Frankfurt (Germany), 6-9 June 2011 Vladimir Ćuk*, Sjef Cobben*, Wil L. Kling*, Roelof B. Timens** TU Eindhoven – The Netherlands, ** Universiteit Twente – The Netherlands Presenter: Dr.ir. G.M.A. Vanalme TU Eindhoven The Netherlands Session: Power Quality and Electromagnetic Compatibility Paper 0580 ANALYSIS OF HARMONIC CURRENT INTERACTION IN AN INDUSTIAL PLANT
2
Frankfurt (Germany), 6-9 June 2011 Paper 0580 Introduction Current transients in the factory lighting system A Variable Speed Drive (VSD) is causing voltage notches Possible resonance?
3
Frankfurt (Germany), 6-9 June 2011 Paper 0580 Lamp current in one phase
4
Frankfurt (Germany), 6-9 June 2011 Paper 0580 Current in all three regimes
5
Frankfurt (Germany), 6-9 June 2011 Paper 0580 Voltage in all three regimes
6
Frankfurt (Germany), 6-9 June 2011 Paper 0580 THDs over 20 ms periods
7
Frankfurt (Germany), 6-9 June 2011 Paper 0580 Voltage harmonics
8
Frankfurt (Germany), 6-9 June 2011 Paper 0580 Current harmonics Broadband distortion – not a resonance problem
9
Frankfurt (Germany), 6-9 June 2011 Paper 0580 Calculated load impedance Low impedance at high orders causes high currents Cable inductance increases the impedance at the end of the plot
10
Frankfurt (Germany), 6-9 June 2011 Paper 0580 Laboratory measurements Current with a clean voltage supply Peak current 3 A
11
Frankfurt (Germany), 6-9 June 2011 Paper 0580 Current spectrum with a clean voltage 3 rd harmonic 5 th harmonic
12
Frankfurt (Germany), 6-9 June 2011 Paper 0580 Simulated low distortion condition Peak current 4 A
13
Frankfurt (Germany), 6-9 June 2011 Paper 0580 Simulated higher voltage distortion Peak current 9 A
14
Frankfurt (Germany), 6-9 June 2011 Paper 0580 Simulated highest voltage distortion Peak current up to 20 A More oscillations than in the field – limited bandwidth of the source
15
Frankfurt (Germany), 6-9 June 2011 Paper 0580 Harmonic fingerprint – 3 rd harmonic Current harmonics even with a clean voltage, but linear response to voltage harmonics!
16
Frankfurt (Germany), 6-9 June 2011 Paper 0580 Lamp impedance – lab. measurement Fitted curve C = 47.7 μF
17
Frankfurt (Germany), 6-9 June 2011 A parallel resonance is not being excited Peaks are caused buy harmonic distortion – notch shape is not important, similar behavior with other shapes These lamps create harmonics, but react linearly to voltage harmonics – parallel capacitance (compensation) Solution – electrical separation Paper 0580 Conclusions