperature, 11=API CTL, 12=ED Density At Ref, 13=ED Density SG, 14=ED Std Volume Flow, 15=ED Net Mass Flow, 16=ED Net Volume Flow, 17=ED Concentration, 18=ED Density Baume, 19=Std Gas Volume Flow DVC5000f Valve control DVC6000f 1=Final Value, 2=Travel Target, 3=Final Position, 4=Travel, 5=Supply Pressure, 6=Pressure A, 7=Pressure B, 8=Pressure Dff, 9=Drive Signal, 10=Travel Deviation, 11=Temperature, 12=Cycle Count, 13=Travel Accum, 14=Reserve PD Event 1, 15=Reserve PD Event 2, 16=Reserve PD Event 3, 17=Reserve PD Event 4, 18=Reserve PD Event 5, 19=Reserve PD Event 6, 20=Reserve PD Event 7, 21=MAI Values, 22=Setpoint_D, 23=Travel_D, 24= Travel Open, 25=Travel Closed, 26=Travel Limit Lo Lo, 27=Travel Limit Lo, 28=Travel Limit Hi, 29=Travel Limit Hi Hi, 30=Proximity Lo Lo, 31=Proximity Lo, 32=Proximity Hi, 33=Proximity Hi Hi ( * ) 4081pH pH Temp. ORP 5081pH pH/ORP Reference impedance Glass impedance Xmt-P-FF 4081C/T Conductivity Absolute conductivity 5081C/T Raw conductivity Xmt-C/T-FF 752 * Although YVP has less number of channels compared with DVC, YVP also has these accessable parameters. Proprietary info goes here…