1 ADS / PHX SERIES SYSTEMS DESIGN

2 What is the ADS / PHX Series?
FM-200 Stored under its own vapor pressure 44 psig Kidde FM-200

3 What is the ADS / PHX Series?
Separate nitrogen storage N2 psig

4 What is the ADS / PHX Series?
Continuous Supply of Nitrogen N2 Acts as a Gas Piston - “Piston Flow”

5 Why do we need the ADS / PHX Series?
FM-200 superpressurized with nitrogen 360 psig N2 Dissolved Nitrogen FM-200

6 System Performance Comparison
400 psig ADS Series ECS / 9300 Series Pressure Time 10 Sec

7 Why do we need the ADS / PHX Series?
Longer Pipe Runs Convenient Cylinder Placement More Efficient Use of Cylinder Fills Difficult Pipe Networks Greater Flexibility Smaller Diameter Pipe

8 ADS / PHX Nozzles Two nozzle types Nozzle sizes 180° Nozzle
1/2” through 2”

9 ADS / PHX Nozzles 180° Nozzle Placed 1” to 2” from a wall
discharge slot aimed away from the wall As close to center of the wall as possible At least 1/3 1/2” to 6” from ceiling to discharge slot

10 ADS / PHX Nozzles 360° Nozzle
Placed as close to center of hazard as possible 1/2” to 6” from ceiling to discharge slot

11 ADS / PHX Nozzle Locations
Proximity of nozzles to significant obstructions At least 3 ft. to 4 ft. of clearance between nozzle and wall (or significant obstruction) Proximity of multiple nozzles At least 6 ft. of clearance between nozzles

12 ADS / PHX Nozzle Locations
Back-to-Back 180° Nozzles 1 ft. to 2 ft. apart Must face away from each other Nozzles discharge equal quantities

13 ADS / PHX Nozzle Coverage
Tested 46 ft. x 56 ft. Rectangle Actual coverage area defined as rectangle with diagonal, d 180° - d = 60.5 ft ° - d = 36.2 ft.

14 ADS / PHX Nozzle Height Maximum height for single nozzle is 16 ft.
Nozzle tiers are allowed Minimum height 1 ft. for UL Listed systems 6” for Kidde Approved Must reduce coverage area for height, 6” to 12” 30 ft. x 30 ft. 180° - d = 33.5 ft. 360° - d = 21.2 ft.

15 ADS / PHX Nozzle Orientation
Ceiling heights 1 ft. and up, nozzles must be pendant (hanging down) Ceiling heights less than 1 ft., nozzles may be either pendant or upright These heights are not UL Listed/FM Approved

16 ADS / PHX Piping Network: Tees
Tee Parameters: Tee Orientation Flow Splits Bull Tees Side Tees “6 Pipe Diameters”

17 ADS / PHX Piping Network: Tees
Any orientation is allowed Horizontal and vertical outlets, as well as inlets 1 inlet, 2 outlets

18 ADS / PHX Piping Network: Tees
Bull tee flow split Minimum imbalance: 50/50 Maximum imbalance: 85/15 IN OUT

19 ADS / PHX Piping Network: Tees
Side tee flow split Minimum imbalance: 65/35 Maximum imbalance Horizontal feed: 85/15 Vertical feed: 84/16 SIDE OUTLET (15 to 35) IN RUN OUTLET (65 to 85)

20 ADS / PHX Piping Network: Tees
“6 Pipe Diameters” Rule: Length of pipe between a tee and a change in direction must be equal to 6 times the nominal diameter of the pipe A change in direction is defined as either an elbow or another tee Must be adhered to before and after the tee Only necessary if the tee feeds agent to separate hazards

21 ADS / PHX Piping Network: Layout
Keep network as simple, balanced and short as possible Consider structural members for hanging/bracing Avoid obstructions

22 ADS / PHX Piping Network: Layout
Maximum allowable elevation difference in system piping (outlet and furthest horizontal pipe run/nozzle, or nozzles) is 30 ft. Max. 30’

23 ADS / PHX Piping Network: Layout
Percent of agent in pipe Max. 140% Percent of agent before 1st tee See chart in manual (page 4-6, Figure 4-1) Arrival time imbalance Max seconds Runout time imbalance Max. 1.0 second

24 ADS / PHX Piping Network: Pipe Sizes
Pipe sizes 1/2” through 6” are Listed/Approved Largest nozzle size is 2”

25 ADS / PHX Piping Network: Nozzles
Minimum nozzle pressure: 72 psi

26 ADS / PHX Piping Network: Hydraulic Calculation
Enter: Enclosure info Agent quantity Agent Source Pipe network Run main calculations Verify system acceptance

27 ECS / 9300/ 9300 vs. ADS / PHX: Design Comparison

28 ECS / 9300 vs. ADS / PHX Available Container Sizes: ECS / 9300
10 lb. to 900 lb. ADS / PHX 225 lb. to 1010 lb.

29 ECS / 9300 vs. ADS / PHX Tees: ECS / 9300 ADS / PHX Outlets horizontal
Bull Split: 50/50 to 70/30 Side Split: 70/30 to 90/10 ADS / PHX Any orientation Bull Split: 50/50 to 85/15 Side Split: 65/35 to (85/15 or 84/16)

30 ECS / 9300 vs. ADS / PHX Pipe Network: ECS / 9300 ADS / PHX
Max. percent of agent in pipe: 80% Max pipe elevation difference: 30 ft. Max arrival/runout imbalance: 0.8 s/2.0 s ADS / PHX Max. percent agent in pipe: 140% Max. pipe elevation difference: 30 ft. Max arrival/runout imbalance: 0.74 s/1.0 s

31 ECS / 9300 vs. ADS / PHX Nozzles: ECS / 9300 ADS / PHX
Coverage area: 40 ft. x 44 ft. Max. height: 16 ft. Min. height: 1 ft. (6”) ADS / PHX Coverage area: 46 ft. x 56 ft.

32 ECS / 9300 vs. ADS / PHX Nozzles: ECS / 9300 ADS / PHX
Mounting height to ceiling: 6 ± 2 inches 180° nozzle offset from wall: 12 ± 2 inches Nozzle orientation: pendant only ADS / PHX Mounting height to ceiling: 1/2 to 6 inches 180° nozzle offset from wall: 1 to 2 inches Nozzle orientation: Pendant (any height) or Upright (height<=1 ft. only)

33 ECS / 9300 vs. ADS / PHX Nozzles: ECS / 9300 ADS / PHX
Min. clearance to wall/obstruction: 6 ft. Min. clearance between nozzles: 10 ft. ADS / PHX Min. clearance to wall/obstruction: 3 to 4 ft. Min. clearance between nozzles: 6 ft.