Commissioning the System
2
Use Service form 1A Proof of performance Speeds up Tech support Reduces recalls Commissioning
3
Balancing Orifices Works with all plenums 15, 35, 50% Easy to re-balance system
4
Airflow Checks U tube or Slope Gauge – best way Delta T in cooling 25-28 deg. Electric Heat Delta T check Motor Amperage
5
Static Pressure Affects on Fan Performance
6
Electric Heat Airflow Convert KW to BTU (3413 X KW = BTU) DeRate for 208 (.8) Cfm x’s1.08 x’s Temp. Diff. = BTU Compare to unit data
7
Winterizing Cooling Only Units Winter supply shut-offs Seal the return Winterize condensate Shut off breaker