Presentation is loading. Please wait.
Published byTimothy Daniel Modified over 9 years ago
2
Modern electronics continue to be placed in denser packaging and smaller enclosures, often causing overheating problems Moisture and airborne dust, oil, dirt, and other contaminants can damage sensitive electronic equipment. Noren Products Incorporated Compact Cabinet Cooler Air-to-Air and Air-to-Water Heat Exchangers solve these problems by removing waste heat, cooling and re-circulating the clean air inside the cabinet. At the same time, it maintains the enclosure’s protective seal against contaminants. It comes in many different integrities including NEMA 12, 4, and 4X. 2
3
Stand Alone Easy Installation Easy to retrofit existing cabinets Low Maintenance Energy Efficient Long Lasting Below Ambient Cooling with Air-to-Water Units Corrosion Resistant Coating Hazardous Location Units UL/cUL Listed Units Wash-down Fans Stainless Steel Housings Custom Units Available ROHS Compliant Green Certified 3
4
Aerospace Computers & Servers Defense Electrical Systems Food & Beverage Industrial Applications Oil & Natural Gas Packaging Medical Paper & Bulk Renewable Energy Telecom & Radar Transportation Waste Water Treatment 4
5
Noren’s Unique Heat Pipe Core Makes Our Heat Exchangers So Efficient: Explanation: NOTE – Corrosive resistant core 6
6
Noren offers: Air-to-Air – Ambient Cooling to slightly above ambient temperature if sized properly o Drop in Model o Flush Mount model o Internal Mount Model Air-to-Water – Below Ambient Cooling to slightly above water temperature o No Exposed Fans o 1 GPM water source Choose the best unit for your application by using our online sizing program For metal cabinet: C= 36P/∆T-9A P = heat load (watts) A = surface area of cabinet (ft 2 ) ΔT = allowable rise in temperature above ambient (°F) C = Cabinet Cooler rating (found in table) Look in table to find the Cabinet Cooler with at least capacity (C). Example: Change information to reflect version from alternate presentation We want to cool a NEMA 12, 72” x 36” x 24” (183 x 92 x 61cm) uninsulated, floor mounted, sheet metal enclosure. We measured outside the cabinet was 90°F /32°C. Then, we calculated heat load (P) to be 600 watts. In this application, allowable temperature rise above ambient (∆T’) is 10°F, mean desired inside temperature is 108°F/42°C. Using C=36P/ ∆T’-9A, we find C=1566 watts. Therefore, we choose the CC2500F to meet the requirement. This cooler operates at current 1.2A @ 115VAC, mean total consumption 138 W. Selecting your Heat Exchanger 5
7
Only moving parts are the fans Standard Fan Offerings Range o 115VAC, 230VAC, 12VDC, 24VDC, 48VDC o 50/60hz, 49-56dba, -40 ° F - +160 ° F Wash Down Fan Features o Indoor hose down o Outdoor hose down - UV protected o Low power draw = 15watts – 32watts o IP 55 Specialty Fans Offered o Hazardous location certified o Smart fans o Military fans 6 Picture of fans
8
Drop In Drop in models extend into the panel from the side, top, front or back. These units have approximately ½ of the unique Noren heat pipe core extended into the cabinet and sealed at the mid flange. There is no air exchange between inside and outside. The fan attached to heat pipe core inside draws the heat over the core and moves the heat to the other end located on the outside. The fan attached to the outside portion of the core dissipates the heat into the ambient air. This removes the heat without allowing air or and contaminant inside. Features: Waste heat removal from 500 – 7,500 BTU´s/hr - Energy Efficient Low Maintenance Light Weight Easy to install Filters available if needed Fans - Low dBA UL Listed Type 12, NEMA 4 Custom units available 6
9
Flush Mount Model Flush Mount models remove waste heat from sealed electrical panels and enclosures using Noren heat pipe technology. The unit can installed on the side, top, front or back of the panel and does not take up space inside the enclosure. Approximately 1/2 of the unique heat pipe core is exposed to the inside of the cabinet and the other portion to the outside; totally sealed to maintain the proper NEMA integrity. These units are ideal for enclosures with little to no room for additional components and in a harsh environment. Features: Low Profile & High Power from 1,100 – 13,700 BTU´s/hr - Energy Efficient Low Maintenance Light Weight Easy to install Filters available if needed Standard SS304 or special ordered SS316 Fans - Low dBA UL Listed Type 12, 3R, 4, 4X, and HAZLOC Custom units available 8
10
Drop In Models Function of drop in : Cool electronics down to slightly above outside ambient air temperature UL Certified to maintain NEMA 12 seal Efficient Heat Pipe Core moves the waste heat Air is circulated inside cabinet to keep hot spots from forming Maintenance free cooling. Only moving part is the fan. Flange and Isoloss gasket keep contaminants out (properly torched on installation) Easy to install on top, door, sides, or back of cabinet o One person can usually install a standard application in less than an hour than one hour Causes no condensation like air conditioners Corrosion resistant. Anodized aluminum housing (standard), Additional salt water and chemical protection available (please inquire) Haz Loc models available Filters available Low power draw, 32 watts per fan results in low operating costs and no new electrical line required AC Fans = 115v 50/60 Hz or 220v 50/60 Hz fans, DC fans also available Fans -- allowable ambient temperature. -40°F to 160°F 6
11
Features: Cools below ambient 3,351; 8,557; 9,300 and 21,800 BTU’s/hr Low Maintenance No filters to clog No external fans, No filter necessary Energy efficient Flush mount Available in Stainless Steel AIR-TO-WATER Compact Cabinet Cooler technology removes waste from sealed electrical panel and other enclosures. Your panel remains sealed from outside contaminated air that can damage sensitive equipment. 9
12
Features: Cools below ambient 3,351; 8,557; 9,300 and 21,800 BTU’s/hr Low Maintenance External fans Energy efficient Flush mounts on the outside 10
13
1. Rated Cooling: 980 Watts (mounted to an uninsulated 24” x 24” x 16” cabinet with 1 GPM of water at 20°C, 40°C ambient air and 60°C cabinet air temperature ) 2. Designed for surface mounting on the outside of cabinet 3. Aluminum housing (color is black) or stainless steel 4. External water inlet and outlet connections 5. Equipped with mounting gasket to maintain air tight seal 6. “P” unit is pressure tested to assure water tight seal 7. UL / cUL listed units (UL file # SA9567) 8. Available with 115VAC, 230VAC, and 12VDC, 24VDC, 48VDC fans 9. Vertical mounting 10. Coolant water pressure: This unit is pressure tested to 100 PSI; safe working pressure is 60 PSI 11. Recommended coolant flow rate (gallons per minute): 1 GPM 12. For design, quote, and sizing assistance please ask our application engineer 11
14
Noren Air-to-Air Unit Purchase price:$1,400 Max install costs:$1,550 Operating cost/yr:$106 ______________________ Total Annual Cost:$261 Air Conditioner Purchase price:$3,340 Max install costs:$3,917 Operating cost/yr:$825 ______________________ Total Annual Cost:$1,608 $1,347 in Annual Savings 12
15
Noren Air-to-Air Unit Purchase price:$1,400 Max install costs:$1,550 Operating cost/yr:$111 ______________________ Total Annual Cost:$266 Compressed Air Purchase price:$440 Max install costs:$571 Operating cost/yr:$4,631 ______________________ Total Annual Cost:$4,688 $4,421 in Annual Savings 13
16
Noren Air-to-Water Unit Purchase price:$1,275 Max install costs:$1,423 Operating cost/yr:$59 ______________________ Total Annual Cost:$202 Air Conditioner Purchase price:$3,340 Max install costs:$3,917 Operating cost/yr:$825 ______________________ Total Annual Cost:$1,608 $1,406 in Annual Savings 14
17
Noren Air-to-Water Unit Purchase price:$1,275 Max install costs:$1,423 Operating cost/yr:$60 ______________________ Total Annual Cost:$203 Compressed Air Purchase price:$440 Max install costs:$571 Operating cost/yr:$4,631 ______________________ Total Annual Cost:$4,688 $4,485 in Annual Savings 15
18
Benefits Include: Minimizes down time Cost Savings Easy to retrofit Easy to design into existing applications Worry free operation Wide selection Easy to size on website Large Selection of heat removal copper units Compact Cabinet Solutions solve issues such as high energy costs Open cabinet doors with fans Dripping water from air conditioners Wash-down areas Replacing air compressor coolers Dirty and dusty environments NEMA 4 and 4X conditions High ambient conditions Toxic Corrosion Resistant Hazardous Locations Customized for special requirement 16
19
Air-to-Air Flush Mount Units for Industrial Application 17
20
Air-to-Water Unit for Waste Water Treatment Facility 18
21
Air-to-Air Flush Mount Unit for Custom Radar Application 19
22
Air-to-Water Unit for Custom Pump Station Application 20
23
Noren Products Inc. 1010 O’Brien Drive Menlo Park CA, 94025 650.322.9500 sales@norenproducts.com GSA# GS-07F-0619W