Presentation is loading. Please wait.

Presentation is loading. Please wait.

VE Training in 2006 Tainan Plant Dunrong Lee Taoyuan Plant Zhiming Xu 2006/12/18.

Similar presentations


Presentation on theme: "VE Training in 2006 Tainan Plant Dunrong Lee Taoyuan Plant Zhiming Xu 2006/12/18."— Presentation transcript:

1 VE Training in 2006 Tainan Plant Dunrong Lee Taoyuan Plant Zhiming Xu 2006/12/18

2 1. VE Presentation 2. Q & A 3. Demo 4. Actual Operation

3 Outline 1.Product Specifications and Features 2.Differences between VE and V 3.New Accessories of VE series 4.Functions 5.Applications

4 Model Number VFDxxxVxxA-2 Models 3-phase 460V 340~510Vac 3-phase 230V 180~265Vac Voltage Tolerance 0.751.52.23.77.55.5151118.52230 Applicable Motor Output (kW) 45375575 Built-in Brake Chopper Built-in DC Reactor B Frame C FrameD FrameE1 Frame C FrameD FrameE FrameE1 Frame *2. Fan cooling for all series (except 1HP) *3. No built- in EMI for all series *4. Built-in digital keypad(KPV-LE01) *1. VFD110V43B-2 is C Frame under development VFD550V/750C 43C-2 is E1 Frame under development

5 3-phase 230V 180~265Vac Two Rated CT/VT 007015022037055075110150185220300370450550750 Codes 57.51117253349657590120146 CT Rated Current CT: It is applied to constant-torque load. Take conveyer belt for example. Its necessary torque does not change with the motor speed. And constant torque usually needs larger starting torque. As the motor generates heat easily when constant torque is applied to lower speed, it is better to increase the horsepower or use the motor special for AC motor drive with constant cooling fan. VT: It is applied to variable-torque load. Such as pump, fan…etc. They are centrifugal machines, who use AC motor drive usually for energy saving. For example, when a fan is running at 50% of the full speed, its necessary torque is smaller than when it is running at full speed. As for the drive with variable torque, it can provide the motor only with necessary torque to save energies. In the applications like this, the maximum transient loads needn’t to be provided extra power. So the drive with variable torque is applied widely for its load endurance. What’s more, the overload current endurance of the drive with constant torque is 150% of rated current for 1 minute, while the drive with variable torque only 120% of rated current for 1 minute because the current of centrifugal machines rarely exceed the rated current. In addition, its starting torque is smaller than that of constant torque. CT Overload Endurance: 150% of rated current for 1 minute, VT Overload Endurance: 120% of rated current for 1 minute * Designed for standard motor application 12357.510152025304050 Applicable Motor Output (HP) 6.259.413213141618193112150182 VT Rated Current 1.52.547.51015202530405060 Applicable Motor Output (HP) 3-phas 460V 340~510Vac 34.268.5131824323845607391110150 CT Rated Current 12357.5101520253040506075100 Applicable Motor Output (HP) 3.85.37.5101622304047567591113138188 VT Rated Current 1.52.547.5101520253040506075100125 Applicable Motor Output (HP)

6 Motor Protection Maximum Output Torqu e Limit Startin g Torque VE Standard feature Tuning Techniqu e SPWM tuning technique Control Mode V/f control /PG FOC vector control /PG SVC(sensor less) Torque control /PG Position control PID Speed Control Range V/f control 1:10 FOC vector control 1:100 FOC+PG1:1000 0.5Hz 150% 0Hz 150% for FOCPG mode Speed control accuracy FOC±0.2% FOC+PG ±0.02% Speed Response Ability FOC+PG 40Hz Max 250% of rated current Torque Accuracy ±5% 0~ 600 Hz VEH up to 3600Hz Accel/ Decel Time 0.00~ 600.00 sec 0.0~ 6000.0 sec Accel/ Decel Curve 4 steps S curve for set Acc./Dec. start and stop time independently Accel/ Decel Steps 1. 4 group Acc./Dec. time 2. Jog Acc./Dec. time 3. Auto Acc./Dec. setting Voltage/ Frequency Random V/f curve setting by using 4 independent points 1.5/2.0 power curve 1. 2 sets of electronic thermal Protection 2. PTC temperature sensor 3. 2 sets over torque protection 4. Current limit 5. Stall prevention during acceleration 6. Stall prevention during operation Overload Endurance 150% 60sec 200% 2sec AC Motor Drive Protection 1. Over-current: 300% of rated current 2. Overload: 150% 60sec 200% 2sec 3. Over-voltage: 290/580Vac 4. Low-voltage: 135/269Vac 5. Current leakage: 50% of rated current 6. Electric shock MOV 7. Over-temperature: 90 o C 8. Compensation for the momentary power loss 9. Phase loss protection

7 Parameter s Tuning 1. Motor dynamic/static test 2. Inertia estimation 3. High- speed field weakening curve estimation Position Control 0 speed control PI gain setting 16 point to point control P to P Home return positioning 16 point position instruction Pulse that following speed and location Division frequency output VE Advanced feature Specialized Application Double rated motor Y- △ switch Light-load auto energy-saving DEB deceleration Mechanical braking control 10 convenient communication block transmit Serial I/O pulse position control Torque and speed mode switch Environmental NEMA 1/IP21 Operation temperature: -10 o C~40 o C Storage temperature: -20 o C~60 o C Ambient humidity: below 90%RH Vibration: 20Hz below 1G 20~60Hz 0.6G Fan cooling Altitude limit: 1000m Control Interface Dual communication port RS485 KPV-CE01Communication Keypad PG Encoder Feedback card BUS Gateway Monitor card and Software Digital I/O, analog I/O

8 VFD-VE series VFD-V series Differences between VE and V (hardware-control board) 7045 PG03 card 7149 Monitor card PG card terminals DFM output selectio n J5 SW1: Sink/ Source mode AFM output selection J8 ACI input selection J4 Same power board I/O pin to pin

9 EDCMREVMI2MI4MI6 +24VFWDMI1MI3MI5 Multi-function digital input terminal SW1:Sink/Source MI1:02-01(3-wire designated terminal) MI2:02-02 MI3:02-03 MI4:02-04 MI5:02-05 MI6:02-06(TRG-designated terminal) MO1MO2 MCM Multi-function digital output MO1:02-13 MO2:02-14 (Open collector output type) ACIAUI ACM+10VAVI Multi-function analog input terminals 03-00~03-17 AVI:0~+10V 10bits ACI:4~20mA or 0~+10V selected from J4 AUI:-10~+10V Caution: J4 cannot be set while the power is applied. AFM AFM: multi-function analog output terminal 03-18,19,20 It is selected from J8 that output is 0~10V or 0~20mA. DFM DFM: Digital frequency output terminal 02-18 It is selected from J5 that Output type is voltage or open collector. MRC MRA RB RARC Multi-function Relay output Relay 1:02-11(RA,RB,RC) Relay 2:02-12(MRA,MRC) I/O Control Terminal 1. All digital terminals use photocoupler. 2. All analog circuits are no isolated.

10 Differences between V and VE (Keypad) V type VFD-PU05 VE type KPV-CE01 It can memorize 2 groups of parameters. It can memorize 4 groups of parameters.

11 Speed Feedback Card of VE (PG) 1. 5V/12V encoder power supply 2. PG1: encoder feedback 3. PG2: pulse command input 4. No pulse output terminal 5. Acceptable encoder signal types: Open Collector, Line drive, Voltage and Complementary type 6. Bandwidth: 300kP/sec 1 EMV-PG01X 1. 5V/12V encoder power supply 2. PG1: encoder feedback 3. PG2: pulse command input 4. Division Pulse output: Open Collector type 5. Acceptable encoder signal types: Open Collector, Line drive, Voltage and Complementary type 6. Bandwidth: 300kP/sec 2 EMV-PG01O 1. 5V encoder power supply 2. PG1: encoder feedback 3. PG2: pulse command input 4. Division Pulse output: Line drive type 5. Acceptable encoder signal types: Open Collector, Line drive, Output Voltage and complementary type 6. Bandwidth: 300kP/sec 3 EMV-PG01L

12 FSW3 Encoder Power supply VP terminal 5V/12V switch FSW1 PG1 encoder signal mode switch FSW2 PG2 pulse signal mode switch A1A2A1B1 Z1 DCMVPA2B2 PG1 motor encoder feedback input terminal Power supply terminal PG2 pulse command input terminal PG Card-EMV-PG01X/O/L PG1 output terminals of pulse frequency division A/O B/O Z/O E VP DCM A/O B/O Z/O 01L 01O01X Line Drive Output Type Open Collector output Type EMV-PG01O EMV-PG01X

13 1. Can be applied to winding & tension systems 2. VE’s Acc./Dec. characteristics can be use in more type of CNC machine 3. PDFF function and load inertia tuning 4. Stable run at zero speed and home search function 5. Improvement of noise endurance and signal treatment with new PG card 6. Monitor card and software which makes parameter setting and problems solving more convenient. 7. Y- △ switch control for wide-range motor in CNC machine field 8. Easy parameter setting and control for the elevator 9. Light load auto energy saving function to avoid motor burn-out duo to long time running especially in CNC machine application 10. Motor temperature feedback (PTC) function for motor over heat protection Differences between VE and V (software)

14 RS-485 Communication Port VE Communication Connection Diagram RS485 Keypad Communication Port

15 V/f FOC Control Parameters Position Control Torque Control Speed Control Torque Torque Control at Low Speed Torque Control at Zero Speed Frequency : the function of running speed Voltage: constant V/Hz to maintain constant flux. Frequency, voltage and vector ( phase relations among magnetic field, rotor and stator) use precise current loop adjustor to control current. No control. Speed error is relevant to the motor slip curve. The torque is proportional to the slip. To calculates the optimum slip so that can generate maximum torque and apply it into the whole speed range. Open-loop control. The running speed is not linear in the speed range. It provides linear speed control from 0 to basic speed. Slip induces rotor current to generate torque. Because current and toque can not be instantly controlled, so dynamic response is not good. Magnetic rotor’s flux vector value would be precisely controlled, so that torque can be controlled instantly. Can not be done cause couldn’t control motor torque and it is open-loop control which mean no encoder feedback. Vary precisely because the current of generating torque and the excitation current can be precisely and separately controlled. Also It is available to use encoder feedback for position control. Worse; because frequency reduced will cause rotor’s impedance increase which makes stator and rotor’s coupling become smaller. Armature current does not generate proportional torque which makes motor running efficiency worse. Better: Rotor’s flux vector can be controlled so that it makes rotor’s flux and current vector maintain at 90°. Stator and rotor has the minimum coupling effect which normally only 30% of the rated torque It can be up to 150% of rated torque. AC Motor Drive Comparison between V/Hz and FOC

16 FOC Introduction The FOC control is a method that controls 3-phase AC motor drive like DC motor, whose torque is proportional to its output current. DTC : Direct Torque Control V/FFOCDTC No Encoder Feedback V/F+PG FOC+PG Encoder Feedback Speed Control Torque Control FOCDTC No Encoder Feedback FOC+PG Encoder Feedback Control Family

17 Variable Speed Control Family of AC Motor As AC motor has been widely used in industry, the methods relevant to variable speed control have had developed a lot with technology. According to its frame and method, they are sorted as below: Pulse width modulation (open loop) VVCF Control CVVF Control VVVF Control Control family Slip tuning control (closed loop) Slip ratio of voltage source inverter Slip ratio of current source inverter FOC (closed loop) (Direct Field-Oriented Control) (Indirect Field-Oriented Control) (Slip Torque Control) (Field Acceleration Control) Variable speed control without sensor (Virtual control of closed circuit) Magnetic field control with motor speed estimated and voltage/current feedback Magnetic field control with motor speed estimated and current feedback

18 FOC Introduction *Reference AC Motor Control by Changhuan Liu VE adopts indirect method of the summation of rotor’s magnetic orientation and encoder FOC Family 1.Install flux-meter to measure flux angle. 2.Estimate flux angle. Direct method Rotor’s magnetic orientation Stator’s magnetic orientation Gas’s magnetic orientation Flux reference coordinates Methods of get synchronous flux angle Motor Mechanical Speed With Feedback Sensor No Feedback Sensor Indirect method Use the summation of motor slip frequency and motor’s electric speed then after integral to get the flux angle.

19 AC motor’s torque would in direct proportion to stator current FOC Profile Stator Rotor Id Iq Coordinates conversion w ids iqs Ids flux current Iqs torque current Rotor and Id axes overlaps , ids maintains fixed value D.C. w IsIs Ia Ib Ic 90 o 180 o 270 o 360 o 450 o 540 o IaIbIcIa T I Ia+Ib+Ic=0 Ia+Ib+Ic=Is T I To calculate Is’s vector sum by mathematical integral Is includes two elements of flux Id and torque Iq It changes the phase’s space position via control Ia Ib and Ic Using instant math mode and according to the position to separate Is into Id flux and Iq torque. Id as the element of DC generates magnetic field while Iq as the element of current generates torque. Keep Ids steady as constant while output torque can be changed directly by changing Iqs.

20 Yaskawa G7 Mitsubishi A500 (SVC) ABB ACS800 (DTC) Mode 1 (SVC) Mode 2 (FOC) Step-load performance Low speed2413 Mid speed2413 High speed2413 * Currently Delta use SVC (Sensor-less Vector Control) control mode. The FOC (Field Oriented Control) is under development. * It is marked mainly according to the dynamic response and steadiness. Comparison between FOC and SVC Brand name Order of characteristics

21 Wm (speed control) Wr ide iqe (torque control) Qe iq current control flux control 2/3 decouple iqe tr*ide ibia Wsl id Control diagram This is torque control *Reference AC Motor Control by Changhuan Liu Indirect rotor’s magnetic orientation control diagram

22 RsRs L ls L lr RrRr LmLm VsVs Induction Motor Equivalent Circuit and Parameters Auto-tuning 05-06 05-18 05-07 05-19 05-08 05-20 05-09 05-21 Traditional Electrical engineer Equivalent circuit RsRs LσLσ R LMLM VsVs VE Equivalent circuit Rs : Stator resistance Lσ : Stator’s inductance Rr : rotor’s inductance Lm : Flux mutual inductance Llr : rotor’s leakage inductance

23 Parameter adjust and V/f mode Trial Run This is mainly means spindle motor. Because the spindle motor nameplate normally will not match its spec. So, take V/F trial run first. Parameters are set as factory values and make sure all the wiring is correct. 1 To set up: Maximum frequency: 01-00 Rated frequency: 01-01 Rated voltage: 01-02 Control mode 00-10=0( VF control mode) Set the Running frequency as the motor's rated frequency. 2 RUN NO Is the current and speed logically? To check output current and motor’s speed. 3 Increase Frequency (slowly) to maximum operation frequency. 4 Congratulations! V/F curve is correct and motor can run at high speed. STOP 5 Please re-adjust V/F curve and operate again STOP 6 Motor may not run at over frequency. STOP 7 YES NO YES Check point 1.Does current near or exceed full load current? 2.Is the slip too big? Check Point 1. Does current decreases when speed is increasing 2. Is the slip too big?

24 Motor Parameters Auto- tuning YES NO1 Can the load be removed from motor? 3.2 Input motor no load current 05-05(guessed) Set 05-00 to 2(static tuning), then press RUN 3.3 Set 05-00 to 3(static tuning and motor’s axis should be locked), then press RUN. (If it not locked motor will run) Parameters are set as factory values and the all wiring is correct. 1 according to motor’s nameplate: Rated voltage: 01-02 Rated frequency: 01-01 Full loaded current: 05-01 Motor power: 05-02 Rated speed: 05-03 motor’s poles: 05-04 According to motor’s power to input suitable ACC./DEC. time: 01-12, 01-13 If motor’s base frequency is bigger than maximum operating freq.(01-00), please set 01-00 as the same with 01-01 2 Set 05-00 to 1(dynamic tuning), then press RUN. (Notice: motor will run) 3.1 NO2 For a while, it is completed when motor has stopped. This process need about 30 s, with small motor. For large motor, it determined by ACC./DEC. time. It will display AUE when it fails. Please check whether wiring and parameters are all correct. Check parameters 05-00,05-06,05-07,05- 08,05-09 whether have successfully been written in 4

25 FOC+PG control mode -Trial Run Select PG feedback card that is suitable to encoder power source and signal type. 1 Correctly installed into drive’s slot and wiring correctly. Input PPR of encoder : 10-00 2 Input encoder’s signal type: 10-01 EMV-PG01X EMV-PG01O EMV-PG01L Set control mode 00- 10= 3 (FOC+PG) Set lower Fcmd for testing RUN Any PG error or abnormity speed? Check other frequency A Change running direction STOP PGF1 check parameters PGF2 wire disconnected PGF3 feedback stall PGF4 slip abnormity B Operate again after elimination Current abnormity C Check the numbers of pulse of the encoder weather is the same with parameters10-00 Check whether the settings of mechanical electronic gear ratio 10-27,10-28 is all right Operate again after elimination YES NO

26 Inertia Estimation Check the coupling of load and motor are all correctly Adjust ACC./DEC. time according to load inertia. The less load inertia need shorter ACC./DEC. time 2 RUN NO YES Do FWD/REV running quickly and observe the change of parameters 11- 01 3 FWD REV Parameters 11-01 has convergence or not Parameters 11-01 has change or not Stop motor’s running 4 Press the PROG/DATA key for set last convergence into 11-01 PROG DATA Set 11-00 as 0 Inertia is estimated wrongly. Decrease the frequency command and estimate again. Continue to estimate 1 Confirm drive control mode 00-10=3 Set Fcmd to 2/3 of motor’s rated frequency Set 11-00 as 2 YES NO Convergence speed is according to different load inertia. The bigger inertia convergence is slower and needs do more test

27 02468101214161820 -60 -40 -20 0 20 40 60 02468101214161820 800 1000 1200 1400 1600 1800 (Hz) (PU) SpdRef inertia Inertia Estimation Frequency command Load inertia value System will run Convergence

28 Vector control diagram 00-20 P I + + + + + ÷ - Current control PWM 00-17 M coordinates change Encoder 10-00, 10-01 Actual frequency Current feedback Weak magnetism curve Torque bias 07-28 No bias According to 03-00 analog multi-function According to 07-28 torque bias According to multi-function input terminals Torque limit ASR low-pass filter 10-09 07-32~07-35 10-21/10-22 zero speed PI 10-04/10-05 middle speed PI 10-06/10-07 high speed PI Base voltage/current: 01-01/01-02 Motor’s parameters 05-01~05-09 Source of frequency command PI adjustor

29 Vector control -Adjust Methods YES Estimate Jm value NO Set auto gain adjustment 11-00=1 Adjust 11-02, 11-03 & 11-11 separately for difference speed which its response need Adjust if it is require 11-04 (PDFF function) Adjust by requirement 10-08 (ASR1/ASR2 switch frequency) Adjust by requirement 07-32~35 (torque limit) Manual gain adjust 11-00=0 (factory setting) Adjust 10-04, 10-05 : middle speed 10-06, 10-07: high speed 10-21, 10-22: 0 speed Adjust by requirement 10-09(normally no need to adjust)

30 Vector control- PI Adjustor To adjust 11-11 for output higher torque at 0Hz 10-06 10-07 10-04 10-05 10-21 10-22 0 Hz 10-08 Hz PI 5 Hz (PI adjustment-Manual gain adjust) 11-03 11-02 11-11 0 Hz 10-08 Hz PI 5 Hz 1.Must known inertia first 2.Set 11-00 as 1 (PI adjustment-auto gain adjust) To adjust 10-21, 10-22 for output higher torque at 0Hz

31 Beside traditional PI control, VE-series also provides PDFF function to reduce overshoot. To enable PDFF function, it need to: 1.Must know inertia first 2.Set 11-00 to 1 3.Adjust 11-04 (the larger number is set and the suppressed overshoot function will be better. But it will cause worse system response) Vector control-PDFF It is recommended to disable this function (Pr. 11-04=0) for Y- △ connection switch and ASR1/ASR2 switch application PDFF PI

32 For the spindle application, the adjustment method is 1. To run the motor at its max. frequency 2. Monitor the output voltage 3. Adjust settings of Pr.11-05 (motor 1) or Pr.11-06 (motor 2) to make the output voltage reach motor rated voltage 4. The larger number it is set, the larger output voltage you will get. Vector control-Flux Weakening Curve Fbase 11-05 / 11-06 Hz N-m

33 Vector control-Speed Feedforward For the spindle motor fast ACC./DEC application The adjustment method is: 1. With factory default and it can not meet the requirement of system ACC./DEC. time 2. Adjust 11-12, the larger number you set, the faster response you will get. 3. For general, no need to adjust.

34 10-23 Position feed forward Position Control diagram P I + + + ÷ - Current control PWM 00-17 M coordinates change Encoder Actual frequency Current feedback Weak magnetism curve Toque bias 07-27 No bias According to 03-00 analog multi-function According to 07-28 toque bias According to multi-function to input terminals Toque limit ASR low-pass filter 10-09 07-32~07-35 06-12 10-21/10-22 zero speed PI 10-04/10-05 middle speed PI 10-06/10-07 high speed PI 10-00 10-01 PI adjustor P D Integral + - + + Actual position 10-21 Position command Frequency command

35 Tuning-Position 10-23 P D + + + Position command Frequency command Actual position 10-21 Position selection 10-19 I/O serial position PG card Pulse command According to multi-function Input -  10-19 internal position (Home)  Multi-input uses external terminals to set 34 multi-step position function enable (multi-point position)  Serial, uses external terminals to set 41 serial position clock and 42 serial position (multi-point position) All above need to use external terminals to set 35 position control  PG reference input, use 00-20 = 5, 10-15 PG ref input Enable External terminals set 37 pulse position command input enable (position following)

36 Torque Control diagram P I + + + + ÷ - Current control PWM 00-17 M Encoder Actual frequency Current feedback Weak magnetism curve Toque bias 07-27 No bias According to 03-00 analog multi-function According to multi-function to input terminals Toque limit 06-12 ASR low-pass filter 10-09 Toque limit 07-32~07-35 10-21/10-22 zero speed PI 10-04/10-05 middle speed PI 10-06/10-07 high speed PI 10-00 10-01 PI adjustor The source of toque command can through 07-21 to select KP/communication/analog Toque limit Toque command filter time 07-23 speed/toque Mode selection + Speed limit command is selected by 07-24, 00-20 or 07-25/07-26 coordinates change According to 07-28 toque bias

37 06-12 current limit Torque Limit of FOC Quadrant 1 Quadrant 4 Quadrant 3 Quadrant 2 Forward motor mode Reverse generator mode Reverse motor mode Forward generator mode Forward Reverse speed Positive torque Negative torque The minimum of the comparison result of the three layers will be torque limit Analog terminal 03-00~02 d7: positive torque limit d9: regenerative torque limit d10: positive/negative torque limit Analog terminal 03-00~02 d7: positive torque limit d10: positive/negative torque limit Analog terminal 03-00~02 d8: negative torque limit d9: regenerative torque limit d10: positive/negative torque limit Analog terminal 03-00~02 d8: negative torque limit d9: regenerative torque limit d10: positive/negative torque limit Reverse regenerative torque Limit 07-35 Forward regenerative torque Limit 07-33 Forward motor torque Limit 07-32 Reverse motor torque Limit 07-34

38 Torque Control-Speed Limit Method Method 1 07-24=0 Speed limit is from Pr.07-25,Pr.07-26 Torque frequency/speed Forward 07-25Reverse 07-26 Method 2 07-24=1 Speed limit is from Pr.00-20 (Source of the frequency command ) Torque frequency/speed Reverse 00-20Reverse 07-26 Toque frequency/speed Forward 07-25Reverse 00-20 When 07-24=1, Speed limit is positive, then negative speed limit is determined by 07-26 When 07-24=1, Speed limit is negative, then positive speed limit is determined by 07-25

39 Torque Control Speed Control Torque Control Speed Control ON RUN Speed/Torque Control Switch ON Multi-function Input Default: d26 Torque/Speed Mode Switch OFF Speed Limit Speed Command Speed Limit Speed Command Torque Command Torque Limit Torque Command Torque Limit Run/Stop 03-00~03=d1 AVI/AUI/ACI: Fcmd 03-00~03=d2 AVI/AUI/ACI: Tcmd Control Mode Speed Control (Ramp to Stop) STOP Speed/Torque Control Timing Chart 00-10 =d03/d04

40 Motor Y- △ Switch Function (Wiring) Y- △ connection switch: can be used for wide range motor Y connection for low speed: higher torque can be used for rigid tapping △ connection for high speed: higher speed can be used for high-speed drilling IM UVW XYZ △ connection control 02-11~14=d32 Y connection control 02-11~14=d31 RA MRA U V W △ connection is completed 02-01~06=d30 Y-connection is completed 02-01~06=d29 MI1 MI2 Wiring diagram of Y- △ connection switch function

41 Motor Y- △ Switch Timing Chart ON If switch F setting is 60Hz, then real switch F is 62Hz at acceleration 05-11 Y- △ Switch frequency Real switch F is 58Hz at Deceleration Motor speed/frequency 1. Here motor is in free run status, VFD stops outputting 2. Motor speed will decreases according to load inertia Y-connection control signal output Y-connection confirmation input △ connection Control signal output 02-11~14=d32 △ connection confirmation input 02-11~14=d30 Mechanical spring time 02-11~14=d31 02-11~14=d29 Switch waiting time is 05-30 min.=0.2sec Band is 2Hz

42 RUN Mechanical brake release DC brake Brake Control Function Mechanical brake Control function can work together with zero speed holding or DC brake to get the purpose of load would not slide or pause when starting up. So it can be widely used in the field of elevator and crane. Motor speed/frequency 02-31 brake release delay time Brake delay release output 02-11~02-14 =d12 Mechanical brake braked 07-02 DC braking time during start 07-03 DC braking time during stop RUN/STOP STOP

43 DEB Function (Deceleration Energies Regeneration) The DEB (Deceleration Energy Backup) function is the AC motor drive decelerates to stop after momentary power loss. When the momentary power loss occurs, this function can be used for the motor to decelerate to 0 speed with deceleration stop method. When the power is on again, motor will run again after DEB return time. ( Can be applied to high speed spindle motor) It doesn't need multi- function terminals DC BUS LV level Soft-start relay ON level (LV+30V) DEB return time counting level (LV+30V+58V) 07-14 Soft-start Relay DEB function is activated Output frequency DEB return time Pr. 07-13 DEB DEC. Time Status 1: Insufficient power supply due to momentary power-loss/ unstable power (due to low voltage)/ sudden heavy-load When Pr. 07-14 is set to 0, the AC motor drive will be stopped. Drive will not ACE. To the frequency before DEB even the power has return

44 Status 3:Some brand can enable DEB function via external terminal. For VFD-VE series, the DEB function can be used by combine deceleration time and EF function. For example, in textile machinery, you will hope that all the machines can be decelerated to stop to prevent broken stitching when power loss. In this case, the system controller will send a signal to the drive, thus, it can be done via combine DEB and EF function. DEB Function (Sequel) DC BUS voltage LV level Soft-start relay ON level (LV+30V) DEB return counting time level (LV+30V+58V) 07-14 Soft start relay DEB function is activated Output frequency DEB return time DEB DEC. time 07-13 Status 2: unexpected power off, such as momentary power loss

45 This function is used to enhance the unstable speed/position due to analog resolution no enough. It needs to use with external input terminals (Pr 02-11~Pr.02-14 set 43). Set Pr. 10-25 as analog input resolution switch frequency Max. frequency for resolution switch of analog simulation value Resolution switch 02-11~02-14 =d43 FORWARDREVERSE AUI 0V AUI +10V AUI -10V Max. output frequency Pr.01-00 Resolution switch frequency Pr. 10-25 Output frequency 0Hz Max, frequency switch waiting time

46 Spindle motor (0.75kW~11kW) Main applying function:0~3600Hz High speed curving machine PCB drilling machine Spindle motor Market Application 1

47 Elevator (7.5kW~22kW) (90m/min), crane Main applying function: FOCPG control, auto DC brake and mechanical brake control Market Application 2

48 Drilling, lathe, milling and curving Integrated CNC machine, tools box Main applying function: home position, multi-step position, pulse command position, electronic gear ratio, mechanical gear ratio, Y- △ start-up switch and speed search Market Application 3

49 Printing machine Main applying function : toque control (TQRPG) Surface and intaglio printing machine, flexible printing machine Market Application 4

50 Application Example 1

51 Application 1 (flexible tapping-Wiring) FWD REV AVI Speed command MI1 Accel time 1 and 2 switch RLY1 Driver is ready MO1 Speed attained MO2 Zero speed including stop U.V,W 1024ppr Line-drive PG in VFD controller Motor Spindle 1024ppr Line-drive

52 Application 1 (flexible tapping-Time chart) SpdRef Run Stop FWD MI1 = 1/2 accel/decel switch Drilling Flexible tapping Run 1st step accel/decel 2nd step accel/decel Z axis in Spindle decelerate Z axis doesn't move Principle axis Z 軸 out

53 Drilling Flexible tapping Application 1(flexible tapping-Wave Form) 1000rpm

54 Application 1 (High-Speed Position -Wiring) FWD REV AVI Speed Command MI4 Position Control ON RLY1 Error indication MO1 At speed (Setpoint at running) MO2 Zero Speed including Drive Stop(INV fout) U.V,W PG in AC Motor Drive Controller Motor Spindle 1024ppr Line-drive MI5 Reset RLY2 On Position PG out

55 Application 1 (High-Speed Position –Time chart) SpdRef Run Stop FWD MI4 = Position Control (35) Speed Mode Position Mode (internal position, home 10-19) RLY2 = On Position (39) MO1 = At Speed (2) MO2 = Zero Speed (34)

56 Application 1(High-Speed Position-Wave Form) 24681012141618 -100 0 100 200 300 24681012141618 -50 0 50 100 24681012141618 -50 0 50 (Hz) (A) SpdFdb iqRef ias High speed internal position

57 Application 1 (Motor Y-D Switch) Y Delta Y

58 Application Example 2

59 Application 2 (Fast Acceleration/Deceleration) About 4 seconds 12000rpm About 2 seconds

60 Application Example 3

61 Application 4 (Tension Control - Wiring) FWD REV AVI Speed Limit AUI Torque Command (0~10V) MO1 Error indication U.V,W PG in AC Motor Drive Controller Motor 1024ppr Line-drive PG out Diagram 1: V Wiring As for VFD-V, FWD/REV specifies torque command and speed limit direction.

62 Application Example 4 (Tension Control –VE Wiring) FWD REV AVI Speed Limit AVI2 Torque Command (0~10V) MO1 Error indication U.V,W PG in AC Motor Drive Controller Motor 1024ppr Line-drive PG out Diagram 2: VE Wiring MI1 direction of Torque command If the torque command is from AUI, then, torque direction is decided by the by AUI.

63 Application 4 (Tension Control –Time chart) SpdLimit Run Stop FWD MI1 = direction of Torque command Torque Command SpdLimit Run Stop REV MI1 = direction of Torque command Torque Command Control Time chart: (a) FWD Torque Command; (b) REV Torque Command (a) (b) Speed limit have accelerate/decelerate

64 Application 4 (Tension Control-Wave Form) Torque Mode Speed Mode PG feedback signals are interfered, which causes unstable speed.

65 Application 5 (Elevator Control-Wiring) Eric (seem G5)Cable NumberVE PinDef.SetPinSet 19RB Error indication 028RB Error indication 20RC0028RC 9MRA During Run 002MRA Brake release function 10MRC006MRC 11DCM018DCM 6S6Multi-Speed 2 (25Hz)023MI 1Multi-Speed 2 (25Hz) 5S5Emergency Stop0022MI 4Emergency Stop 1S1FWD020FWD 2S2REV021REV 7S7Multi-Speed 3 (6Hz)022MI 2Multi-Speed 2 (6Hz) 8S8Jog (0Hz)024MI 5Multi-Speed 3 (0Hz) 3S3 Multi-Acc/Dec 1 (connect to pin7) MI 3 Multi-Acc/Dec 1 (connect to MI 2) 4S4 Multi-Acc/Dec 2 (connect to pin8) MI 6 Multi-Acc/Dec 2 (connect to MI 5)

66 Application 5 (Elevator Control -Timing) SpdRef Motor Operation Indication Run/Stop Command DCI Brake 40Hz 6Hz 0Hz DCI MI2 & MI3 MI5 & MI6 2nd step speed 6Hz 3rd step speed 0Hz

67 Application 5 (Elevator Control –Wave Form) 02468101214161820 -10 0 10 20 30 40 50 02468101214161820 0 10 20 30 40 50 02468101214161820 -50 0 50 (Hz) (A) Spd* Spd iq* ias

68 Thank You

69 +/- Multi-function terminals PID cancelled 02-01~02-06=d21 d/dt ∫ Integral time upper limit 08-04 Delay time 08-07 PID Freq. Output Command limit 08-05 Feedback signal offset 08-14 feedback signal offset value 08=15 feedback signal detect time PID offset value 08-06 + + + Frequency command F com Warn and keep operatingd0 Warn and ramp to stopd1 Warn and coast to stopd2 Warn and keep at last frequency d3 Treatment of ACI feedback signal break 08-09 Detect time 08-08 Multi-function simulation value 03-00,03-01 03-02 PG2 pulse input 10-15 Multi-function simulation value 03-00,03-01 03-02 Multi-function digital terminal MI1~MI6 02-01~02-06 PID feedback display 00-04=d10 Input Selection of the PID targeted Value 00-20 Analog signal filter time 03-13,03-14,03-15 PID feedback source 08-00 Analog signal filter time 03-13,03-14,03-15 PG2 signal filter time 11-17 Integral time I(08-02) Derivative time D(08-03) P gain Proportional gain P(08-01) Σ + ΣΣ

70 PID feedback source 08-00 No PID feedbackd0 Positive PID feedback from AVI d1 Positive PID feedback from PG card skip direction d2 Positive PID feedback from PG2 input d3 Negative PID feedback from AVI d4 Negative PID feedback from PG2 skip direction d5 Negative PID feedback from PG2 d5 No functiond0 AVI analog input 03-00 d5 ACI analog input 03-01 d5 AUI analog input 03-02 d5 Multi-function analog function PID source of the master frequency command 00-20 Digital keypadd0 RS-485 serial communication d1 Multi-function analog terminals d2 By multi-function digital terminals d3 PG2 pulse input skip direction d4 PG2 pulse inputd5 No functiond0 AVI analog input 03-00 d4 ACI analog input 03-01 d4 AUI analog input 03-02 d4 Multi-function analog input No functiond0 A phase lead B phase d1 B phase lead A phase d2 A is pulse, B is direction d3 PG2 pulse input 10-15 B is pulse, A is direction d4 Frequency UP command d19 Frequency DOWN command d20 Multi-step command d1,d2,d3,d4 Multi-function digital terminals 02-01~02-06(MI1~MI6) JOG commandd5 Proportional gain P(08-01) +/- Multi-function PID cancelled 02-01~02-06=d21 Derivative time D(08-03) Integral time I(08-02) Integral time upper limit 08-04 Delay time 08-07 PID output upper limit 08-05 Feedback fault treatment If F out >08-05 detection time or feedback fault 08-09 PID offset value 08-06 + + + Frequency command F com Feedback signals filter time 08-15 08-14 08-15 +/- Warn and keep operatingd0 Warn and ramp to stopd1 Warn and coast to stopd2 Warn and keep at last frequency d3 Treatment of ACI feedback signal fault 08-09 Detect time 08-08

71 Proportional gain P(08-01) +/- Multi-function PID cancel 02-01~02-06=d21 Differential time D(08-03) Integral time I(08-02) Integral time Upper limit 08-04 PID delay Time 08-07 08-05 PID Freq. Output Command limit Treatment of the feedback Signal fault If F out >08-05 Time over 08-09 PID offset 08-06 + + + Frequency command F com Warn and keep operating d0 Warn and RAMP to stop d1 Warn and COAST to stop d2 Warn and keep at last frequencyd3 Treatment of ACI feedback signal fault 08-09 Detect time 08-08 ACI feedback signal Feedback signal filter time 08-15 08-14 08-15 +/- Multi-function simulation value 03-00,03-01 03-02 PG2 pulse input 10-15 Multi-function simulation value 03-00,03-01 03-02 Multi-function digital terminal MI1~MI6 02-01~02-06 PID feedback display 00-04=d10 Input Selection of the PID targeted Value 00-20 Analog signal filter time 03-13,03-14,03-15 PID feedback source 08-00


Download ppt "VE Training in 2006 Tainan Plant Dunrong Lee Taoyuan Plant Zhiming Xu 2006/12/18."

Similar presentations


Ads by Google