Download presentation
Presentation is loading. Please wait.
Published bySheryl Fletcher Modified over 9 years ago
1
1 Pumping System Fundamentals 2014 Jeff Turner Systecore Inc. www.systecoreinc.com www.michigansteam.com
2
2 Overview Welcome Pumping Review Piping Review
3
3 Back to the Basics!
4
4 Pump Review Pump Sizing Pump Types Parallel Pumping Series Pumping Other Cautions
5
5 Pumping Sizing PRO-MAX ® Series Pumps
6
6 Affinity Laws
7
7 How does it work? Full Trim Impeller...
8
8 How does it work? Partially Trimmed Impeller...
9
9 Affinity Laws Capacity varies as the ratio of the diameters. Head varies as the ratio of the square of the diameters. Brake horsepower varies as the ratio of the cube of the diameters.
10
10 120 110100908070605040 3020 140 130 10 4 24 20 16 12 8 H.[FT] US.gpm 50% 60% 70% 75% 79% Adjustment of the Pumping Capacity Trimming Impellers? Why Not? Decreases Pump Efficiency One Way Trip VSD’s
11
11 Affinity Laws
12
12 Affinity Laws
13
13 What’s on a Pump Curve? Flow, gpm Head, feet Efficiency curves Impeller trims Horsepower curves NPSH Curve Pump speed Non-overloading value, minimum flow
14
14 Example Selection Point Flow = 1000 gpm Head = 90 feet What then? Pump Curve Booklet Software Websites Select: 5” End Suction Pump
15
15
16
16
17
17 Detail Report - ‘Standard Efficiency’ Motor Centrifugal Pump - Detail Report Pump Series: HVES Pump Size: E4N11A-2 Performance Rank: 1 Pump Speed: 1750 Total Capacity: 1000.0 gpm Total Head: 90.0 Feet Efficiency: 85.8 pct NPSH req: 11.7 Feet Discharge Size: 4.000 in Velocity: 18.03 fps Suction Size: 6.000 in Velocity: 11.10 fps Impeller Diameter: 10.815" PRV Size: Max BHP: 30.00 (at design: 67.21 pct) Pump Power, BHP: 26.7 ( 21.99 Kw) Motor Power, HP: 40.00 (BHP/HP = 0.74) Choose ‘non-overloading’ motor
18
18 Detail Report - ‘Standard Efficiency’ Motor
19
19 Detail Report - ‘High Efficiency’ Motor Motor: Century E+ AC MOTOR 230/460V SCE S324T DPE E600 40.000 HP 1770 RPM 4 poles 60 Hz 3 phase Voltage: 460 RPM: 1784.31 Eff: 93.38 AMP: 35.31 P.F.: 83.70 KVA: 28.14 Annual Operating Cost: $20627.78 for 8760.0 hours annually at $0.10/Kwh
20
20 Operating Cost Comparison Standard Efficiency$21,180 High Efficiency$20,628 Annual Savings$ 552 (@ $0.10/kWh)
21
21 Pumping system Sources of pressure drop Pipe Fittings Valves Coils Source (boiler or chiller)
22
22 System Curve Head varies as the square of the flow.
23
23 Impeller Change/Flow, Percent 0 10 20 30 40 50 60 70 80 90 100 010203040 5060708090100 Percent of Design Head Head System Curve
24
24 What Impacts the System Head? Actual component pressure drops Actual piping loses Present vs. future loads Safety Factors Heating vs. cooling flow
25
25
26
26 Jeff’s 1st Law Pumps are stupid. Pumps don’t know flow... Pumps don’t know temperature......it will deliver as much flow as it can based on the system resistance it sees.
27
27 Pump Over-heading Balance System? Close Valve @ Pump? Trim the impeller? Adjustable Frequency Drive?
28
28 Why Trim the Impeller? Centrifugal Pump - Detail Report Pump Series: HSC Pump Size: S5A12A-2 Performance Rank: 2 Pump Speed: 1750 Total Capacity: 1000.0 gpm Total Head: 55.0 Feet Efficiency: 77.58 pct NPSH req: 10.72 Feet Discharge Size: 4.000 in Velocity: 18.03 fps Suction Size: 6.000 in Velocity: 11.10 fps Impeller Diameter: 9.375" PRV Size: Max BHP: 18.19 (at design: 78.20 pct) Pump Power, BHP: 17.80 ( 13.39 Kw) Motor Power, HP: 20.00 (BHP/HP = 0.90)
29
29 Standard efficiency Why Trim the Impeller?
30
30 High efficiency Why Trim the Impeller? Motor: Century E+ AC MOTOR 230/460V SCE 256T DPE E401 20.000 HP 1700 RPM 4 poles 60 Hz 3 phase Voltage: 460 RPM: 1761.91 Eff: 90.28 AMP: 22.33 P.F.: 83.36 KVA: 17.79 Annual Operating Cost: $12991.58 for 8760.0 hours annually at $0.10/Kwh
31
31 Operating Cost Comparison- High Efficiency Motor + Trimming Impeller Std Eff Hi EffDifference @100 Ft$21180 $20628 $552 @ 55 ft 13362 12992 $370 Difference$ 7818 $ 7636 $8188
32
32 The Effects of Glycol on Pump Selection
33
33 Sample Problem The calculations are based on 1,000 gpm of water to the process, and as such designed the system utilizing 8 inch pipe & 6410 feet of pipe. A 5” pump is selected for 1000 gpm @ 90 feet of head. The correct impeller size is 10.8125” and the correct motor is 30 hp, nol.
34
8 in 1.56 6.42
35
6410 1.56 100
36
36 Centrifugal Pump - Detail Report Pump Series: HVES Pump Size: E4N11A-2 Performance Rank: 2 Pump Speed: 1750 Total Capacity: 1000.0 gpm Total Head: 90.0 Feet Efficiency: 85.8 pct NPSH req: 11.70 Feet Discharge Size: 4.000 in Velocity: 18.03 fps Suction Size: 6.000 in Velocity: 11.10 fps Impeller Diameter: 11.250" Max BHP: 30.00 (at design: 79.50 pct) Pump Power, BHP: 26.7 ( 23.54 Kw) Motor Power, HP: 40.00 (BHP/HP = 0.79) --------------------------------------------------------------------- Motor: Century E+ AC MOTOR 230/460V SCE S324T DPE E600 40.000 HP 1770 RPM 4 poles 60 Hz 3 phase Voltage: 460 RPM: 1783.06 Eff: 93.43 AMP: 37.29 P.F.: 84.79 KVA: 29.71 --------------------------------------------------------------------- Annual Operating Cost: $22070.62 for 8760.0 hours annually at $0.10/Kwh
37
37 Sample Problem The new process requires fluid which is 50% propylene glycol at 45°F. What is the new head requirement? What is the new impeller and motor size for these conditions?
38
45 50 1.05 13.21 0.00013542
39
1000 8 in. 6.42 2.29
40
6410 2.29 147
41
41
42
Centrifugal Pump - Detail Report Pump Series: 1510 Pump Size: 5G Performance Rank: 1 Pump Speed: 1750 Total Capacity: 1000.0 gpm Total Head: 147.0 Feet Efficiency: 82.99 pct NPSH req: 8.07 Feet Discharge Size: 5.000 in Velocity: 16.03 fps Suction Size: 6.000 in Velocity: 11.10 fps Impeller Diameter: 12.625" Max BHP: 51.68 (at design: 67.94 pct) Pump Power, BHP: 44.720 ( 33.35 Kw) Motor Power, HP: 60.00 (BHP/HP = 0.75) --------------------------------------------------------------------- Motor: Century E+ AC MOTOR 460V SCE Y364T DPE E716 60.000 HP 1775 RPM 4 poles 60 Hz 3 phase Voltage: 460 RPM: 1776.13 Eff: 92.79 AMP: 52.21 P.F.: 86.40 KVA: 41.60 --------------------------------------------------------------------- Annual Operating Cost: $31482.63 for 8760.0 hours annually at $0.10/Kwh
43
43 Sample Problem Results 5” pump must be selected for 1000 gpm @ 147 feet of head. The correct impeller size is 12.3125 inches and the correct motor is 60 horsepower (non-overloading).
44
44 Parallel Pump Operation Total system head 1/2 system flow
45
45 Two pumps in operation Each pump Head (ft) Flow (gpm) Parallel Pump Operation
46
46 Parallel 6” Pump Curve
47
47 90 80 70 60 50 40 30 20 10 0 100908070605040 3020 100 % Full Load HP % Flow Parallel C/S 2 Pumps Single C/S Single Parallel C/S Parallel Pump Operation
48
48 Series Pump Operation Total system flow 1/2 system head per pump
49
49 Flow (gpm) Two pumps in operation Head (ft) Single pump curve Series Pump Operation
50
50 Flow (gpm) Two pumps in operation Each pump Head (ft) Series Pump Operation
51
51 Pump Types
52
52 Basemounted Vertical Inline Vertical Turbine Types of Pumps
53
53 Typical Size Range by Pump Type
54
54 Pump types: –Basemounted Long & Close coupled, end suction Horizontal Split case, double suction –Vertical Inline Close coupled Spacer coupled Centrifugal Pump Construction
55
55 Type HVES Frame Mounted End Suction PRO-MAX ® Series Pumps Flows to 2,500 GPM Heads to 400 ft. TDH Delivery in 7 working days
56
56 PRO-MAX ® Series Pumps Flows to 2,500 GPM Heads to 450 ft. TDH Delivery in 7 working days Space saving design Type HVES Close Coupled End Suction
57
57 Type HSC Horizontal Split Case Flows to 6,000 GPM with larger ones on way Heads to 160 ft. TDH Optional 300 PSI W.P. Delivery in 7 working days PRO-MAX ® Series Pumps
58
58 Type VIL - Vertical Inline Pumps (Close Coupled) PRO-MAX ® Series Pumps Flows to 2,500 GPM Heads to 450 ft. TDH Delivery in 7 working days Space saving design
59
59 Lineshaft –88 Models –5-20” bowls –4 Styles –20 - 10,000 gpm –7 - 200 feet head Submersible –48 Models –5 - 14” bowls –40 - 2000 gpm –25 - 300 feet head Vertical Turbine Pumps
60
60 Important considerations: –Manufacturing standards/Quality (ISO 9001) –Serviceability, maintenance after turnover of project –Availability of replacement parts/motors –Effect of pump on system efficiency, flexibility for reconfiguration for future use. –ASHRAE 90.1 - optimizing energy use of pump –Pricing comparison between Basemount & V-I-L, an understanding the necessities for maintenance friendliness. Centrifugal Pump Construction
61
61 Important considerations: –Hytrel (orange) versus EPDM (black) Couplers –ANSI/OSHA Coupling Guard –HVAC Pumps Centrifugal Pump Construction
62
62 29 Recommended installation: –Basemount –Tie in with finished floor Centrifugal Pump Construction
63
63 31 Recommended installation: –Basemount –Tie-in with finished floor impractical –Spring/RSR isolation Centrifugal Pump Construction
64
64 Piping Review Why Variable Volume Primary-Secondary Piping Air Management Primary-Secondary Variations
65
65 Why Variable Volume? 3-Way Valve Systems:
66
66 Variable Volume Systems Permit Constant Volume Chiller Pumping Permit Variable Volume Load Pumping
67
67 Primary-secondary Pumping Return Supply Pump Controller Constant or Variable Speed Secondary Pumps Primary- secondary Common Chiller 3 Chiller 2Chiller 1 Constant Speed Primary Pumps Air Separator and Expansion Tank(s)
68
68 Jeff’s 2nd Law More Pumps is Better!
69
69 HD 125 100 75 50 25 150 255075100 % Design Flow Primary Pumps = V/V Secondary Pumps + Constant Flow Primary Pumps, only Pump Head Comparison
70
70 Pressure Absorbed by 2-way Valves
71
71 Graphical AOC Cost Comparison
72
72 Primary-secondary Pumping Return Supply Pump Controller Constant or Variable Speed Secondary Pumps Primary- secondary Common Chiller 3 Chiller 2Chiller 1 Constant Speed Primary Pumps Air Separator and Expansion Tank(s)
73
73 How does P-S Work? Supply C H I L L E R C H I L L E R C H I L L E R Return Primary-Secondary Common Primary Loop (Production) Secondary Loop (Distribution)
74
74 Common Pipe Design Supply Primary Loop (Production) Secondary Loop (Distribution) Primary-secondary Common Chiller 3 Pipe Diameters, Minimum Length Friction Loss < 1.5 ft Return Equal Diameter Balance and Check Valve
75
75 Common Pipe Design Overall Pressure drop in the common pipe shall not exceed 1.5 ft. A distance of 3 pipe diameters between the common tees is desirable. The velocity of the secondary return should not exceed 5 fps.
76
76 How does P-S Work? Primary Flow = Secondary Flow Secondary Flow > Primary Flow Primary Flow > Secondary Flow C H I L L E R C H I L L E R C H I L L E R Return Primary-secondary Common Supply Primary Loop (Production) Secondary Loop (Distribution)
77
77 Front Loaded Common Chiller 2, off Chiller 1, on
78
78 Common --No Flow Secondary Pumps 1500 0 CHWS Temp 45 o F CHWR Temp 55 o F ECW Temp 55 o F 1500 Chiller 2, off Chiller 1, on Production Flow = Distribution Flow
79
79 CHWS Temp Common -- 500 Secondary Pumps 1500 2000 1500 2000 0 47.5 o F CHWR Temp 55 o F ECW Temp 55 o F Mixing (1500 @ 45) + (500 @ 55) Chiller 2, off Chiller 1, on 2000 Distribution > Production
80
80 Increasing Supply Water Temperature - How Serious? Coil Selection - additional rows. Series Chiller - for the critical load. Chiller Temperature Reset... –1 to 3 % increase in operating cost per degree of reset.
81
81 Common -- 900 Secondary Pumps 3000 2100 1500 2100 1500 CHWS Temp 45 o F CHWR Temp 55 o F ECW Temp 52 o F Mixing (2100 @ 55) + (900 @ 45) (Flow in GPM) P/S Chiller Bridge - Front Loaded Common Chiller1, on Chiller 2, on Production > Distribution
82
82 Step Function Linear Function Return Primary/Secondary Common Supply Production Distribution Chiller 3 Chiller 2 Chiller 1 Primary-Secondary Relationship
83
83 Typical Load Profile
84
84 % Load % Time 100 80 60 40 20 100755025 Chiller 1 Chiller 2 1 1 22 Chiller 2, 60% Chiller 1, 40% Applying a 60/40 Chiller Split
85
85 % Load Time Approaching Flow = Load
86
86 Chiller Sequencing From Loads Common Pipe To Loads Production Secondary Pumps Distribution Chiller 2, off Chiller 1, on FSFS T S-S T S-R Chiller 3, off Primary Pumps T P-S T P-R FPFP
87
87 Back Loaded Common Secondary Pumps Chiller 2, off Chiller 1, on 1500
88
88 Common 0 Flow Secondary Pumps 1500 CHWS Temp 45 o F CHWR Temp 55 o F Chiller 2, off Chiller 1, on 1500 Production = Distribution
89
89 Common 500 gpm Secondary Pumps 1500 2000 1500 2000 0 CHWS Temp 47.5 o F CHWR Temp 55 o F 500 Mixing (1500 @ 45) + (500 @ 55) 500 Chiller 1, on Chiller 2, off Distribution > Production
90
90 Production > Distribution
91
91 Applying a Variable Speed Chiller
92
92 Hybrid Chiller Plant Primary- Secondary Common Return Supply Secondary Constant Speed Pumps Chiller 3Chiller 2Chiller 1
93
93 Air Management Air Removal versus Air Control
94
94 Types of Tanks Compression Tank Diaphragm Bladder
95
95 Compression Tank System Connection
96
96 Diaphragm Tank System Connection Air Charge
97
97 Bladder Tank System Connection Air Charge
98
98 Standard Tank Installation Tank Fitting PRV from system to system Rolairtrol Lock Shield Valve Pitch up PNPC
99
99 Diaphragm Tank Installation System Vent Rolairtrol From System Vent Diaphragm Tank Thermal Loop Lock Shield Valve PNPC To System
100
100 Standard or Diaphragm Tanks? Standard Water and air in contact May be larger, heavier Require tank fittings Rarely require repair Low initial cost Diaphragm/Bladder Impermeable barrier Probably smaller Require vents and thermal loop Repair difficult or impossible Higher initial cost
101
101 Pumping Away Chiller 3Chiller 2Chiller 1 Air Separator and Expansion Tank(s)
102
102 Tank Location Air Water Compression Tank Pump System Point of No Pressure Change
103
103 Pumping Away from the Tank System Pressure Pump Off Pump On Pump Pressure Difference PNPC Keep Short
104
104 Pumping Toward the Tank System Pressure Pump Off Pump On Pump Pressure Difference PNPC
105
105 Types of HVAC Pumping Systems 1. Primary-Secondary Pumped –Direct Return –Reverse Return 2. Primary-Secondary-Tertiary Pumped 3. Primary-Secondary-Tertiary Hybrid Pumped 4. Primary-Secondary Zone Pumped 5. Primary V/S Pumped
106
106 C H I L L E R C H I L L E R C H I L L E R Return Supply Pump Controller Secondary Pumps 1. Two Pipe Direct Return
107
107 Primary-Secondary Pumped
108
108 1a. Two Pipe Reverse Return
109
109 P-S with Reverse Return
110
110 Primary-secondary Variations 1. Primary-Secondary-Tertiary Pumped 2. Primary-Secondary-Tertiary Hybrid Pumped 3. Primary-Secondary Zone Pumped 4. Primary Variable Speed Pumped
111
111 2. Primary-Secondary-Tertiary C H I L L E R C H I L L E R Zone A Zone B Zone C Optional Variable Speed Pump DP Sensor Modulating Control Valves Secondary Pumps C H I L L E R Primary Pumps Tertiary Pumps Common Pipe Common Pipe
112
112 Tertiary Zone T3 T1 Load MV Load MV Load MV Common Pipe T2 Tertiary Zone Pump Tertiary Bridge Secondary Pump(s) Secondary Chilled Water Return Small Bypass Maintains Accurate Temperature Reading
113
113 3-way valve application
114
114 Three-way Valve System
115
115 Multi-zone application
116
116 District cooling application Individual building temperature control Static pressure isolation Return water temperature control Btuh Totalization Outdoor temperature reset Independent operation
117
117 District cooling application with GPX Independent pressure control Building operation isolation HVAC fluid isolation
118
118 Primary-Secondary-Tertiary
119
119 3. Primary-Secondary-Tertiary Hybrid
120
120 Primary-Secondary-Tertiary Hybrid
121
121 Parallel Pump Curves
122
122 Variable Speed Pump Curve
123
123 Tertiary Pump Bypass Piping Tertiary Pump Secondary Supply Secondary Return Common Low Pressure Drop Valve N/C N/O
124
124 C H I L L E R C H I L L E R Return Supply Common Primary Secondary Constant Speed Chiller Pumps VS Zone Pump Circuit Setter VS Zone Pump VS Zone Pump 4. Primary-Secondary Zone Pumping
125
125 Shared Piping
126
126 Primary-Secondary Zone Pumped
127
127 Primary Variable Speed Pumping AFD C H I L L E R C H I L L E R C H I L L E R Flow Meter Modulating Control Valve Two-position Control Valves DP Sensor Controller
128
128 AFD C H I L L E R C H I L L E R C H I L L E R Flow Meter, option Modulating Valve Two-position Control Valves DP Sensor Controller DP Sensor Primary Variable Speed Pumping
129
129 Design Considerations Size Bypass for Minimum Flow of Largest Chiller. Size Bypass Modulating Valve for Zone P. Size Chiller P Sensor for Minimum Chiller Flow. Sequence Chillers Based on P Switch or Temperature.
130
130 Consider this design if: System flow can be reduced by 30%. System can tolerate modest change in water temperature. Operators are well trained. Demonstrates a greater cost savings. High % of hours is at: –Part load. –Full load with low entering condenser water.
131
131 Do not use if: Supply temperature is critical. Constant volume. Existing controls are old or inaccurate. Operator unlikely to operate as designed. System is noise sensitive.
132
132 Primary Variable Speed Cautions System Volume Rate of Change Turn-down Ratio Chiller Selection Pump Selection Supply Water Temperature Controls Complexity Sensor Calibration Operator Ability
133
133 System Volume Dictates impact of rate of flow change. Chiller protection. –Freeze up. –Trip out.
134
134 Rate of Change Trane: –30% per minute flow change. –10% per minute flow change. York: STR = System Volume Design Flow –If greater that 15, 100% to 50% in 15 minutes. –If less than 15, 100% to 50% in 15 + (15 - STR) minutes.
135
135 Turn-down Ratio Chiller manufacturers publish 3 - 11 fps flow range. Nominal base of 7 fps desirable. Variation of 1 to 2 fps. Type and brand.
136
136 Chiller Selection Equal size chillers. –Redundancy. –Parts. –Maintenance. Unequal size chillers. –Control issues. –Flow issues –Additional equipment.
137
137 Pump Selection Equal size pumps. –Redundancy. –Parts. –Maintenance. Unequal size pumps. –Control issues. –Flow issues. –Premature failure.
138
138 Supply Water Temperature Dependant on : –System volume. –Rate of flow change. Application specific.
139
139 Controls Complexity Additional controls for the chillers Additional controls the pumps. Pumps operate on flow, temperature, and P. Chiller P.
140
140 Sensor Calibration Multi-sensor control: –Flow. –Temperature. – P. Maintenance. Calibration.
141
141 Operator Ability Within operators ability?. Training is mandatory. –Initial –Periodic. Systems too complex?
142
142 Problems in the Field Difficulty in system control. Chiller stability. Laminar flow - heat transfer issues. Flow confirmation. Real world.
143
143 Primary Variable Speed Pumping
144
144 Sensor Location and Pump Sequencing
145
145 Return Supply Pump Controller AFDs Differential Pressure Sensor Chiller 3 Chiller 2Chiller 1 Sensor Location
146
146 Return Supply Variable Head Loss Constant Head Loss Pump Controller AFDs Differential Pressure Sensor Chiller 3 Chiller 2 Chiller 1 Maximizing Variable Head Loss
147
147 Control Area Example
148
148 P AB+EF 20FT P Zone 1 20FT P BC+DE 20FT P Zone 2 20FT TDH = P AB + EF + BC + DE + P ZONE 2 = 60 FT Pressure Drops in Piping (Table 11-1)
149
149 Control Area Calculation
150
150 Control Area Curve
151
151 Applying Multiple Sensors
152
152 Return Supply Pump Controller AFDs Chiller 3 Chiller 2Chiller 1 WRONG! Single Point Pressure Sensor Single Point Pressure Sensor
153
153 Single Point Pressure Sensor
154
154 Staging Variable Speed Pumps in Parallel 1. Pump Speed 2. End-of-Curve Protection 3. Efficiency Optimization
155
155 Staging Based on Pump Speed A lag pump is staged on after the lead pump in reaches full speed. The pumps then operate in parallel, varying their speed together. As load decreases, the lag pump is destaged and the lead pump maintains setpoint once again. Required transmitter(s): Zone differential pressure only.
157
157 End of Curve Protection As the lead pump increases in speed, there may be a point prior to reaching full speed where the single pump could operate off its published end of curve. Rather than allow this to occur, the lag pump is staged on so as to share the flow requirements. Required transmitter(s): Zone differential pressure and a flow meter.
159
159 System Efficiency Optimization As the speed of the lead pump increases in relation to load, the overall efficiency of the pumping system (pump, motor, drive) also changes. For any given system there may be a range in speed where it is more efficient to run multiple pumps in parallel even though one pump could satisfy the load without end of curve concerns. Required transmitters: Zone differential pressure, flow meter, kilowatt meter, and system differential pressure transmitter.
Similar presentations
© 2025 SlidePlayer.com. Inc.
All rights reserved.