Download presentation
Presentation is loading. Please wait.
Published byPierce Harper Modified over 9 years ago
1
DIGITAL DIFFERENTIAL RELAYS FOR TRANSFORMER PROTECTION USING WALSH SERIES AND LEAST SQUARES ESTIMATORS Ali Reza FEREIDUNIAN*, Ali Reza FEREIDUNIAN*, Mansooreh ZANGIABADI*, Mansooreh ZANGIABADI*, Majid SANAYE-PASAND*, Gholam POURNAGHI** * : ECE Dep., Faculty of Engg., University of Tehran,Tehran, IRAN *:* Kerman Regional Electric Company (KREC), Kerman, IRAN
2
Differential Protection The fundamental principle of differential protection: sum of the currents entering a device through normal paths should be zero: Kirchhoff's Current Law (KCL). If the currents enter (or leave) through abnormal paths, namely fault paths, then the sum of the currents through normal paths will not be zero.
3
Differential Protection Illustration
4
Problems in transformer differential protection: inrush current, CT inaccuracy, CT saturation, over-excitation. These problems produce fault trips (fault alarm when there isn’t any trip) or no alarm when there is a trip in transformer protection function
5
DIFFERENTIAL RELAY IMPLEMENTATION: Current Sensor (CT): converts large amounts of current to small amounts Data Acquisition System: gathering data Filter: anti aliasing Pre-processor: scaling and so on Estimator: estimating peak & phase Decision Maker (Classifier): fault/no fault
6
Effect of CT Saturation on a Sinusoidal Current:
7
WE HAVE USED TWO METHODS: FOR ESTIMATING PEAK AND PHASE OF INPUT WAVE.
8
Walsh coefficients :
9
Walsh Series (Ctd): W=A * F F=A-1*W where F=[ F0 F1 F2 F3 F4 F5 F6 F7 F8] A-1=AT
10
Least Squares : A*X = B E = A*X – B = LPI(A) * B LPI(A) =
11
Sampling: 12 point window (for half cycle estimation) or 24 points (for full cycle estimation) with with 24 sample/cycle sampling system
12
Least square frequncy response for fundamental frequency
13
The Decision Space
14
Inrush Pattern Recognition A significant second harmonic: Inrush Current Pattern Recognition
15
A CASE STUDY Real recorded data: Transformer internal fault, Transformer external fault, Transformer inrush current
16
High and Low Voltage Side Currents for External Fault
17
High and Low Voltage Side Currents for Internal Fault
18
High and Low Voltage Side Currents for Inrush Current
19
Three Phases Differential Currents in External Fault
20
. Three Phases Differential Currents in Internal Fault
21
Three Phases Differential Currents in Inrush Current
22
Decision Space in External Fault for three Phases
23
Decision Space in Internal Fault for Three Phases
24
Decision Space in Inrush Current for Three Phases
25
Second/Fundamental Harmonic Ratio for External Fault
26
Second/Fundamental Harmonic Ratio for Internal Fault
27
Second/Fundamental Harmonic Ratio for Inrush Current
28
General Trip Alarm for External Fault
29
General Trip Alarm for Internal Fault
30
General Trip Alarm for Inrush Current
31
Summary A digital differential relay for transformer protection was presented. Two estimator systems: Walsh series and least squares algorithms were formulated and designed. The differential protection decision maker subsystem was introduced. Current signals harmonic components and second harmonic restraint concept were utilized in decision maker subsystem.
32
Conclusion In a practical case study, the designed relay performance was tested under three real circumstances: external fault, internal fault and inrush current. It was shown -using graphs and illustrations- that the presented relay issues trip alarm for transformer internal fault, and does not issue trip alarm for external fault and inrush current situations.
33
Conclusion (Ctd) It were seen that both estimation algorithms perform their job correctly. Walsh series acts better than least squares algorithm, especially on second harmonic estimation. An anti alias filter (for example a Butterworth one) will improve response of the estimator.
Similar presentations
© 2025 SlidePlayer.com. Inc.
All rights reserved.