Bacton blending feasibility study Gas Quality Workshop 23 April 2007 Dr Nick Bates, National Grid Gas Transmission
2
Bacton blending feasibility study Scope ABB report National Grid view on findings Summary
3
Bacton Blending - Scope Blending only Assume sufficient compliant gas available
4
Bacton Blending - Scope Blending only Assume sufficient compliant gas available Allow minor modifications to assets
5
Bacton Blending - Scope Blending only Assume sufficient compliant gas available Allow minor modifications to assets Gas leaving the site must be compliant with GS(M)R
6
Bacton Blending - Scope Blending only Assume sufficient compliant gas available Allow minor modifications to assets Gas leaving the site must be compliant with GS(M)R Define response requirements for measurement and control (valve)
7
Bacton Blending – ABB Findings It is feasible to implement a measurement and control system for blending at Bacton
8
Bacton Blending – ABB Findings It is feasible to implement a measurement and control system for blending at Bacton The Bacton pipework provides a non-ideal blending arrangement BactonIdeal
9
Bacton Blending – ABB Findings It is feasible to implement a measurement and control system for blending at Bacton The Bacton pipework provides a non-ideal blending arrangement Control system would depend on feed-forward control GQ Feed forward GQ Feedback Set point Limit Safety Margin
10
Bacton Blending – ABB Findings It is feasible to implement a measurement and control system for blending at Bacton The Bacton pipework provides a non-ideal blending arrangement Control system would depend on feed-forward control Transient changes in gas quality are a significant issue
11
Bacton Blending – ABB Findings It is feasible to implement a measurement and control system for blending at Bacton The Bacton pipework provides a non-ideal blending arrangement Control system would depend on feed-forward control Transient changes in gas quality are a significant issue Some supplies are connected at Bacton in a way that makes blending infeasible, e.g. BBL supply
12
Bacton blending – National Grid view Whilst it is feasible to implement blending measurement and control there are implications for National Grid and the gas industry The blending depends on sufficient compliant gas to blend with non-compliant gas The control system would have an effect on flows – potentially including end of day quantities Further detailed work would be required to make a case that the blending system would not increase the risk of unsafe gas within the UK gas network Implementation of blending could introduce constraints within the remainder of the Bacton site
13
Bacton blending - Summary It is feasible to install a blending measurement and control system at Bacton but further work is required to demonstrate that there would not be a significant additional gas quality risk Any service is likely to be constrained and may only be available on an interruptible basis The constraint on operation may include the NTS downstream of the Terminal Whilst only Bacton has been studied, similar issues are anticipated at other National Grid entry points