1
Invensys Controls Europe An Invensys Company EWCM 41x0 family New 32x74
2
Product description Product architecture Panel mounting, case dimensions 32x74x75 mm (including cables) Case plastic in ABS, UL-94 V0; Power supply: 12 Vac 50/60 Hz; Removable connectors (outputs and inputs); RTC on board (for alarm history) Number of compressors adjustable by parameter (up to 4); Advanced GUI 4 digits LED display + 18 (colour) icons and leds to improve “easy to use” Human Interface Advanced control algorithms Historical data storage, inverter management, etc. Inverter Control of Compressors Inverter Control of Fans New compressors rack controller
3
Technical information Technical information: Microprocessor:8bit 14.7MHz RAM: 4 Kbyte SRAM FLASH:128 Kbyte COM1UART 1, TTL for local conn. or monitoring connection I/O’s resources: 4 A.I. 2 temp. + 2 config. (NTC/V/I or D.I.) 5 D.I.all SELV (Safety Extra Low Voltage) 4 or 5 D.O. 2A, 230Vac, SPST* 0 or 1 triac onboard2A, 230Vac 1 or 2 pulse outputs 0 or 1 A.O.SELV, V or I Power supply: 12Vac +/-10%, 50/60Hz, no insulation provided
4
Physical layout Panel Mounting Solution Bus adapter Copy Card 75mm
5
4120 connection schemes
6
4180 connection schemes
7
HMI: Display and Icons Fan LED Prog Menu Alarm Icon Heating mode Cool Mode Display is Temperature (C/F) Bar / Psi Display is pressure Compressor ON Not configured LED (for future) Go into machine status menu Access to subfolders Set parameters value 5 secs pressure goes into Prog. menu Increase parameter value Navigate through folders 5 secs pressure goes into band menu Decrease parameter value Navigate through folder 5 secs pressure goes into setpoint menu Exit from menues 5 secs pressure goes into a menu to select standard visualization
8
Compressors management. DIGITAL Can be used for homogeneous compressors up to 4; Higher is the distance from the set, higher is the number of step running; Start and stop values are calculated automatically dividing the band equal parts (=number of steps) Advanced policy on compressor management (Balancing / saturation / fixed sequence);
9
Compressors management. CONTINUOUS It’s a PROPORTIONAL control based on low pressure probe; Two Cut-Off function available (for minimum speed and for saturation);
10
Fans management. Uses proportional algorithm; In Chill mode can activate also “pre-ventilation” algorithm (fan speed at max before to turn on a compressor);
11
Fans management. CONTINUOUS At every start-up fans will be forced to spin at max power; If pre-ventilation is on, before to turn a compressor on fans are forced at a maximum speed.
12
Advanced functions The controller can be turned On/Off by: Keyboard; Digital input; Working hours: Thanks to the installed RTC system can record working hours; Historical Alarm: Thanks to the RTC the system can record the time of alarms;