Programming the CD101
3
Push and hold the SET button for 3 seconds
4
AL1 will appear. Keep pressing the SET button until you see LCK
5
The default value of LCK will be 1000. We need to change this value to unlock the thermocouple settings.
6
Change the value of LCK to 1100. You can use the < key to change the cursor position. Press SET again until you have exited the menu.
7
(back to the normal operation screen)
8
Push and hold SET and < together
9
Set the value of Cod to 0000
10
Change the value of SL1 to 1100 for the pt100 thermocouple
11
Press and hold SET and < to return to normal operation
12
Normal operation
13
Push and hold the SET button for 3 seconds
14
Keep pressing SET until you see LCK. Set the value to 1000. Press and hold SET to exit the menu.
15
Normal operation
16
Setting the desired temperature
17
Press and release the SET button. The orange numbers on the SV row will flicker. Use the ˄ and ˅ buttons to change the value. Use the < button to change decimal places. Press SET to confirm.
18
For additional programming details, see this manual for the CD101 controller. For other PID controllers, consult your users manual.this manual for the CD101 controller