1 Rosemount 485 Annubar® Flowmeter Series

2 Rosemount 485 Annubar Flowmeter How It Works
Impact Pressure (40%) Total DP Blockage / Suction Pressure (60%) Static Pressure (40/60 relationship not the same for all APT’s) HIGH LOW Velocity Profile DP(hw) = PH(avg.) - PL(avg.) Flow Impact area

3 Rosemount Invented the Averaging Pitot Tube and Continues to Innovate
1970 1978 1984 1998 2002 Integral thermowell available in all sizes Innovative upstream slot for comprehensive averaging T-shaped sensor creates large stagnation zones on backside to reduce noise

4 T-Shape Improves Accuracy and Reduces Plugging
Provides a more accurate measurement than traditional APTs

5 Flow Testing Results Available on Rosemount.com
±0.75% Accuracy Document Number

6 Rosemount Annubar Flowmeters
Pak-Lok Patented compression design firmly secures the Annubar sensor to the opposite wall of the pipe. Rated up to 600# ANSI. Flanged With Opposite Side Support Meets the requirement of high pressure applications. Available up to 2500# ANSI. Flange-Lok Combines Pak-Lok compression mechanism with a mounting flange Flo-Tap Can be hot-tapped without interruption of the flow. Easily removed for cleaning or line pigging. Available up to 600# ANSI.

7 Flo-tap Mounting Can Be Used in Applications with Dirty Fluids
Can be easily removed for cleaning or line pigging and re-installed

8 Annubar APT has Lowest Permanent Pressure Loss of Any Primary Element
On this one, we need to take out the name optima and change it to the new Annubar Minimizes Pumping and Compression Costs

9 Larger Line Size, Larger Installation Savings with Annubar Technology
72 inch $23,451 Savings 36 inch $9,765 Savings 14 inch $3,513 Savings 8 inch $1,645 Savings 6 inch $1,313 Savings

10 Total Installed Cost Comparison
Annubar APTs require less material Small size, less weight 24” Annubar < 45 lbs.* Total installed costs are lower for Annubar Flowmeters, including: Shipping costs Labor time and cost Lifting equipment Less Straight Piping Needed *For 150# Flanged version ~70lbs, Pak-lok ~45lbs as shown with transmitter

11 Annubar Technology Reduces Straight Run Requirements
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 .67 Beta Orifice Rosemount Annubar 0.75% Accuracy .67 Beta Orifice with 19-Tube Bundle Elbow Mounted Annubar 3.0% Accuracy 0.1% Repeatability

12 Less Welding and Pipe Fabrication Required
Annubar® 4” linear (100mm) of weld 63” linear (1600mm) of weld 10” (250mm) line Orifice

13 Pak-lok Mounting Installs in 3 Easy Steps

14 Integrated Flowmeters Reduce Installation and Maintenance Time and Cost
Annubar Installation Traditional Orifice Plate Installation Assembly is factory leak tested Few leak points at time of installation Leak points at every fitting Factory Checked 1 leak = $184/year in wasted pump energy Energy to compress fluid escaping through leak is wasted and costs electricity$$ U.S. Dept. of Energy Office of Industrial Technologies 1/16th” leak assumed

15 Choose Any Transmitter and We Will Integrate into a Flowmeter
Rosemount 3051SFA Annubar Flowmeter Rosemount 3051S MultiVarible™ Mass Flow Transmitter Rosemount 3051S Rosemount 3051CFA / 2051CFA Annubar Flowmeter Rosemount 3051/2051

16 Complete Portfolio of Fully Integrate Flowmeters
Rosemount 3051SFA Rosemount 3051CFA Wireless Advanced Diagnostics MultiVariable Mass Flow Rosemount 2051CFA Flowmeters Arrive Fully Assembled, Configured and Leak Tested and Ready to Install Capability

17 Accurate Flow Measurement Requires Dynamic Compensation
MultiVariable Combines Three Transmitters into One with Advanced Computations Rosemount 3051SMV 3 Measurements in 1 Transmitter Real-Time, Fully Compensated Flow 1 Differential Pressure Transmitter 2 Pressure Transmitter DP DP DP Coefficients vary with all three measurements P P P T T T T T Accurate Flow Measurement Requires Dynamic Compensation 3 Temperature Transmitter

18 MultiVariable™ Transmitter Provides Real-Time Full Compensation of Mass and Energy Flow
Dynamically corrects for all variables – 22 updates/second We Calculate: Density Viscosity Velocity Beta Ratio Enthalpy Gas Expansion Discharge Coefficient Velocity of Approach Reynolds Number Compressibility Factor We Measure: Differential Pressure Static Pressure Process Temperature You Receive: You Enter: Mass Flow Energy Flow Volumetric Flow Totalized Flow Process Temperature Differential Pressure Static Pressure Process Fluid Primary Element Line Size *Includes AGA DCM and GCM Methods for flow calculation