Presentation is loading. Please wait.

Presentation is loading. Please wait.

CIMON PLC KDT Systems Co., Ltd.. KDT SYSTEMS Why CIMON PLCs ? All CPU share the same programming environment (CICON) All CPU share the same programming.

Similar presentations


Presentation on theme: "CIMON PLC KDT Systems Co., Ltd.. KDT SYSTEMS Why CIMON PLCs ? All CPU share the same programming environment (CICON) All CPU share the same programming."— Presentation transcript:

1 CIMON PLC KDT Systems Co., Ltd.

2 KDT SYSTEMS

3 Why CIMON PLCs ? All CPU share the same programming environment (CICON) All CPU share the same programming environment (CICON) No additional training needed for up/down sizing of control systemNo additional training needed for up/down sizing of control system Though BP series are small sized PLC, they inherit powerful functionalities from higher series of CIMON PLCs (CP/XP)Though BP series are small sized PLC, they inherit powerful functionalities from higher series of CIMON PLCs (CP/XP)

4 KDT SYSTEMS Why CIMON PLCs ? CP and XP CPU share the same modules CP and XP CPU share the same modules I/O modules, special function modules, power, base....I/O modules, special function modules, power, base.... Provides big merit on maintenance as well as cost.Provides big merit on maintenance as well as cost.

5 KDT SYSTEMS Why CIMON PLCs ? Fully verified network compatibility Fully verified network compatibility not only between PLCsnot only between PLCs but also SCADA and Panels (TOUCH, XPanel)but also SCADA and Panels (TOUCH, XPanel)

6 KDT SYSTEMS What is different ? : Technologies How many PLC manufacturers support redundant system in all around the world ? How many PLC manufacturers support redundant system in all around the world ? CIMON supports redundant PLC CPU system.CIMON supports redundant PLC CPU system. and we have some good references as power plant.and we have some good references as power plant.

7 KDT SYSTEMS Redundant CPU Details

8 KDT SYSTEMS What is different ? : Expansion Innovative base expansion system Innovative base expansion system Provides easy engineering with simple cableProvides easy engineering with simple cable Removes the distance limit between basesRemoves the distance limit between bases Plays the same role of remote I/O, but faster.Plays the same role of remote I/O, but faster. Expansible up to 16 basesExpansible up to 16 bases Category 5, 10Base-T, Max 100m

9 KDT SYSTEMS CPU EP02A EP02A  2 Port  10Mbps Ethernet Expansion numner setup by rotary switch Expansion numner setup by rotary switch EP01A EP01A  1 Port  10Mbps Ethernet LOCAL EXPANSION #1 EXPANSION #2 EXPANSION #14 EXPANSION #15 EXPANSION #16

10 KDT SYSTEMS What is different ? : Ethernet Take the internet on your fields Take the internet on your fields Even BP supports the ethernet. (option)Even BP supports the ethernet. (option) Remote maintenance by internet : The CICON can connect with a PLC though internet.Remote maintenance by internet : The CICON can connect with a PLC though internet.

11 KDT SYSTEMS What is different ? : CICON Dialog based configuration Dialog based configuration Removes DIP switches from special function modulesRemoves DIP switches from special function modules Dialog based programming Dialog based programming Generates sequence program automaticallyGenerates sequence program automatically PID, Protocol, Network configurationsPID, Protocol, Network configurations Special function card configurationsSpecial function card configurations Thermistor, Loadcell, position (pulse output) Thermistor, Loadcell, position (pulse output) Continued ....Continued ....

12 KDT SYSTEMS Dialog based programming

13 CPU Specifications

14 KDT SYSTEMS CPU Specification : XP XP1RXP1AXP2AXP3A Program Memory 128 Kstep64 Kstep I/O Point 819240962048 USB / RTC USB / RTCYes MemoryD: 32000 Words / M,L,K: 16000 Points / T,C: 4096 RedundancyYesNo

15 KDT SYSTEMS CPU Specification : CP CP3P : Removable flash memory CP3P : Removable flash memory CP3ACP3BCP3PCP3UCP4ACP4BCP4CCP4DCP4U PgmMem 32 KStep16 KStep I/O1024384 DataMem 100005000 RTCNoYesNo Yes USBNoYesNoYes Comm.No RS232CRS422/485

16 KDT SYSTEMS CPU Specification : BP InputOutput BP32MDT 16 DC24V 16 Tr. Sink BP32MDCTr. Source BP32MDRRelay BP16MDT 87 Tr. Sink BP16MDC Tr. Source BP16MDR Relay

17 KDT SYSTEMS CPU Specification : BP BP32M  Abundant program capacity:  8,000 Step  Device Range:  Internal Relay: 4,096 Points  Data Memory: 5,000 Words  Max. 3 block expansion BP16M  Abundant program capacity:  4,000 Step  Device Range:  Internal Relay: 4,000 Points  Data Memory: 1,000 Words  Not expansible

18 Basic Modules

19 KDT SYSTEMS PowerSPASPC/SPRSP2B Input Voltage AC 90~240V, 50/60Hz DC 24V Input Current 0.25A Max for 220VAC 1.8A Max Inrush Current Less than 30A Output Voltage/Current +5V / 3.5A +24V / 0.5A +5V / 3.5A +24V / 0.5A +15V / 0.5A -15V / 0.3A +5V / 3.5A +15V / 0.5A -15V / 0.3A SPA cannot be used with analog/temperature modules

20 KDT SYSTEMS Base Model I/O Slots CM1-BS03A3 CM1-BS04A4 CM1-BS05A/R5 CM1-BS08A/R8 CM1-BS10A/R10 CM1-BS12A12

21 KDT SYSTEMS Digital Input XD16AXD16B  16 DC 24V Input  Photo coupler isol ation XD32CXD32B  32 DC 24V Input  Photo coupler isolati on XA08A XA08B  8 AC Input XY16DR  8 24Vdc Input  8 Relay Output

22 KDT SYSTEMS Digital Output YR16A  16 Relay  2 Amp / 240VAC YS08A  8 SSR  100~240Vac YT16AYT16B  16 Tr. Output  0.5A / 24V  Sink /Source YT32AYT32B  32 Tr. Output  0.2A / 24V  Sink /Source

23 KDT SYSTEMS Analog Input  All settings are configured by CICON  Input Voltage : 0 ~ 5V, 1 ~ 5V, 0 ~ 10V, -10 ~10V  Input Current : 0 ~ 20mA, 4 ~20mA  Resolution : 14 bit  Photocoupler isolated AD08V Voltage Input 8 Ch. AD08I Current Input 8Ch. AD04VI Voltage/Current Input 4 Ch. (configurable)

24 KDT SYSTEMS Analog Output  All settings are configured by CICON  Output Voltage : -10 ~10V  Output Current : 4 ~20mA  Resolution : 14 bit  Photocoupler isolated. DA04V Voltage output 4 Ch. DA08V Voltage output 8 Ch. DA04I Current output 4 Ch. DA08I Current output 8 Ch.

25 Special Function Modules

26 KDT SYSTEMS RTD  4 Channels  All settings are configured by CICON  Resolution : 14 bit  Real temp. value provided (in C, F)  Resolution in Temp. : 0.1 C  Photo coupler isolated RD04A for Pt.100, JPt.100 RD04B for Pt.1000, JPt.1000

27 KDT SYSTEMS Thermocoupler TC04A  4 Channels  All settings are configured by CICON  Resolution : 14 bit  Real temp. value provided (in C, F)  Resolution in Temp. : 0.1 C  Photo coupler isolated

28 KDT SYSTEMS Thermistor TH08A  8 Channels  All settings are configured by CICON  includes resistance table input  Type : NTC thermistor  Resolution : 14 bit  Real temp. value provided (in C, F)  Resolution in resistance :  100Ω ~ 40kΩ : 1Ω  40kΩ ~ 400kΩ: 10Ω  400kΩ ~ 1MΩ : 30Ω

29 KDT SYSTEMS Loadcell WG02A / WG04A  2 or 4 channels loadcell input ( ~ 3mV/V)  1/200,000 resolution  Embedded batch process control (unloading/mixing/filling/bin)

30 KDT SYSTEMS High Speed Counter  2 Channels  All settings are configured by CICON  1-Phase input or 2-Phase input  32 bit counter  Speed : Max. 200 kPPS  Provides comparator output ( ) HS02B Voltage input signal (5, 12, 24 Vdc) HS02D RS422A input signal level (Line driver)

31 KDT SYSTEMS Pulse Output / Positioning PS02A  2 axis  Line driver pulse output (RS422A)  All settings are configured by CICON  Position parameter / tables  Supports 2 axis linear/arc interpolation  Speed : Max. 1 MPPS

32 Communication & Network

33 KDT SYSTEMS Serial Communication Application Protocol Application Protocol HMI-ProtocolHMI-Protocol MODBUS/RTU Slave & MasterMODBUS/RTU Slave & Master DNP3.0DNP3.0 PLC Link : Max. 32 stationsPLC Link : Max. 32 stations Loader (CICON) communicationLoader (CICON) communication Supports modem connection Supports modem connection Embedded RS232C-RS422/485 converter Embedded RS232C-RS422/485 converterSC01A RS232C 1 Ch. SC01B RS422/485 1 Ch. SC02A RS232C 1Ch. + RS422/485 1 Ch. SC01DNP RS232C 1 Ch. (DNP 3.0 protocol)

34 KDT SYSTEMS Typical Serial Application Plays a role of RS232C- RS485 Converter

35 KDT SYSTEMS Remote Network by Modem Leased Line Modem (DSU) or Dial-Up Modem

36 KDT SYSTEMS Ethernet No limit on number of EC01A with a CPU No limit on number of EC01A with a CPU Application Protocol Application Protocol HMI-Protocol, MODBUS/TCP, DNP3.0HMI-Protocol, MODBUS/TCP, DNP3.0 PLC Link : Max. 64 stationsPLC Link : Max. 64 stations Loader (CICON) communicationLoader (CICON) communication Protocol Stack Protocol Stack ARP, ICMP, IP, UDP, TCPARP, ICMP, IP, UDP, TCP 10BaseT, 10 Mbps 10BaseT, 10 Mbps

37 KDT SYSTEMS HMI Link by Ethernet

38 KDT SYSTEMS PLC Link by Ethernet

39 KDT SYSTEMS Data Logger LG32A / LG64A  Data log buffer for PLC  Logged data are retained in PLC while communication fail.  All logged data are transmitted to SCADA after communication recover.  Embedded communication  Protocol : HMI Protocol  Port : RS232C (supports cable / dial-up modem)  Internal non-volatile log memory : 32 MB / 64MB

40 BP Series Expansion Blocks

41 KDT SYSTEMS Expansion block naming : BP CM2 – BP (1) E (2) (3) Series Name Number of Points 04, 16, 32 Module Type E : Expansion Output Type T: Digital TR Output(Sink) C: Digital TR Output(Src) R: Digital Relay Output A: Analog Output O: No Output Input Type D: Digital DC 24V Input A: Analog Input R: RTD Input T: TC Input O: No Input

42 KDT SYSTEMS Digital I/O Expansion ModuleInputOutput BP16EDTBP16EDCBP16EDR8 DC 24V 8 TR Sink TR Source Relay BP32EDTBP32EDCBP32EDR1616 TR Sink TR Source Relay BP16EDO160- BP16EOTBP16EOCBP16EOR0-16 TR Sink TR Source Relay

43 KDT SYSTEMS Analog Expansion ModuleInputOutput BP04EAO4 Voltage/Current 0- BP04EAA22 Voltage/Current BP04E0A0-4 BP04ERO4 RTD (Pt.100/JPt.100) 0- BP04ETO4Thermocoupler0- Analog module can be expanded up to 2 modules.


Download ppt "CIMON PLC KDT Systems Co., Ltd.. KDT SYSTEMS Why CIMON PLCs ? All CPU share the same programming environment (CICON) All CPU share the same programming."