Download presentation
Presentation is loading. Please wait.
Published byFlora Robertson Modified over 9 years ago
1
An-Najah National University Faculty of Engineering Building Engineering Department Graduation Project – 2 Integrated Design for Hotel Prepared By: Ahmad Khalid Shams Ammar Yaser Abu Hantash Murad wael odwan Yazan Ahmad AlKilani Project supervisor: Dr. Amr Toffaha
2
Outline : Site of the project Architectural Design. Environmental Design. Structural and seismic Design. Mechanical Design. Electrical Design. Safety Design.
3
Site of the project: Location and site: Area=21000m2
4
Site of the project: Location and site:
5
Architectural Design
6
The Site Plan for the project:
7
Ground Floor plan(Area =4072 m2)
8
First Floor plan(Area =2840 m2)
9
second Floor plan(Area =2840 m2)
10
Third Floor plan(Area =2840 m2)
11
forth Floor plan(Area =2840 m2)
12
North elevation
13
South elevation
14
West elevation
15
East elevation
16
Section A-A
17
Section B-B
18
Section C-C 18
19
Environmental Design
20
The good orientation of the hotel which allows sunlight to enter the hotel in the winter The good orientation of the hotel which allows sunlight to enter the hotel in the winter from most areas to maximize heat gain in winter. In the other hand we use double glass for windows and cantilever in all elevations to reduce heat gain in summer. and internal vertical shutters on West and East walls
21
Orientation of the building:
22
Annual sun path for the hotel
23
Sun path in January month:
24
Sun path in July month:
25
layers for external walls (U = 0.560 W/m 2.k.)
26
U-value for the windows 2.260 26
27
Acoustical Design (Walls): Bedroom to Bedroom: type of walls between bedrooms is hollow blocks 20 cm thickness. STC required between bedrooms = 52 db STC layers 48 8-in. Dense hollow block Plus 4 Add plaster to both sides 52 Total
28
Acoustical Design (Walls): Corridor to Bedroom: type of walls between bedrooms is hollow blocks 20 cm thickness. STC required between bedrooms = 52 db STC layers 488-in. Dense hollow block Plus 10 Add furring strips, lath and plaster to both sides 58Total
29
Hall meetings must be completely isolated on the outside as well as having sound absorbing materials inside the hall and to achieve this was to use Acoustic panels with the highest sound absorption. 29
30
Structural and Seismic Design
31
Design Codes The American Concrete Institute code ACI 318- 08. The seismic design according to UBC-97. The analysis and design were done using SAP2000 program. Structural Design
32
General note: In seismic design we divide the hotel into 5 blocks to make regular shapes and a seismic joint between them. Then we distribute columns and shear walls as shown below.
33
1. Concrete compressive strength : f’c =28 MPa for slabs, footing, and beams. f’c =35MPa for columns, and shear walls. 2.Yielding strength of steel The yield strength of steel Fy= 420MPa 3. Bearing capacity of soil the bearing capacity of soil = 350 KN/m 2 * Design data :
34
Structural system for block(3): One way ribbed slab with hidden beams Thickness of slab: The longest span(one end continues) = 530 cm. The thickness of slab (h) = Ln/18.5 = 530/18.5 =28cm The thickness of slab (h) = 31 cm
35
Beams dimension columns dimension Footings dimension Dimension (mm) Type 650*310Main beams 400*310Secondary beams TypeDimension (mm) Internal Columns800*400 Edge Columns700*400 Circular Columns500 mm diameter TypeDimension (cm) Internal isolated Footing270*270*60 Edge isolated Footing240*240*50 Wall Footing230*600*50
36
The distribution of columns and shear walls in the building:
37
3D Modeling from SAP2000 Program:
38
Check Model: Compatibility check
39
Equilibrium checks: Error%SAPManual 1.84 %6354964740 Dead load.92 %13235.913356.1 Live load
40
Seismic design using Response Spectrum – UBC 97: W = 64740KN Soil type S B I = 1 R = 4.5 C v = 0.20 C a = 0.20 T = 0.4353 sec. V = 6610 KN
41
Natural Period (T) for the building: T(sec) 0.462From SAP 0.4353Manual
42
Structural System Design : 1. Slab design:
44
2. Main Beam Design:
45
3. Columns Design (Edge Square Column) :
47
3. Columns Design (Internal Square Column) :
49
4. Footings Design:
50
4. Footings Design (Internal Isolated Footing) :
51
4. Footings Design (Edge Isolated Footing) :
52
4. Footings Design (Wall Footing) :
53
5. Shear Walls Design:
54
5. Reinforcement details around openings:
55
MechanicalDesign
56
General Mechanical design of a building involves many aspects including : 1. Water Supply System. 2. Drainage System Design. 3. Vertical Transportation (Elevators). 4. HVAC System
57
Water Supply System ** Large-size Underground water tank : Capacity = 150 cubic meter. ** two water tanks on the roof for cold water : Capacity = 30 cubic meter for each. ** two water tanks on the roof for hot water : Capacity = 20 cubic meter for each. ** two Pump each one between the underground tank and the cold water tank on the roof.
58
1-Water Supply System: At the beginning of the design we've divided the building into four zones as shown in the following figure and we designed the zone A.
59
1-Water Supply System: (The first floor to the forth floor water supply layout):
60
1-Water Supply System: Calculations : Water demand (gpm) Number of F.U Type of supply control Main feeder 72232Flush Tank Zone A 61 170 Flush Tank Zone B 62179Flush Tank Zone C 63180Flush Tank Zone D
61
1-Water Supply System: Calculations : ** Pipes diameters for zone A: Diameter for inch)) branches Diameter for M.H.F(inch) Diameter for M.V.F(inch) floor 0.51.252G.F 3/81.252first 3/41.252second
62
1-Water Supply System: Calculations : The design of the last two floors like the second floor in addition to the auxiliary pump for each floor works 24 hours which is called Joke and the powers for the pump as follows: The power of the pump for F 4 = 0.433*(1 floor * 10.5 ft.) = 4.55 psi.
63
1-Water Supply System: Hot Water supply: **We have two water tank for hot water on the roof. **each one connect with solar panels and a boiler to heating water. ** Hot water pipes diameters will be the same of the cold water pipes diameters used.
64
2- Drainage System Design Pipes diameters : ** The vertical stack pipe diameter = 4 inch. ** horizontal pipes from laundry, kitchen sink and bathtub up to the floor drain diameter = 2 inch @ ¼ inch per foot slope. ** Horizontal pipe from floor drain to the vertical stack diameter = 4 inch @ 1/8 inch per foot slope.
65
2- Drainage System Design (Pipes diameters) : ** horizontal pipe from lavatory to the vertical stack diameter = 4 inch @ 1/8 inch per foot slope. ** The main drain pipes (underground pipes) diameter = 6 inch @ 1% slope.
66
3- Vertical transportation (Elevators): ** The required elevators for the hotel after making the calculations are: Two motor driven elevators: Capacity = 2500 lb., and speed = 350 fpm. One special elevator for hotel services. To increase well-being in the hotel and to facilitate the movement of customers we used four elevators and two for service.
67
4- HVAC System: A heating, ventilating and air conditioning (HVAC) system is designed to satisfy the environmental requirements of comfort in summer and winter. In this section we designed the first floor which shown in the figure.
68
4- HVAC System: U values and : U(W/m2.k)Material 0.560 External wall 0.50ceiling 2.260Glass(Double glazed low emittance) 3.60Wood door
69
4- HVAC System: Heating Load : The heat loss of a building consists of : Heat loss through all exposed walls ceiling,floor, windows and doors. Heat loss from ventilation and infiltration. Domestic hot water load.
70
4- HVAC System: Heating Load Calculations : heat loss by conduction = 22098 W Heat loss by infiltration and ventilation= 32465 W Domestic hot water load = 8128 W Heat load for boiler =( 22098 W+ 32465 W+ 8128 W)1.1=68960 W
71
4- HVAC System: Heating Load Calculations : No. of section and radiators: Each room need one radiator. Corridors A,C need two radiators. Corridors B,D need one radiator. Corridors E need four radiators. Each W.C need one radiator. Each space from previous spaces need number of sections different from other spaces.
72
4- HVAC System: Cooling Load : The heat gain of a building consists of : Heat gain from all exposed walls, ceiling,floor, windows and doors. Heat gain from people. Heat gain from lighting.
73
4- HVAC System: Cooling Load Calculations : Total heat gain =69383 W Number of exact : Each room from (1-12) need two exacts. Each room from (13-18) need three exacts. Each room from (19-26) need two exacts. Corridors A,C need five exacts. Corridors B,D need two exacts. Corridors E need six exacts.
74
ElectricalDesign
75
Electrical Design The lighting design depends on two types of lighting : Day light. Artificial lighting. Artificial lighting design depend on several factors such as: Room dimension. The function of the room. Selection of the luminaries. Maintenance factor for lamps. Reflection factors for ceiling, walls, and floors.
76
Electrical Design Restaurant: E recommended for restaurant = 200 lux E avg from dialux = 300 lux
77
Electrical Design Bedroom: E recommended for bedroom = 200 lux E avg from dialux = 252 lux
78
Electrical Design Distribution of lighting and switches for bedrooms: 78
79
Electrical Design Distribution of lighting and sockets for bedrooms:
80
SafetyDesign
81
Safety Design Safety design in the hotel includes many points such as: 1- stairs and distribute it in the hotel, in our project we have distributed four stairs tow of them at the middle and tow stairs at the edges of the hotel 2- safety signs and distribute it in the hotel. these two points to help people to evacuate the hotel in any case of emergency quickly and easily.
82
Safety Signs used and distributed in the hotel:
83
Right ExitLeft ExitExit Output stairsDo not use elevators
84
Safety Signs used and distributed in the hotel: Fire Exit First aid Emergency Lights Manual fire alarm Smoke detectorsExtinguishers
85
Safety Design 3- The third point in the design of safety is put out the fire in case the incident occurred and for this case we have used automatic sprinkler. ***The hotels are classified as Medium hazard, so the max distance from sprinkler to another Should not be more than 4.6 m, and the area that covers by each sprinkler Should not be more than 12.1 m 2.
86
Safety Design calculation for sprinklers: Area for each room in F1,F2,F3,F4=46.75 m 2 Area for each sprinkler = 12.1 m NO. of sprinkler for each room=46.75/12.1=3.8 Use 4 sprinkler for each room Each room need for 4 sprinkler and 2 smoke detectors
Similar presentations
© 2024 SlidePlayer.com. Inc.
All rights reserved.